https://www.phoenixcontact.com/us/products/2308098
09/03/2014Page1/4
Universal current transducer-MCR-SL-CUC-600-I-2308098
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universal current transducer, for measuring DC, AC, and distorted currents, 0 ... 600 A input current, 4 ... 20 mA
output
The MCR-SL-CUC-100-I is illustrated
Product Features
Variable mounting on DIN rail and mounting plate
Simple connection technology thanks to COMBICON plug-in connection terminal blocks
Compact dimensions also enable distributed use
3-way isolation
Universal current measurement, no shunt required
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 297.6 GRM
Custom tariff number 90303310
Country of origin Japan
Technical data
Dimensions
Width 90 mm
Height 33.8 mm
Depth 85 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Input data
https://www.phoenixcontact.com/us/products/2308098
09/03/2014Page2/4
Universal current transducer-MCR-SL-CUC-600-I-2308098
Technical data
Input data
Input current range 0 A ... 600 A
Overload capacity 3 x IIN
Frequency measuring range 20 Hz ... 6000 Hz (0 Hz)
Connection method Cable design: 32 mm diameter
Output data
Output name Current output
Current output signal 4 mA ... 20 mA
Max. output current < 25 mA
Load/output load current output < 300 Ω
Switching output
Output name No switching output
Power supply
Nominal supply voltage 24 V DC
Supply voltage range 20 V DC ... 30 V DC
Max. current consumption (30 + IOUT) mA
Connection data
Conductor cross section solid min. 0.25 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Stripping length 10 mm
General
Maximum transmission error <± 1 % (of final value)
Temperature coefficient, typical 0.02 %/K (0 ... 60°C)
0.04 %/K (-40 ... 65°C)
Linearity error <± 1 % (From the range end value)
Step response (10-90%) 150 ms
Surge voltage category III
Pollution degree 2
Rated insulation voltage 300 V AC
Test voltage input/output 3.5 kV (50 Hz, 1 min.)
Test voltage input/power supply 3.5 kV (50 Hz, 1 min.)
Noise emission EN 61000-6-4
https://www.phoenixcontact.com/us/products/2308098
09/03/2014Page3/4
Universal current transducer-MCR-SL-CUC-600-I-2308098
Technical data
General
Noise immunity EN 61000-6-2
Color green
Housing material Frianyl B63 V0 GV30
Conformance CE-compliant
Classifications
eCl@ss
eCl@ss 4.0 27200303
eCl@ss 4.1 27200303
eCl@ss 5.0 27200303
eCl@ss 5.1 27210902
eCl@ss 6.0 27210902
eCl@ss 7.0 27210902
eCl@ss 8.0 27210902
ETIM
ETIM 3.0 EC002475
ETIM 4.0 EC002048
ETIM 5.0 EC002475
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Drawings
https://www.phoenixcontact.com/us/products/2308098
09/03/2014Page4/4
Universal current transducer-MCR-SL-CUC-600-I-2308098
Dimensioned drawing
90
Ø32 33,8
70
Circuit diagram
IN 1.3
1.4
1.2
1.1
GND
NC
OUTI
+24VDC
ADC
µC
DAC
I
Schematic diagram
A
B
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com