Power Capacitors B32343C
Power Factor Correction
Construction
Dielectric: Polypropylene film
Non PCB, biodegradable soft resin
Extruded round aluminum can with stud
Provided with discharge resistors
Features
Three phase, delta connected
Naturally air cooled or forced air cooling
Indoor mounting
Typical applications
PFC and detuned systems
Terminals
Fast-on terminals
Mounting parts
Threaded stud at bottom of can
Max. torque = 4 Nm for M8 (Ø 53 mm)
Max. torque = 10 Nm for M12 (Ø 63.5 mm)
FK PM PFC December 2004
Page 1 of 6
Power Capacitors B32343C
Power Factor Correction
Technical data and specifications
Standard IEC 831-1+2, IS: 13340/41
UL 810 5th edition, cUL file E106388
Rated capacitance CN & QR According to dimensions table
Tolerance (%) -5 / +10
Rated voltage UR According to dimensions table
Rated frequency fR 50/60 Hz
Mean life expectancy Up to 100 000 operating hours
Maximum ratings
Maximum permissible overvoltage Umax UR + 10% (up to 8 h daily)
UR + 15% (up to 30 min daily),
UR + 20% (up to 5 min daily)
UR + 30% (up to 1 min daily)
Maximum permissible overcurrent Imax 1.5 x IR (IR: rated current), including combined effects
of harmonics, overvoltages and capacitance
Number of switching operations Max. 5 000 switchings per year according IEC 831
Transient inrush current (max) IS Up to 200 x IR
Losses:
Dielectric
Total
< 0.2 W/kvar
< 0.45 W/kvar
Test voltage, terminal/terminal UTT 2.15 x UR , 10 s
Test voltage, terminal/case UTC 3 000 VAC, 10 s
Temperature class -25/D
Max. temp. 55 °C
Max. mean 24 h = 45 °C
Max. mean 1 year = 35 °C
Safety Self-healing technology, overpressure disconnector,
maximum allowed fault current 10 000 A in accordance
with UL 810-standard
Case/shape Aluminum/cylindrical
Enclosure IP00, IP20, optionally IP54
Permissible maximum humidity 95%
Maximum permissible altitude 4 000 m above sea level
Mounting position Upright
Mounting and grounding Threaded M8 (4 Nm / Ø 53 mm),
M12 (10 Nm / Ø 63.5mm)
FK PM PFC December 2004
Page 2 of 6
Power Capacitors B32343C
Power Factor Correction
Dimensional drawing
KLK1670-2
11,8±0,5
l±216
M12
d
Marking
±2 +lExpansion to α
FAST-ON
Terminal 6,35 x 0,8
Creepage distance 10.5 mm (ø 53)
10.0 mm (ø 63.5)
Clearance 13.0 mm (ø 53)
16.5 mm (ø 63.5)
Diameter (ø) 53 mm
63.5 mm
Expansion α max. 12 mm
Mounting
M12 M8
(ø 63.5 mm) (ø 53 mm)
Torque T=10 Nm T=4 Nm
Toothed J12.5 J8.0
washer DIN 6797 DIN 6797
Hex nut BM12 BM8
DIN 439 DIN 439
FK PM PFC December 2004
Page 3 of 6
Power Capacitors B32343C
Power Factor Correction
Rated voltage: 230 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
Ordering code
MKP230-D-0.5 0.5 1.3 0.6 1.6 3 * 10 53 x 114 0.30 B32343C2002A530
MKP230-D-0.7 0.7 1.9 0.9 2.3 3 * 15 53 x 114 0.30 B32343C2002A730
MKP230-D-1.0 1.0 2.5 1.2 3.0 3 * 20 63.5 x 129 0.30 B32343C2012A030
MKP230-D-1.5 1.5 3.8 1.8 4.6 3 * 30 63.5 x 129 0.40 B32343C2012A530
Rated voltage: 400 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
Ordering code
MKP400-D-1.0 1.0 1.4 1.2 1.7 3 * 7 53 x 114 0.30 B32343C4012A000
MKP400-D-1.5 1.5 2.2 1.8 2.6 3 * 10 53 x 114 0.30 B32343C4012A500
MKP400-D-2.0 2.0 2.9 2.4 3.5 3 * 13 63.5 x 129 0.40 B32343C4022A000
MKP400-D-2.5 2.5 3.6 3.0 4.3 3 * 17 63.5 x 129 0.40 B32343C4022A500
MKP400-D-5.0 5.0 7.2 6.0 8.6 3 * 33 63.5 x 129 0.40 B32343C4052A000
Rated voltage: 415 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
Ordering code
MKP415-D-1.0 1.0 1.4 1.2 1.6 3 * 6 53 x 114 0.30 B32343C4012A010
MKP415-D-1.5 1.5 2.1 1.8 2.4 3 * 9 53 x 114 0.30 B32343C4012A510
MKP415-D-2.0 2.0 2.8 2.4 3.4 3 * 12 53 x 114 0.40 B32343C4022A010
MKP415-D-2.5 2.5 3.5 3.0 4.2 3 * 15 63.5 x 129 0.40 B32343C4022A510
MKP415-D-5.0 5.0 7.0 6.0 8.4 3 * 31 63.5 x 154 0.40 B32343C4052A010
Rated voltage: 440 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
Ordering code
MKP440-D-0.9 0.9 1.2 1.0 1.3 3 * 5 53 x 114 0.30 B32343C4011A040
MKP440-D-1.0 1.0 1.3 1.2 1.6 3 * 6 53 x 114 0.30 B32343C4012A040
MKP440-D-1.2 1.2 1.6 1.5 2.0 3 * 7 53 x 114 0.30 B32343C4011A540
MKP440-D-1.5 1.5 2.0 1.8 2.3 3 * 8 53 x 114 0.30 B32343C4012A540
MKP440-D-2.1 2.1 2.7 2.5 3.3 3 * 11 53 x 114 0.40 B32343C4021A540
