D-UFB-IB-S-RBO Order No.: 2748360
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2748360
PHOENIX CONTACT Deutschland GmbH Page 3 / 5
http://www.phoenixcontact.de Feb 2, 2011
Output voltage limitation at 1 kV/µs (Core-Core)
static
≤ 12 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 12 V
Output voltage limitation at 1 kV/µs (Core-GND)
static
≤ 12 V
Residual voltage at In, (conductor-conductor) ≤ 30 V
Residual voltage at In, (conductor-ground) ≤ 30 V
Residual voltage at In, (conductor-GND) ≤ 30 V
Protection level UP (Core-Core) ≤ 35 V
Protection level UP (Core-Earth) ≤ 35 V
Response time tA (Core-Core) ≤ 500 ns
Response time tA (Core-Earth) ≤ 500 ns
≤ 500 ns
Input attenuation aE, sym. 0.1 dB (≤ 7 MHz)
0.1 dB (≤ 8.5 MHz)
0.1 dB (up to 2.5 MHz 600 Ohm Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm
system
Typ. 100 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm
system
> 100 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm
system
Typ. 30 MHz
Capacity (Core-Core) 50 pF
Capacity (Core-GND) 50 pF
Capacity (Core-Earth) 50 pF
Surge carrying capacity in acc. with IEC 61643-21
(Core-Core)
C1 (500 V / 250 A)
Surge carrying capacity in acc. with IEC 61643-21
(Core-Earth)
C1 (500 A/250 A)
Connection data
Type of connection D-SUB-9
Connection type IN D-SUB-9 socket
Connection type OUT D-SUB-9 connector
Connection method Remote bus output
Connection, protective circuit
Standards/regulations IEC 61643-21