JAE Series Magnetic Circuit Protectors Introduction * 205 Poles * 207 Configurations * 211 Operating Characteristics * 213 Delay Curves * 216 Decision Tables * 217 JAE/JRE/JLE Series Hydraulic Magnetic Circuit Protectors INTRODUCTION 205 In today's applications, ambient operating temperatures present circuit protection challenges for many design engineers. High current thermal protective devices may not provide the desired degree of protection. The JAE/JRE/JLE series magnetichydraulic circuit protector addresses this issue by providing circuit protection for high current applications with a consistent trip point over temperatures ranging from -40C to +85C. this family is the JLE, an F-frame "listed circuit breaker" which complies with conditions of UL-489. Other members of the family include the JTE, for telecommunication applications and complies to UL-489A, and the JAE, a special construction version. In addition, the JAE is now in compliance with the standards used in Australia and New Zealand, AS 60947.2-2005 (equivalent to IEC 60947-2:2006+A1). The JAE/JRE/JLE series is actually a family of circuit protectors available in one to six pole assemblies with a variety of configurations and terminal styles. The principle member of The JAE/JRE/JLE series magnetic-hydraulic circuit protector provides circuit protection for high current applications. It provides a consistent trip point over temperatures ranging from -40C to +85C. JAE Series - Introduction http://airpax.sensata.com JAE (F-frame) 2.969 (75.41) 1.500 (38.10) 7.125 (180.97) General Description -mid-trip handle available for visual identification of fault-tripped circuit breakers - optional internal low voltage shunt to meter current (single and multi-pole units are dimensionally equivalent in depth) - terminal options for design flexibility in various applications - multiple trip time delays for application flexibility - electrical and mechanical actuated auxiliary switch options for external monitoring of circuits -reduced voltage drop through the circuit breaker vs. other circuit protective devices Number of Poles - 1, 2, 3, 4, 5, 6 Current and Voltage Ratings - 100 to 250 amps, 160Vdc - 100 to 250 amps, 125/250Vdc - 100 to 250 amps, 65Vdc -275 to 800 amps, 160Vdc (paralleled poles) - 275 to 1200 amps, 65Vdc (paralleled poles) Interrupting Capacity - 10,000 amps, 160Vdc - 10,000 amps, 125/250Vdc - 100,000 amps, 65Vdc (1 amps to 800 amps) - 10,000 amps, 160Vdc (ratings 1000 amps) - 65,000 amps, 65Vdc (801 amps to 1200 amps) Approvals - UL 489 Listed - UL 489A Listed - CSA Certified - CUL/CUR Certified - TUV Certified - CCC Certified - AS 60947.2-2005 (equivalent to IEC 60947-2:2006+A1) Single-pole ratings: UL489, 250 amps max at 160 Vdc, 10,000 amp interrupting capacity and 250 amps max at 65 Vdc, 65,000 amp interrupting capacity. Multi-pole ratings: UL 489A, 800 amps max at 160 Vdc, 10,000 amp interrupting capacity and 1,200 amps max at 65 Vdc, 65,000 amp interrupting capacity. ISO-9001 Certified JAE Series - Introduction 206 Optional Metering Shunt 1.264 (32.11) 3.188 (80.98) .470 (11.94) 1.266 2.406 (61.11) Optional Metering Shunt .329 (8.36) ON OPTIONAL TRIPPED POSITION 7.125 (180.97) 2.741 (69.62) .470 (11.94) 1.937 (49.21) 3.093 (78.56) OFF .300 (7.62) .470 (11.94) Dimension "A" .437 HOLE SHOWN 1.420 (36.07) .283 (7.18) .250 (6.36) 1.215 (30.86) R.105 TYP. ON 2.313 (58.75) 6.559 (166.61) 2X 10-32 MOUNTING SCREW DEPTH: .230 MIN. .315 MAX. OPTIONAL M5 OFF .300 (7.63) .250 (6.36) 1.000 (25.40) 207 JAE Series - Poles http://airpax.sensata.com JAE (F-frame) Terminal Configuration DIM."A" BOX TERMINAL