7T Series - Panel Thermostat Features 7T.81.0.000.240x 7T SERIES 7T.81.0.000.230x Panel thermostat Small, compact size (17.5 mm wide) Snap action themostatic Bimetal sensor * Wide temperature setting range * Long electrical life * 35 mm rail (EN 60715) mount * * * Heating control * Ventilation control Max Min Heating control - Should the panel temperature fall below the (minimum) set temperature the contact will close to call for heat. The contact will open when this set temperature is exceeded. Ventilation control - Should the panel temperature exceed the (maximum) set temperature then the contact will close to call for cooling. The contact will open when the temperature falls below this set temperature. For outline drawing see page 2 G Contact specification Contact configuration Rated current/Maximum peak current A 1 NC 1 NO 10/10 10/10 250/250 250/250 Rated load AC1 VA 2,500 2,500 Rated load AC15 (230 V AC) VA 250 250 Rated voltage/Maximum switching voltage V AC 0.125 0.125 A 1/0.3/0.15 1/0.3/0.15 mW (V/mA) 500 (12/10) 500 (12/10) AgNi AgNi Single phase motor rating AC3 (230 V AC) kW Breaking capacity DC1: 30/110/220V Minimum switching load Standard contact material Temperature setting range Setting range (ventilation) Switch temperature differential Setting range (heating) Switch temperature differential -- C -- K C K -20...+40 -20...+40 +0...+60 74 +0...+60 -- 74 -- 100*103 100*103 -45...+80 -45...+80 IP 20 IP 20 Technical data Electrical life at rated load AC1 Ambient temperature range Protection category cycles C III-2014, www.findernet.com Approvals (according to type) 1 7T SERIES 7T Series - Panel Thermostat Ordering information Example: 7T Series, thermostat for ventilation control, contact activates ventilation should the panel temperature exceed the set value (max+60C), 35 mm rail (EN 60715) mount. 7 T . 8 1 . 0 . 0 0 0 . 2 3 Series 0 3 Control function (Temperature only) 1 = (-20...+40)C 3 = (0...+60)C Type 8 = 35 mm rail (EN 60715) mount No. of contacts 1 = 1 contact Contact configuration 3 = 1 NO contact 4 = 1 NC contact Voltage type 0 = No operating voltage required Monitoring function 2 = Temperature, adjustable Rated operating voltage 000 = No operating voltage required Technical data Insulation Dielectric strength between open contacts V AC 500 Other data Screw torque Nm 0.5 0.5 solid cable stranded cable mm 1x2.5 1x1.5 AWG 1x12 1x16 Max. wire size 2 G Outline drawings III-2014, www.findernet.com 7T.81 Screw terminal 2