06/25/2012 HPL-ED2012 V1.1 EN 1 / 4
Function�element,�MSC-DEA�/�XTSEA
Part�no. PKE-SWD-32
Article�no. 126895
Delivery�programme
Product range SmartWire-DT slave
Basic function Motor protection
Motor protection for heavy starting duty
Product range Accessories
Accessories SmartWire-DT PKE module (motor-starter combinations)
Function For connecting the motor-starter combination to SmartWire-DT,
"expanded" 24 VDC version (MSC-DEA…) up to 15 kW.
Description Surface-mounting to contactors.
One module per contactor and PKE necessary.
Additional SWD contactor module required fir actuation of reversing
starter.
1 electrical interlock for the surface mounting of reversing starters.
1-0-A switch for manual or automatic operation.
Selectable overload relay function (ZMR) for switching off the contactor
on overload.
Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used.
Messages Switch position contactor/PKE/1-0-A switch
Motor current in %
Thermal motor image in %
Trip indications (Overload, Short-circuit,...)
Set value of overload releases
Set time lag (CLASS)
Part no. of trip block
Commands Contactor actuation
Activation Overload relay function (ZMR)
Information about equipment supplied Connecting cable between module and trip block PKE-XTUA-…
included as standard.
For use with DILM(C)7… - DILM(C)32
MSC-DEA
Connection to SmartWire-DT yes
Connection type Push in terminals
Notes
Take into account the max. current consumption of the contactor coils per SmartWire-Darwin line.
A2 connections must not be bridged.
Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used.
Additional SWD contactor module required fir actuation of reversing starter.
Approvals
NA Certification Request filed for UL and CSA
Part�no. PKE-SWD-32
General
Standards IEC/EN 61131-2
EN 50178
IEC/EN 60947
Dimensions (W x H x D) mm 45 x 38 x 76
Weight kg 0.04
Mounting on DILM7…DILM32
Mounting position as DILM7 to DILM32
Ambient�conditions,�mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3,5 mm Hz 5 - 8.4
Constant acceleration 1 g Hz 8.4 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15
g/11 ms
Impacts 9
Drop to IEC/EN 60068-2-31 Drop
height
mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 0.3
Electromagnetic�compatibility�(EMC)
Overvoltage category II
Pollution degree 2
06/25/2012 HPL-ED2012 V1.1 EN 2 / 4
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8
Contact discharge (Level 2) kV 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80 - 1000 MHz V/m 10
1.4 - 2 GHz V/m 3
2 - 2.7 GHz V/m 1
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
CAN/DP bus cable kV 1
SmartWire-DT cables kV 1
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10
Climatic�environmental�conditions
Operating ambient temperature (IEC 60068-2) °C
Ambient temperature °C -25 - +60
Condensation Take appropriate measures to prevent condensation
Storage °C -30 - +70
relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 - 95
SmartWire-DT�network
Station type SmartWire-DT slave
Address allocation automatic
SmartWire-DT status LED LED green/orange
Connections Plug, 8-pole
Connection External device plug SWD4-8SF2-5
Current consumption mA 58
Pick-up power
for DILM 7-9 W 3
for DILM 12-15 W 4.5
for DILM 17-38 W 12
Pick-up current
for DILM 7-9 mA 125
for DILM 12-15 mA 188
for DILM 17-38 mA 500
Holding power
for DILM 7-9 W 3
for DILM 12-15 W 4.5
for DILM 17-38 W 0.5
Holding current
for DILM 17-38 mA 21
for DILM 12-15 mA 188
for DILM 7-9 mA 125
Mode�parameter
Manual/automatic mode yes
Setting Rotary switch
Connection�auxiliary�contact
Cable length m 2.8
Connection type Push in terminals
Terminal�capacities
Solid mm20.2 - 1.5 (AWG 24 - 16)