SHOWN SEE SINGLE POLE CONFIGURATIONS FOR ADDITIONAL TERMINAL STYLES 1.420 [36.07] Captive Nut (-F1) REMOVABLE LUG COVER 518-031-6030 (LINE SIDE ONLY) .426 1.170 (29.72) .283 [7.18] .250 [6.36] 1.215 [30.86] R.105 TYP. 6.559 [166.61] ON Stud (-B3) 2.313 [58.75] 1 ON 1 2X 10-32 MOUNTING SCREW. DEPTH:.230 MIN. .315 MAX. OPTIONAL M5 OFF SCREW 3/8 - 16 UNC 2A .250 [6.36] .300 [7.63] .111 (2.82) Long Stud (-B4) 1.014 (25.76) COPPER ALLOY STANDOFF 1.500 (38.10) 2.500 (63.50) MULTI-POLE DIMENSIONS SCREW 3/8 - 16 UNC 2A Solderless Connector (-F0) .734 (18.64) Number of Poles Dimension "A" 1 1.500 [38.10] Max 2 3.000 [76.20] Max 3 4.500 [114.30] Max 4 6.000 [152.40] Max 5 7.500 [190.50] Max 6 9.000 [228.60] Max .219 (5.56) #6-300 MCM AL/CU Solderless Connector 1.670 (42.43) 1.170 (29.72) JAE Series - Poles 208 PARALLEL MULTI-POLE ASSEMBLIES Amp Range Number of Poles Dimension "A" Dimension "B" 275 to 400 2 2.375 [60.33] Max 3.000 [76.20] Max 450 to 600 3 3.875 [98.43] Max 4.500 [114.30] Max 650 to 800 4 5.375 [136.53] Max 6.000 [152.40] Max 850 to 1000 5 6.875 [174.63] Max 7.500 [190.50] Max 1050 to 1200 6 8.375 [212.73] Max 9.000 [228.60] Max Note: Tolerance of 0.030 [0.762] 1.170 [29.72] DIM."A" (SEE TABLE) "B" 1.500 [38.10] TERMINAL TYPE -B1, F1 OR -B2 .875 [22.22] 10.370 [263.40] 8.870 [225.30] 209 JAE Series - Poles http://airpax.sensata.com JAE (F-frame) DIM."C" .757 [19.23] PANEL MOUNTING DETAILS 2.328 [59.13] 2.814 [71.48] .250 [6.36] 1.500 [38.10] 10-32 MOUNTING SCREW Number of Poles Dimension "C" 1 1.515 [38.48] Max 2 3.015 [76.58] Max 3 4.515 [114.68] Max 4 6.015 [152.78] Max 5 7.515 [190.88] Max 6 9.015 [228.98] Max Notes: 1. All mounting inserts shall be utilized when panel mounting circuit breakers. Panel mounting screws shall have recommended torque applied. 2. Panel mounting screws shall not extend beyond back of mounting panel more than specified mounting insert depth. 1.607 [40.82] "B" DIM "A" 1.500 [38.10] .854 [21.69] .875 [22.22] 10.370 [263.40] ON I ON I OFF BOX TERMINAL SHOWN JAE Series - Poles 210 CONFIGURATIONS Series Trip The most popular configuration for magnetic protectors is the series trip, where the sensing coil and contacts are in series with the load being protected. The handle position conveniently indicates circuit status. In addition to providing conventional overcurrent protection, it's simultaneously used as an on-off switch. Auxiliary Switch This is furnished as an integral part of a series pole in single or multi-pole assemblies. Isolated electrically from the protector's circuit, the switch works in unison with the power contacts and provides indication at a remote location of the protector's on-off status. 1.437 (36.50) 1.305 (33.15) SWITCH ONLY Alarm Switch ALARM SWITCH RLS4 SERIES Series with Auxiliary Switch Configurations PLUG SEE SWITCH OPTIONS Auxiliary Switch .416 [10.57] .235 [5.97] PLUG 2.772 [70.41] AUXILIARY SWITCH REC4 Alarm & Auxiliary Switch Combination .752 [19.11] C NO NC BREAKER IN OFF POSITION .250 [6.35] 2.438 MAX. [64.52] .110 [2.79] .252 [6.40] .252 [6.40] -IREC4 211 JAE Series - Configurations ALARM SWITCH RLS4 AUXILIARY SWITCH REC4 http://airpax.sensata.com JAE (F-frame) Shunt Trip Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, interlock and emergency rapid shut down circuitry. Trip may be accomplished by voltage or current, which must be removed after trip. 1.187 [30.15] 4.754 [120.76] FLATWASHER Shunt Trip The shunt trip is designed for controlling two separate loads with one assembly. The control is established by providing overload protection for the critical load. When the current through this