24
Specications Legacy Power Relays
92
DPST-NO, 30 A;
DPDT, 30 A (NO) / 3 A (NC)
Specifications
Part Number 92S7 92S11
Contact Characteristics
Contact Configuration DPST-NO DPDT
Contact Material Silver alloy
Thermal (Carrying) Current
30 A 30 A (NO); 3 A (NC)
Maximum Switching Voltage
(Conforming to IEC)
250 Vac / 28 Vdc
Maximum Switching Voltage
(Conforming to UL)
300 Vac / 28 Vdc
Current Ratings at Voltage
(Conforming to IEC)
(NO) 30 A at 250 Vac;
25 A at 28 Vdc, 100,000 cycles
(NO) 30 A at 250 Vac;
25 A at 28 Vdc, 100,000 cycles
(NC) 3 A at 250 Vac;
3 A at 28 Vdc, 100,000 cycles
Current Ratings at Voltage
(Conforming to UL)
(NO) General Use: 30 A at 277 Vac, 100,000 cycles
Resistive: 20 A at 28 Vdc, 100,000 cycles
Motor: 1�0 hp at 120 Vac;
3�0 hp at 240 Vac, 100,000 cycles
LRA/FLA : 96 A / 22 A @ 240 Vac (AC coil), 30,000 cycles;
110 A / 25�3 A @ 240 Vac (DC coil), 30,000 cycles
Pilot Duty: 720 VA / A300, 6,000 cycles
Short Circuit: 5000 A(rms) @ 240 Vac
Tungsten: 10 A at 120 Vac 50/60 Hz, 25,000 cycles;
6 A at 250 Vac 50/60 Hz, 25,000 cycles
(NO) General Use: 30 A at 277 Vac, 100,000 cycles
Resistive: 20 A at 28 Vdc, 100,000 cycles
Motor: 1�0 hp at 120 Vac;
3�0 hp at 240 Vac, 100,000 cycles
LRA/FLA : 96 A / 22 A @ 240 Vac (AC coil), 30,000 cycles;
110 A / 25�3 A @ 240 Vac (DC coil), 30,000 cycles
Pilot Duty: 720 VA / A300, 6,000 cycles
Short Circuit: 5000 A(rms) @ 240 Vac
Tungsten: 10 A at 120 Vac 50/60 Hz, 25,000 cycles;
6 A at 250 Vac 50/60 Hz, 25,000 cycles
(NC) Resistive: 3 A at 277 Vac 6,000 cycles;
3 A at 28 Vdc 100,000 cycles
Switching Capacity
Maximum: 7500 VA / 840 W (when mounted with 13 mm gap between 2 relays); 6250 VA / 700 W (when mounted side by side without a gap)
Minimum:
170 mW
Minimum Switching
Requirements
10 mA at 17 V
Coil Characteristics
Coil Voltage Range112–240 Vac2 50/60 Hz; 12–24 Vdc
Operating Range
(% of Nominal)
80%–110%
Average Consumption 4 VA −20% / +10% (AC); 1.7 W −20% / +10% (DC)
Drop-out Voltage Threshold
15% minimum (AC); 10% minimum (DC)
General Characteristics
Electrical Life at Rated Load
Resistive load: 100,000 cycles, unless otherwise specified under “Current Ratings at Voltage”
Inductive load: See load curves on page 25�
Mechanical Life at No
Load (Unpowered)
5,000,000 operations
Operating Time
(Response Time) at
Nominal Coil Voltage
25 ms maximum
Rated Impulse Withstand 4000 V (1�2 μs / 50 μs)
Dielectric Strength Between coil and contact: 4000 Vac
Between poles: 2000 Vac
Between contacts: 1500 Vac
Operating Temperature
Range
−40 to +55 °C ( −40 to +131 °F)
Storage Temperature Range
−40 to +85 °C (−40 to +185 °F)
Vibration Resistance ± 1 mm (10–35 Hz) and 3 g-n (35–150 Hz)
Shock Resistance 10 g-n (in operation) / 30 g-n (not in operation)
Weight (Average) 0�082 kg (0�181 oz)
Conformity to Standards IEC/EN 61810-1, UL 508, CSA C22-2 n°14
Agency Certifications UL Listed (E164862), CSA (225619), CE (per IEC 60947-1), RoHS
Note: Actual product performance may vary depending on application and environmental conditions.
1 For available standard coil voltages, refer to the standard part number table on page 23.
2 All AC coils are rectified.