Edition: September 2014
C53000-L2140-A320-4
SIPROTEC
Overcurrent Time Protection
7SJ80
Motor Protection
7SK80
Voltage and Frequency
Protection
7RW80
Communication Modules
PROFIBUS DP
Bus mapping
Preface
Table of contents
Data in the PROFIBUS DP messages 1
Standard mapping 3-1 2
Standard mapping 3-2 3
Standard mapping 3-3 4
Index
Siemens AG
C53000-L2140-A320-4
Disclaimer of Liability
We have checked the contents of this manual against the
hardware and software described. However, since deviations
cannot be ruled out entirely, we do not accept liability for complete
conformity or for any an y errors or omissions.
The information provided in this manual is checked at regular
intervals and any corrections that might become necessary are
included in the next releases.
We are grateful for any improvements that you care to suggest.
We reserve the right to make technical improvements without
notice.
Document version: V01.10.02
Copyright
Copyright © Siemens AG 2014. All rights reserved.
Dissemination or reproduction of this document, or evaluation and
communication of its contents, is not authorized except where
expressly permitted. Offenders are liable for the payment of
damages. All rights, including rights created by patent grant or
registration of a utility model or design, are reserved.
Registered Trademarks
SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks
of SIEMENS AG. Other designations in this manual may be
trademarks whose use by third parties for their own purposes would
infringe the rights of the owner.
3SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Preface
Purpose of this
manual This manual describes the data in the messages of the PROFIBUS DP slave for the
SIPROTEC devices 7SJ80, 7SK80 and 7R W80.
It is divided into the followin g topic s:
Data in the PROFIBUS DP messages Chapter 1,
Standard map pin g 3- 1 Chap te r 2,
Standard map pin g 3- 2 Chap te r 3,
Standard mapping 3-3 -> Chapter 4.
General informatio n on the oper ation, asse mbly, commissioning an d configur ation of
the SIPROTEC devices you find in the following manuals:
PROFIBUS DP
communication
profile
The following man u al inform s yo u ab ou t bus-specific parameters, data type
definitions, settings and hardware description of the PROFIBUS DP communication
modules for SIPROTEC devices:
You can order the manuals
via the internet un de r http://www.siprotec.com
or contact your local Siemens representative.
PROFIBUS DP
specification The PROFIBUS DP specification and the structure of the PROFIBUS DP messages
are defined in the international standards:
IEC 61158
"Digital data communications for mea surement and control -
Fieldbus for use in industrial control systems"
Communication profile type 3
IEC 61784
"Digital data communications for mea surement and control"
Communication profile family CPF3/1
Manual Order number
SIPROTEC 4 System Description E50417-H1176-C151
7SJ80 Device Manual E50417-G1140-C343
7SK80 Device Manual E50417-G1140-C344
7RW80 Device Manual C53000-G1140-C233
Manual Order number
SIPROTEC Communication module,
PROFIBUS DP - Communication profile C53000-L1840-B001-03
Preface
4 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Validity of this
manual This manual is valid for the SIPROTEC devices:
7SJ80 (Firmware ver sion V4.60 or higher),
7SK80 (Firmware version V4.60 or higher)
7RW80 /Firmware version V4.60 o r higher)
with
PROFIBUS DP communication module firmware version 04.03.01 or higher.
The following have to be used for device parameterization:
DIGSI version 4.82 or higher,
PROFIBUS DP Standard mappings 3-1, 3-2 and 3-3 for 7SJ80, 7SK80 and
7RW80.
Additional
support For questions regarding the SIPROTEC system, please contact your Siemens
representative.
Training courses Individual course offerings may be found in our Training Catalog, or questions may be
directed to our Traini ng Center in Nuremberg.
Target audience Protection engineers, commissioning engineers, personnel concerned with
adjustment, checking, and service of selective protective equipment, automatic and
control facilities, and personnel of electrical facilities and power plants.
Note:
With the 7SJ80, 7SK80 and 7RW80 SIPROTEC devices, only PROFIBUS DP
communication modules of hardware version 4 or higher are use d (for a description
of the hardware versions of the PROFIBUS DP communication modules, ref. to
manual “SIPROTEC Communication module, PROFIBUS DP - Communication
profile”).
Preface
5
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
QUALIFIED PERSONNEL
Within the meaning of safety precautions of this manual and the instructions, qualified
personnel are those persons who are qualified to set up, install, place into service, and
operate this device, and who possess the following qualifications:
Training and instruction (or other qualification) for switching, grounding, and
designating devices and systems.
Training or instruction in accordan ce with safety standards for care and use of
certain safety equipment.
First aid training.
Typographic and
graphical
conventions
The following text formats are used to identify concepts giving device information
described by the text flow:
Parameter names, or identifiers for configuration or function parame ters that appear in
the device display or on the screen of a PC (with DIGSI) are shown in mono-script
(same point size) bold text. This also applies to he ader bars for selection menus.
Parameter conditions, or possible settings of parameters that appear in the device
display or on the screen of a PC (with DIGSI), are additionally shown in italic style. This
also applies to selection items for selection menus.