load becomes excessive and reaches the trip point, the protector will open and remove power from both loads simultaneously. The total current rating of both loads must not exceed the maximum contact rating. Relay Trip LOCKWASHER 1/4-28 2 NUTS Metering Shunt 1.266 2.406 [61.11] 3.310 [84.06] 1.187 [30.15] 2.741 [69.62] 1.445 [36.70] 1/4-28 2X ELECTRICAL CONNECTORS TO METERING SHUNT AND / OR AUXILIARY SWITCH(ES) WHEN USED. CONSULT FACTORY FOR CONFIGURATIONS. METERING SHUNT/AUXILIARY SWITCH CONNECTORS Description MOLEX AMP Pin (Male) 02-09-2103 770147-1 Socket (Female) 02-09-1104 770146-1 JAE Series - Configurations 212 OPERATING CHARACTERISTICS Trip Free Will trip open on overload, even when forcibly held on. This prevents the operator from damaging the circuit by holding the handle in the ON position. Insulation Resistance Will not be less than 100 megohms at 500 volts D.C. Endurance Test to be performed at rated current and rated voltage at 3mSec time constant DC. Rate of operation to be 5 operations per minute for breakers rated at 250 amps and less and 4 per minute for breakers rated above 250 amps. Breakers rated above 250 amps but 600 amps or less shall be rated for 1000 loaded operations and 5000 mechanical operations. Auxiliary Switch When supplied will be S.P.D.T. configuration with a maximum rating of 10 amperes 250 VAC 1 amp 80 Vdc. When optional metering shunt or parallel pole configuration is specified, maximum rating is 1 amp 80 Vdc. High-Low Temperature Circuit breakers will operate in the range from -40C to +85C. All agency testing is conducted with wire sized per 75C chart of the National Electrical Code. In all cases the breaker connections should be sized to limit the maximum terminal temperature to 100C absolute when the breaker is operating in the maximum ambient temperature at the maximum load current. Overload DC rated circuit breakers will withstand 50 operations at 600% of rated current. The current shall have no less than a 3mSec time constant at rated voltage. Units to be operated in groups of five at the rate of operations per minute with fifteen minutes between groups to allow for cool down. Dielectric Strength Circuit Breaker will withstand 1000 volts plus twice rated voltage 60 Hz AC for 60 seconds from terminal to terminal. Voltage Ratings On all types, voltages up to and including 160 volts DC. Multi-pole units can be supplied for 125/250 volts Vdc. All units will be marked with the standard maximum voltage. UL listed breakers will be labeled with the UL listed voltage. DC Applications (typ) A choice of delays is offered for DC applications. Delay 51 is a short delay for general purpose applications. Delay 52 is long enough to start certain types of motors and most transformer and capacitor loads. Delay 53 is a long delay for special motor applications. All trip curves and trip currents are specified with the breaker mounted in the normal vertical position at ambient temperature of +25C. For test and measurement purposes, the breakers should not carry current prior to application of overload for calibration test. For other than vertical mount position, consult factory. General notes for Agency Approvals All supplementary protectors are of the overcurrent (OC) type The family of protectors has been evaluated for end use application for use group (UG) A The terminals (FW) - Terminals are coded as follows: 0 - Suitable for factory wiring only 1 - Line terminals evaluated for field wiring 2 - Load terminals evaluated for field wiring 3 - Line and load terminals evaluated for field wiring The maximum voltage ratings for which the