MKP440-D-2.5 2.5 3.3 3.0 3.9 3 * 13 63.5 x 129 0.30 B32343C4022A540
MKP440-D-4.2 4.2 5.5 5.0 6.6 3 * 23 63.5 x 129 0.40 B32343C4051A040
MKP440-D-5.0 5.0 6.5 6.0 7.8 3 * 27 63.5 x 154 0.50 B32343C4052A040
Rated voltage: 480 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight Ordering code
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
MKP480-D-1.5 1.5 1.8 1.8 2.2 3 * 7 63.5 x 129 0.40 B32343C4012A580
MKP480-D-2.0 2.0 2.4 2.4 2.9 3 * 9 63.5 x 129 0.40 B32343C4022A080
MKP480-D-2.5 2.5 3.0 3.0 3.6 3 *11 63.5 x 129 0.40 B32343C4022A580
FK PM PFC December 2004
Page 4 of 6
Power Capacitors B32343C
Power Factor Correction
Rated voltage: 525 VAC, 50/60 Hz, delta connection
Type 50 Hz 60 Hz CN d x h Weight
Output
kvar
IR
A
Output
kvar
IR
A
µF
mm
kg
Ordering code
MKP525-D-1.0 1.0 1.1 1.2 1.3 3 * 4 53 x 114 0.30 B32343C5012A020
MKP525-D-1.5 1.5 1.6 1.8 2.0 3 * 6 53 x 114 0.30 B32343C5012A520
MKP525-D-2.0 2.0 2.2 2.4 2.6 3 * 8 63.5 x 129 0.40 B32343C5022A020
MKP525-D-2.5 2.5 2.7 2.7 3.0 3 * 9 63.5 x 129 0.40 B32343C5022A520
FK PM PFC December 2004
Page 5 of 6
Power Capacitors B32343C
Power Factor Correction
Cautions
Discharge and short circuit capacitor before handling!
Mechanical damage
In case of dents of more than 0.5 mm or any other mechanical damage, capacitors must not be used at all.
Vibration resistance
The resistance to vibration of capacitors corresponds to IEC 68, part 2–6. Max. test conditions:
Test duration 2 h corresponding to max. 0.7 g
Frequency range 10 ... 55 Hz corresponding to max. 0.7 g
Displacement amplitude 0.75 mm corresponding to max. 0.7 g
These figures apply to the capacitor alone. Because the fixing and the terminals may influence the vibration
properties, it is necessary to check stability when a capacitor is built in and exposed to vibration.
Irrespective of this, you are advised not to locate capacitors where vibration amplitude reaches the
maximum in strongly vibrating equipment.
Connection
Make sure connection cables are of flexible type or flexible copper bands are used. This is mandatory to
allow the overpressure disconnector work and avoid mechanical stress on the terminals and feed throughs.
The connection cables to the capacitor should be designed for a current of at least 1.5 times the rated
current so that no heat is conducted into the capacitor. If reactors are used in an application, the distance
between reactor and capacitor must be great enough so that no heat of the reactors, which are operating at
a much higher temperature level, is conducted via connection cable to the capacitors.
Avoid bending cable lugs, cables or other mechanical force on the terminals. Otherwise leakages may set
the safety device out of operation. Ensure firm fixing of terminals, fixing torque to be applied as per
individual specification. Maximum specified terminal current (please refer to technical data of specific
series) must not be exceeded at any case.
Grounding
The threaded bottom stud of the capacitor has to be used for grounding. In case grounding is done via
metal chassis that the capacitor is mounted to, the layer of varnish beneath the washer and nut should be
removed.
Storage and operating conditions
Do not use or store capacitors in corrosive atmosphere, especially where chloride gas, sulfide gas, acid,
alkali, salt or the like are present. In dusty environments regular maintenance and cleaning especially of the
terminals is required to avoid conductive path between phases and/or phases and ground.
U Please read information about PFC capacitors and cautions as well as installation and maintenance
instructions (Power Factor Correction Product Profile, actual version) to ensure optimum performance
and prevent products from failing, and in worst case, bursting and fire, etc.
Information given in the PFC-product profile and values given in the data sheet reflect typical
specifications. You are kindly requested to approve our product specifications or request our approval
for your specification before ordering.
EPCOS AG 2004. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless
otherwise agreed.
FK PM PFC December 2004
Page 6 of 6