Flexible with ferrule mm20.25 - 1.5
Technical�data�ETIM�4.0
Radiostandard Bluetooth No
Short-circuit protective device, outputs available No
Type of voltage (input voltage) DC
06/25/2012 HPL-ED2012 V1.1 EN 3 / 4
Flush mounting plates possible No
Height mm 38
Performance level acc. to EN ISO 13849-1 A
Number of HW-interfaces other 2
Number of outputs 1
Supporting protocol for PROFIsafe No
Supply voltage DC V 15
Supply voltage AC 60 Hz V 0
Supporting protocol for EtherNet/IP No
IO link master No
Number of HW-interfaces USB 0
Supporting protocol for TCP/IP No
With optical interface No
Wall mounting/direct mounting No
Number of HW-interfaces serial TTY 0
Appendant apparatus (Ex ib) No
Supporting protocol for other bus systems YES
Supporting protocol for DeviceNet Safety No
Protection type (IP) IP20
Supporting protocol for PROFINET IO No
Supporting protocol for Data-Highway No
Voltage type of supply voltage DC
Supporting protocol for CAN No
Type of electric connection Spring clamp connection
Category to EN 954-1 1
Number of inputs 0
Permitted voltage at input V 15
Number of HW-interfaces RS232 0
Rack-mounting possible No
Input current at signal 1 mA 0
Width mm 45
System component YES
Explosion safety category for dust without
Supporting protocol for INTERBUS-Safety No
Supporting protocol for SUCONET No
Supporting protocol for DeviceNet No
Supporting protocol for SafetyBUS p No
Fieldbus connection over separate bus terminal possible YES
Depth mm 77.3
SIL according to IEC 62061 0
Supporting protocol for EIB No
SIL according to IEC 61508 0
Output current A 0.5
Type of digital output -
Radiostandard WLAN 802.11 No
Associated apparatus (Ex ia) No
Delay time on signal change ms 84
Number of HW-interfaces Wireless 0
Supporting protocol for MODBUS No
Supporting protocol for SERCOS No
Safety class according to DIN V 19250 0
Supporting protocol for Foundation Fieldbus No
Supporting protocol for LON No
Supporting protocol for INTERBUS No
Type of output voltage DC
06/25/2012 Eaton Industries GmbH
http://www.moeller.net/en
© 05/2012 by Eaton Industries GmbH
HPL-ED2012 V1.1 EN (UX111)
4 / 4
Supporting protocol for PROFIBUS No
Number of Industrial Ethernet HW interfaces 0
Number of HW-interfaces PROFINET 0
Permitted voltage at output V 28.8
Supporting protocol for AS-Interface Safety at Work No
Number of HW-interfaces RS485 0
Explosion protection for gas without
Supporting protocol for AS-Interface No
Supporting protocol for PROFINET CBA No
Supply voltage AC 50 Hz V 0
Number of HW-interfaces parallel 0
Rail mounting possible No
Number of HW-interfaces RS422 0
In-/outputs configurable No
Suitable for safety functions No
Dimensions
SmartWire-DT PKE module (motor-starter combinations)
Additional�product�information�(links)
IL03402024Z�(AWA1210-2706)�SmartWire-DT:�Function�element�for�PKE12/32,�MSC-DEA
IL03402024Z (AWA1210-2706)
SmartWire-DT: Function element for
PKE12/32, MSC-DEA
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03402024Z2010_08.pdf
MN05006001Z-EN(AWB2723-1613)�SmartWire-DT,�Unit
MN05006001Z-EN(AWB2723-1613)
SmartWire-DT, Unit - Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN05006001Z_DE.pdf
MN05006001Z-EN(AWB2723-1613)
SmartWire-DT, Unit - English
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN05006001Z_EN.pdf
MN05006001Z-IT (AWB2723-1613)
SmartWire-Darwin utenti - italiano
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN05006001Z_IT.pdf
Motor starters and "Special Purpose
Ratings" for the North American market
http://www.moeller.net/binary/ver_techpapers/ver953en.pdf
Busbar Component Adapters for
modern Industrial control panels
http://www.moeller.net/binary/ver_techpapers/ver960en.pdf