protectors have been tested are shown in the chart The current is the amperage range that the protectors have been tested The tripping current (TC) - Tripping current is coded as a percentage of the ampere rating 0 - Tripping current is less than 125% of ampere rating 1 - Tripping current is in the range of 125% to 135% of ampere rating 2 - Tripping current is more than 135% of ampere rating 3 - Tripping current is 135% and meets MCCB trip time requirements The overload rating (OL) - designates whether the protector has been tested for general use or motor starting applications. 0 - tested at 1.5 times amp rating for general use 1 - tested at 6 times AC rating or 10 times DC rating for motor starting The short circuit current rating (SC) - The short circuit rating in amperes following a letter and number designating the test conditions and any calibration following the short circuit test is defined below: C - Indicates short circuit test was conducted with series overcurrent protection U - Indicates short circuit test was conducted without series overcurrent protection 1 - Indicates a recalibration was not conducted as part of the short circuit testing 2 - Indicates a recalibration was performed as part of the short circuit testing 3 - Indicates recalibration was performed along with the dielectric and voltage withstand for "Suitable for Further Use" rating 213 JAE Series - Operating Characteristics http://airpax.sensata.com JAE (F-frame) JRE/JRM/JREP/JRMP SUPPLEMENTARY PROTECTORS - AGENCY APPROVALS Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps) Voltage (V) Frequency (Hz) UG FW Phase Min. Poles TC OL UL/CSA TUV UL 508 & CSA TUV 65 DC A 0, 3 -- 1 1 1 100-250 -- U2, 100000 -- 65 DC A 0, 3 -- 2 1 1 275-400 -- U2, 100000 -- 65 DC A 0, 3 -- 2 1 1 450 -- U2, 100000 -- 65 DC A 0, 3 -- 3 1 1 450-600 -- U2, 100000 -- 65 DC A 0, 3 -- 3 1 1 700 -- U2, 65000 -- 65 DC A 0, 3 -- 3 1 1 700 -- U2, 100000 -- 80 DC -- -- -- 1 -- -- -- 15-250 -- 10000/25000 160 DC A 0, 3 -- 1 1 1 100-250 15-250 U2, 10000 5000/10000 160 DC A 0, 3 -- 2 1 1 251-400 -- U2, 10000 -- 160 DC A 0, 3 -- 3 1 1 401-600 -- U2, 10000 -- 160 DC A 0, 3 -- 3 1 1 700 -- U2, 10000 -- 277/480 50/60 A 0, 3 3 3 1 1 150 -- U2, 5000 -- JTE/JTM/JTEP/JTMP COMMUNICATIONS EQUIPMENT CIRCUIT BREAKERS - AGENCY APPROVALS Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps) Voltage (V) Frequency (Hz) Phase Min. Poles UL/CSA TUV UL 489A TUV 65 -- 1 -- 100000 -- DC 100 to 250 65 DC -- 2 275 to 400 -- 100000 -- 65 DC -- 2 401 to 450 -- 100000 -- 65 DC -- 3 450 to 600 -- 100000 -- 65 DC -- 4 700 to 800 -- 100000 -- 65 DC -- 5 900 to 1000 -- 65000 -- 65 DC -- 6 1100 to 1200 -- 65000 -- 80 DC -- 1 -- 15 to 250 -- 25000 160 DC -- 1 100 to 250 15 to 250 10000 10000 160 DC -- 2 251 to 400 -- 10000 -- 160 DC -- 3 401 to 600 -- 10000 -- 160 DC -- 4 700 to 800 -- 10000 -- JLE/JLM - AGENCY APPROVALS Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps) Voltage (V) Frequency (Hz) Phase Min. Poles UL/CSA TUV UL489 & CSA TUV 65 -- 1 -- 100000 -- DC .10 - 250 80 DC -- 1 -- 15 - 250 -- 25000 160 DC -- 1 .10 - 250 15 - 250 10000 10000 125/250 DC -- 2 100 - 250 -- 10000 -- 240 50/60 1 1 .10 - 250 -- 10000 -- 240 50/60 1&3 2 .10 - 250 -- 18000 -- JAE Series - Operating Characteristics 214 OPERATING CHARACTERISTICS PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +25C Delay 100% 125% (Note A) 150% 200% 400% 600% 800% 1000% 51 & 51F No Trip .5 to 10 .25 to 3 .15 to 9 .05 to .3 .015 to .15 .01 to .09 .01 to .04 52 & 52F No Trip 9 to 90 5 to 40 2 to 15 .5 to 3 .03 to 1 .01 to .28 .01 to .08 53 & 53F No Trip 100 to 1000 50 to 400 22 to 