For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
404
Telcom Protection Products
Power Feed Through Terminal Blocks
Series C7024
Specifications
Description: A
power feed through
terminal block with
two rows of 14-28
studs capable of
accommodating the industry standard two-hole compression
lugs on 34" centers.
Dimensions: See Dimensions illustration.
Ratings:
Volts: — 600V
Amps: — 115A per pole
Center Spacing: 0.75" (19.1mm).
Wire Range: #2-8 AWG.
Poles: 1 to 12.
Bolt Hole Spacing: 0.75" (19.1mm).
Stud: Standard 14-28 stud (tin-plated bronze).
Torque Rating: 36 lb-in.
Operating Temperature: 130°C.
Agency Information: UL/C-UL, CSA; CE Certified.
Flammability Rating: UL 94V0.
Catalog Numbers
Catalog “A” Dimension- mm (in)
Number Poles ±0.4 (±0.02) “B” Dimension- mm (in)
C7024-01 01 21.6 (0.85) -
C7024-02 02 40.6 (1.60) 19.05 ±0.08 (0.750 ±0.003)
C7024-03 03 59.7 (2.35) 38.10 (1.500)
C7024-04 04 78.7 (3.10) 57.15 ±0.26 (2.250 ±0.010)
C7024-05 05 97.8 (3.85) 76.2 (3.00)
C7024-06 06 116.8 (4.60) 95.25 ±0.26 (3.750 ±0.010)
C7024-07 07 135.9 (5.35) 114.30 ±0.38 (5.250 ±0/015)
C7024-08 08 154.9 (6.10) 133.35 ±0.38 (5.25 ±0.015)
C7024-09 09 174.0 (6.85) 152.40 ±0.38 (6.00 ±0.015)
C7024-10 10 193.0 (7.60) 171.45 ±0.38 (6.750 ±0.015)
C7024-11 11 212.1 (8.35) 190.50 ±0.38 (7.500 ±0.015)
C7024-12 12 231.1 (9.10) 209.55 ±0.38 (8.250 ±0.015)
][0.106
2.70TYP
][0.02
0.5 TYP
][0.52
13.2TYP
B
][0.003
±
0.750 0.0819.06
][0.70
17.8TYP
][0.124
3.16TYP
16.53TYP
[0.651]
A
][1.60
40.6
][1.10
28.0
][0.700
17.780
MIN. AT STUD PAD
TYP
Ø
Ø14.4
[0.57]
Typical Applications
Applications requiring up to 115A utilizing a 2-hole
compression lug on 34" centers
• Ideal as an input/output block for telecommunications power
panels
• Use to eliminate busbars
Dimensions - mm (in)
Catalog Number Build-A-Code
Series Poles
C7024 –
01-12
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Eaton:
C7024-04 C7024-06 C7024-10