Specications TP Series
All gures typical at 77°F (25°C) unless
otherwise stated
Maximum surge current
20kA peak current (8/20µs waveform)
Leakage current
Less than 10µA at maximum working voltage
Working voltage
35 VDC maximum
Bandwidth
1MHz
Resistance
No resistance introduced into loop
Ambient temperature limits
-40°C to +80°C (working)
-40°F to +185°F (working)
-40°C to +85°C (storage)
-40°F to +185°F (storage)
Humidity
5% to 95% RH (non-condensing)
Electrical connections
TP48
3 flying leads (line1, line 2 & ground)
TP48 3 Wire
4 flying leads (+ve, -ve, signal & ground)
TP48 4 Wire
5 flying leads (+ve, -ve, signal +ve, signal -ve, ground)
Wire size 32/0.2 (1.0mm2, 18 AWG)
Lead length 250mm (minimum)
Casing
ANSI 316 stainless steel hexagonal barstock, male thread
Threads
TP48-3-N & TP48-4-N 1/2” NPT
TP48-3-I & TP48-4-1 20mm ISO (M20 x 1.5)
TP48-3-G & TP48-4-G G 1/2” (BSP 1/2”)
Weight
175g (6.2oz)
Dimensions
See Figure 1
EMC compliance
To Generic Immunity Standards EN50082, part 2
for industrial environments
Electrical safety
EEx ia IIC T4, Ceq=O, Leq=0; the unit can be connected
without further certification into any intrinsically safe loop
with open circuit voltage <60V and input power <1.2W.
EEx d IIC T4; the unit is apparatus-approved to flame proof
(explosionproof) standards, and can be fitted into a similarly
approved housing.
The TP Series protection network
consists of
high-power, solid-state electronics and a gas-lled
discharge
tube capable of diverting 20kA impulses.
The whole unit is encased in an ANSI 316 stainless
steel housing, threaded for the common conduit
entries used on process transmitters. Versions are
available for 1/2” NPT, 20mm ISO, and G1/2”
(BSP 1/2 inch) threaded entries.
Country (Authority) Standard Certificate/File No. Approved for Product
EC (BASEEFA) EN 50014:1997 + BASEEFA04ATEX0251X EEx ia IIC T6 (Tamb = -40 to 60°C) TP48-X-Y-Z
Amendments 1 & 2 EEx ia IIC T5 (Tamb = -40 to 85°C)
EN 50020:1994, EN 50284:1999 EEx ia IIC T4 (Tamb = -40 to 60°C)
EC (BASEEFA) EN 50014:1997 + BASEEFA04ATEX0251X EEx d IIC T6 (Tamb = -40 to 60°C) TP48-X-Y-Z
Amendments 1 & 2 EEx d IIC T5 (Tamb = -40 to 80°C)
EN 50018:2000 + Amendment 1 EEx d IIC T4 (Tamb = -40 to 85°C)
Atex Directive BS EN 50021:1999 TML02ATEX0032X Ex n II T6 (-40°C<Tamb<+60°C) TP48-X-Y-Z
94/9/EC EEx n II T5 (-40°C<Tamb<+85°C)
USA (FM) Class Nos. 3600 3022293 Intrinsically Safe: TP48-X-Y-Z
(1998), 3610 (1999), I, II, III/1/A-G, I/0/IIC
3611 (1999), 3615 Explosionproof: I/1/A-D
(1989), 3810 incl. Non incendive: I/2/A-D, I/2/IIC
Supp 1 (1995-07) Dust ignition proof: II,III/1/EFG
(1989-03), Special protection: II/2/FG
ANSI/NEMA 250
(1991),
ISA-S12.0.01 (1999)
Canada (FM) C22.2 No. 157 3025374 Intrinsically Safe: TP48-X-Y-Z
C22.2 No. 213 I, II, II/1/A-G, I/O/IIC
C22.2 No 142 Explosionproof: I/1/A-D
C22.2 No. 94 Nonincendive: I/2/A-D, I/2/IIC
C22.2 No. 30 Dust ignition proof: II, III/1/EFG
Special protection: II/2/FG
Global IEC 60079-0:2004 IECEx BAS 07.0045X Ex ia IIC T4/T5/T6 TP48-X-Y-NDI
IEC 60079-11:2006 Ex tD A20 IP6X T85°C/T100°C/
IEC 61241-0:2004 T135°C
IEC 61241-1:2004
Key: X = 3 or 4 or blank, Y = N, I or G, Z = NDI
Approvals
The TP units are designed for mounting directly into
an unused conduit entry on a process transmitter
housing. Generally, two such entries are provided,
one of which is used for the loop wiring. On the
unused entry, the blanking plug or other closure
device is removed and an appropriately threaded TP
screwed into its place. The transmitter specication
should provide information indicating the required
thread type. TP units can be installed using thread
adaptors if necessary, including certied adaptors in
hazardous area applications.
For applications where two conduit entries are
not provided or where both are used for electrical
connections, TP units can be housed in conventional
conduit hub or junction boxes, provided access
to the loop terminals is possible. Figure 2 shows
connection details for 3 & 4 wire process transmitter.
Installation
Figure2
Dimensions
Lead length
9.85” (250mm)
minimum
(75mm)
1.07”
(27mm)
2.17”
(55mm)
0.91”
(23mm)
Dimensions across ats 0.91” (23mm)
Figure 1
Description Part No.
Non-certified SPD - 1/2” NPT thread TP48N
Non-certified SPD - 20mm ISO thread TP48I
Non-certified SPD - G 1/2” (BSP 1/2 inch) TP48G
Non-certified SPD - 1/2” NPT thread TP483N
Non-certified SPD - 20mm ISO thread TP483I
Non-certified SPD - G 1/2” BSP 1/2 inch TP483G
Non-certified SPD - 1/2” NPT thread TP484N
Non-certified SPD - 20mm ISO thread TP484I
Non-certified SPD - G 1/2” BSP 1/2 inch TP484G
Certified SPD - 1/2” NPT thread TP48NNDI
Certified SPD - 20mm ISO thread TP48INDI
Certified SPD - G 1/2” (BSP 1/2 inch) TP48GNDI
Certified SPD - 1/2” NPT thread TP483NNDI
Certified SPD - 20mm ISO thread TP483INDI
Certified SPD - G 1/2” - BSP 1/2 inch TP483GNDI
Certified SPD - 1/2” NPT thread TP484NNDI
Certified SPD - 20mm ISO thread TP484INDI
Certified SPD - G 1/2” - BSP 1/2 inch TP484GNDI
Technical Data
Nominal voltage Un
Rated voltage (MCOV) Uc
Nominal current In
Nominal discharge current (8/20μs) isn
Max discharge current (8/20μs) Imax
Lightning impulse current (10/350μs) Iimp
Residual voltage @ isn Up
Voltage protection level @ 1kV/μs Up
Bandwidth fG
Capacitance C
Series resistance R
Operating Temperature Range
Category tested
Overstressed fault mode in=3kA
Impulse durability (8/20μs)
Degree of protection
AC durability
Service conditions
TP48 Series
35V
58V
---
3kA
20kA
2.5kA
95V
L-G 500V
<76V
1MHz
100pF
---
-40°C to +85°C
A2, B2, C1, C2, C3, D1
12kA
10kA
IP66
1Arms, 5T
80kPa - 160kPa
5% - 95% RH
Ordering Data
182