150 4 to 25 .5 to 5 .010 to 2 .01 to .1 61 & 61F No Trip .4 to 10 .25 to 3 .13 to .9 .03 to .2 .015 to .15 .01 to .09 .008 to .045 62 & 62F No Trip 9 to 95 5 to 40 2 to 15 .05 to 3 .03 to 1 .01 to .28 .008 to .08 63 & 63F No Trip 100 to 1100 48 to 400 20 to 150 4 to 25 .5 to 6 .01 to 2 .008 to .1 NOMINAL DCR / IMPEDANCE RECOMMENDED TORQUE SPECIFICATIONS Resistance (ohms) Current Ratings (Amps) DC Delays 51, 52, 53 Torque (in-lbs) 10 to 12 M5 Mounting Inserts 8 to 10 3/8-16 and M10 x 1.5 Captive Nuts 220 to 230 3/8-16 and M10 x 1.5 Studs 220 to 230 Solderless Connectors 180 100 .000375 110 .000375 125 .000340 150 .000325 175 .000315 200 .000225 225 .000225 Pounds Grams 250 .000225 2.25 1020 400 .000125 600 .000083 800 .000063 1,000 .000050 1,200 .000042 Notes: Resistance is plus or minus 50%. If a metering shunt option is provided it will add the shunts resistance to these values (i.e. A 400 Amp metering shunt would add (R=V/I). 0000625 O hms of resistance to the non-metering shunt value of .000125 Ohms or .0001875 Ohms for a 400 Amp unit with a metering shunt). DC resistance values are based on measurements by the voltmeter ammeter method. Rated current applied for one hour and at a voltage not less than 20 volts. 215 Component 10-32 Mounting Inserts JAE Series - Operating Characteristics APPROXIMATE WEIGHT PER POLE INRUSH PULSE TOLERANCE Delay Pulse Tolerance 61, 62, 63 8 times rated current (approx) 61F, 62F, 63F 12 times rated current (approx) Inrush Pulse Tolerance The table shown provides a comparison of inrush pulse tolerance with and without the inertial delay feature for each of the 50/60Hz delays. Pulse tolerance is defined as a single pulse of half sine wave peak current amplitude of 8 milliseconds duration that will not trip the circuit breaker. http://airpax.sensata.com JAE (F-frame) 1000 1000 .01 .01 1000010000 1 .1 .1 MAY TRIP MAY TRIP 1000 1000 DELAY 62 &62 62F DELAY & 62F 100 100 TIME IN SECONDS 1 .001 .001 0 0 100 150 100200 150 200300 300400 400500 500600 600700 700800 800900 9001000 1000 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS 10 .01 .01 1 .1 .1 10 10 1 1 .1 .1 0 200 200 300 300400 400500 500600 600700 700800 800900 900 1000 1000 0100 150 100 150 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT MAY TRIP 1000010000 1000 1000 DELAY 53 &53 53F DELAY & 53F DELAY 63 &63 63F DELAY & 63F 100 100 TIME IN SECONDS 100 100 TIME IN SECONDS 1 .001 .001 MAY TRIP 1000 1000 TIME IN SECONDS 10 0 100 150 100200 150 200300 300400 400500 500600 600700 700800 800900 9001000 1000 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 1000010000 .01 .01 10 10 1 1 .1 .1 .01 .01 .001 .001 0 10 DELAY 52 &52 52F DELAY & 52F .01 .01 .001 .001 0 .1 1000010000 100 100 10 .1 .01 .01 .001 .001 0 0 100 150 100200 150 200300 300400 400500 500600 600700 700800 800900 9001000 1000 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT 1000 1000 1 MAY TRIP .1 1 MAY TRIP .1 10 MAY TRIP 1 10 MAY TRIP 1 TIME IN SECONDS 10 DELAY 51 &51 51F DELAY & 51F 100 100 TIME IN SECONDS 10 DELAY 61 &61 61F DELAY & 61F TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS 100 100 MAY TRIP 1000 1000 MAY TRIP 1000010000 MAY TRIP 1000010000 MAY TRIP DELAY CURVES 0 100 150 100200 150 200300 300400 400500 500600 600700 700800 800900 9001000 1000 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT .001 .001 0 200 200 300 300400 400500 500600 600700 700800 800900 900 1000 1000 0 100 150 100 150 125 125 PERCENT OF RATED CURRENT PERCENT OF RATED CURRENT JAE Series - Delay Curves 216 1 How to Order The ordering code for JAE/JRE/JLE F-Frame Circuit Protectors may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number for standard configurations. Factory part numbers are assigned to units with mixed ratings, combinations of styles or construction not listed in the Third Decision Table, etc. With these, it is suggested that order entry be by description and/or drawings, and a part number will be established. Additionally, it is standard policy to establish a factory-assigned part number whenever a descriptive drawing exists to ensure cross reference, traceability and manufacturing control. For example, the following is the code for a single pole breaker series trip, with mid-trip handle indication, auxiliary switch, short delay, 65 volts DC maximum voltage rating with 3/8-16 captive nuts in a current rating of 250 amperes and metric inserts. To determine the ordering number of your particular JAE/JRE/ JLE unit, simply follow the steps shown. You may use this number to place an order or as a reference for further questions you may have. Notes: A 10-32 inserts are provided for front mounting on all units. M5 ISO metric mounting inserts are available and are specified by the eight decision in the part number. BThe auxiliary switch is located on the left hand pole (viewed from terminal end) unless specified otherwise. Note this is the only location available for breakers rated over 250 amps. The switch is available as an alarm switch (changes state when breaker electrically trips) or as an auxiliary switch (changes state when the breaker contacts change state either from tripping or operation of the breaker handle). See outline drawing for location of alarm and auxiliary switches. Note alarm switches are available only with mid trip option. When both an alarm and auxiliary switch are specified with a metering shunt, only the C and NO or C and NC terminals from each switch are available for field termination. C 3/8-16 captive nuts are available for bus bar terminations or crimp lugs (specify front or back termination). 3/8-16 long and short studs are also available (specify front or back mount). A number 6 through 300 MCM AL/CU solderless connector is available (specify front or back mount). DOnly series construction and DC ratings are available in current carrying poles above 250 amps. Consult factory for special requirements. First Decision Type JLE UL Listed JLM UL Listed Mid Trip Construction JRE UL Recognized JREP UL Recognized above 250 amps JRM UL Recognized Mid Trip Construction JRMP UL Recognized Mid Trip Construction above 250 amps JTE UL Listed Telecom Specification JTEP UL Listed Telecom Specification above 250 amps JTM UL Listed Telecom Specification Mid Trip Construction JTMP UL Listed Telecom Specification Mid Trip Construction above 250 amps JAE Non Agency JAEP Non Agency above 250 amps JAM Non Agency Mid Trip Construction JAMP Non Agency Mid Trip Construction above 250 amps EThe coding given permits a self-assigning part number but with certain limitations, (due to the adaptability of magnetic protectors to complex circuits) which require a need for a factory assigned part number. Typical examples are units with mixed ratings, combinations of styles, or construction not listed in the third decision table, etc. With these, it is suggested that order entry be by description and/or drawings, and a part number will be established. Additionally, it is standard policy to establish a factory assigned part number wherever a descriptive drawing exists to provide cross-reference, traceability, and manufacturing control. FWhen specifying a protector for AC motor start or high inrush applications, the peak amplitude and surge duration should be specified for factory assistance in rating selection. GSince magnetic protectors with time delay are somewhat attitude and temperature sensitive, all trip curves and trip currents are specified with the protector mounted in the normal vertical position at ambient temperature of 25C. Protectors do not carry current prior to application of overload for calibration test. For other than vertical mount position, consult factory. HA 25mV at rated current non-isolated metering shunt is available as an option (see outline drawing). The shunt accuracy is 1% full scale 25C ambient. I Dual coil construction is available. Consult the factory. JDecisions referencing this note may be replaced by a factory assigned nondescript number. 217 JAE Series - Decision Tables http://airpax.sensata.com 4 Second Decision 209 (E-frame) 2 Fourth Decision Frequency and Delay Poles -1* Single pole Standard -2 Two poles 50 DC instant trip -3 Three poles 51 DC short delay 51F -4 Four poles 52 DC med. delay 52F -5 Five poles 53 DC long delay 53F -6 Six poles 60 50/60Hz instant trip 61 50/60Hz short delay 62 *Single pole unit above 250 Amps are supplied as parallel milti-pole assemblies. The second decision must indicate the physical number of poles. Option 6 Terminal Terminal Connect -B0 Solderless connector* Back -F0 Solderless connector Front 61F -B1 3/8 - 16 captive nuts Back 50/60Hz med. delay 62F -F1 3/8 - 16 captive nuts Front 63 50/60Hz long delay 63F -B2 .437 hole - SW Switch only -B3 3/8 - 16 stud terminals** Back -F3 3/8 - 16 stud terminals Front -B4 3/8 - 16 stud terminals long with spacers* Back An F after any delay denotes high pulse tolerance construction. * Example: JLM -1 - IREC4 - 51- 1 - F1 - 250 - A - V 1 3 2 3 4 Sixth Decision Terminal Selection 5 6 7 Automatically get anti-flashover for multi-pole construction. Refer to outline drawings. ** Automatically get anti-flashover barrier for multi-pole construction with voltage ratings above 250 volts. 8 7 Third Decision Internal Configuration * -0 Switch only -1 Series -3 Shunt construction*** -4 Relay construction*** -REC4 -REG4 Seventh Decision Current Ratings (see note J) 5 Fifth Decision Voltage and Current Amperes Amperes 100 450 125 500 150 550 Maximum Voltage Maximum Current (Amps) -1 65Vdc 1200A Auxiliary switch* (STD) .110 quick connect -2 125Vdc 800A 175 600 -3 160Vdc 800A Auxiliary switch* .110 quick connect** 200 700 -4 125/250Vdc* 250A 250A 800 Auxiliary switch* (STD) .187 quick connect 240Vac 225 -REC5 -5 -6 277Vac 250A 250 900 -RLS4 Alarm switch* (STD) .110 quick connect -7 277/480Vac 150A Only 275 1000 300 1100 350 1200 -RLS5 Alarm switch* .187 quick connect -DAA4 Dual auxiliary & alarm switch* (STD) .110 quick connect -DAA5 Dual auxiliary & alarm switch* .187 quick connect Auxiliary switch located in the left hand pole when viewed from the terminal end. All meter shunt and parallel pole builds that require an auxiliary switch will automatically get a XXX4 type switch. To connect to the switch terminals which are brought through the cover use a Molex 02-09-1104 or an Amp 770146-1 crimp terminal. ** Gold Contacts *** Shunt and Relay construction not available above 250 Amps and not available in UL Listed Breakers *Two poles breaking V = TUV and CCC Approved 400 Approval requires the addition of a V at the end of the part number, which denotes TUV and CCC approval. Consult the factory for availability. C = CCC Approved This approval requires the addition of a C at the end of the part number. The unit will not be TUV Approved. 8 Eighth Decision Optional A Optional metric inserts M5 S Optional metering shunt