"Annunciations", or identifiers for information produced by the device or required by
other devices or from the switchgear is shown in mono-script (same point size) and
placed into quotation marks.
For diagrams in which the identifier type results from the representation itself, text
conventions may differ from the above-mentioned.
Warning!
During operation of electrical equipment, certain parts of these devices are under high
voltage. Severe personal injury or property damag e can result if the device is not
handled properly.
Only qualified personnel should work on this equipment or in the vicinity of this
equipment. These personnel must be familiar with all warnings and service
procedures described in this manual, as well as with safety regulations.
Prerequisites to proper an d safe operation of this d evice are p roper tra nsport, pro per
storage, setup, installation, operation, and maintenance of the device, as well as
careful operation and servicing of the device within the scope of the warnings and
instructions of this manual.
In particular, the general facility and safety regulations for work with high-voltage
equipment (e.g. ANSI, IEC, EN, or other na tional or international regulations) must be
observed. Noncompliance may result in death, injury or significant equipment
damage.
Preface
6 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
7SIPROTEC PROFIBUS DP - Bus mapping7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Revision index
Listing of the changes between the editions of this manual:
Modified chapters /
pages Edition Reasons of modification
1 First edition, doc. no.: C53000-L2140-A320-1
15.09.2008
4, 26, 36 2 Correction, doc. no.: C53000-L2140-A320-2
10.10.2008
7RW80 added 3 Correction, doc. no.: C53000-L2140-A320-3
29.09.2010
Chapter 4 4 Correction, doc. no.: C53000-L2140-A320-4
03.09.2014
Revision index
8 SIPROTEC PROFIBUS DP - Bus mapping7SJ80/7SK80/7RW80
C53000-L2140-A320-4
9SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Table of contents
Preface.................................................................................................................................................. 3
Revision index ..................................................................................................................................... 7
1 Data in the PROFIBUS DP messages .............................................................................................. 11
1.1 Explanations......................................................................................................................... 12
1.2 Messages in output direction:
PROFIBUS DP master to SIPROTEC device ...................................................................... 14
1.3 Messages in input direction:
SIPROTEC device to PROFIBUS DP master ...................................................................... 15
1.3.1 Annunciations....................................................................................................................... 15
1.3.2 Measured values.................................................................................................................. 15
1.3.3 Metered measurands............................................................................................................ 16
1.4 Configuration data of the standard mappings.......................... ... .... ... ... ... .... ... ... ... ... .... ... ... ... 17
1.5 Notes on SIPROTEC objects ............................................................................................... 19
1.5.1 Changing the setting group .................................................................................................. 19
2 Standard mapping 3-1................ ... .... ... ... ... ... .... ... ................ ... .... ... ... ... ... .... ... ... ... .... ... ... ... ................ 21
2.1 Message in output direction..................................................................................................22
2.1.1 Double commands................................................................................................................ 22
2.1.2 Internal commands............................................................................................................... 23
2.1.3 User-defined single commands or taggings......................................................................... 23
2.2 Message in input direction.................................................................................................... 25
2.2.1 Annunciations....................................................................................................................... 25
2.2.1.1 Double-point indications................ ................ .... ... ... ... .... ... ... ... ... .... ... ... ... .... ................ ......... 25
2.2.1.2 Trips ..................................................................................................................................... 26
2.2.1.3 Alarms .................................................................................................................................. 26
2.2.1.4 Changing the setting group .................................................................................................. 27
2.2.1.5 Diagnosis.............................................................................................................................. 27
2.2.1.6 User-defined single-point indications or taggings................................................................. 28
2.2.2 Measured values.................................................................................................................. 29
2.2.3 Statistic values ........ ... ... ... .... ... ... ... ................ .... ... ... ... .... ... ... ... ... ................. ... ... ... ... ............. 29
2.2.4 Metered measurands............................................................................................................ 30
Table of contents
10 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3 Standard mapping 3-2 ....................................................................................................................... 31
3.1 Message in output direction............................ ... ... ... .... ... ... ... .... ... ................ ... ... .... ... ... ... ... ...32
3.1.1 Event list...............................................................................................................................32
3.1.2 Double commands......... .... ................ ... ... ... .... ... ... ... .... ... ................ ... ... .... ... ... ... .... ... ... ... ...... 32
3.1.3 Internal commands...............................................................................................................33
3.1.4 User-defined single commands or taggings ......................................................................... 34
3.2 Message in input direction................. ... ... ... .... ... ................ ... .... ... ... ... ... .... ... ... ................ ... ... 35
3.2.1 Annunciations....................................................................................................................... 35
3.2.1.1 Double-point indications ....................................................................................................... 35
3.2.1.2 Trips......................................................................................................................................36
3.2.1.3 Alarms................................................................................................................................... 36
3.2.1.4 Changing the setting group............. ... ... ... ... .... ... ................ ... .... ... ... ... ... .... ... ... ... .... ... ... ... ......37
3.2.1.5 Diagnosis.............................................................................................................................. 37
3.2.1.6 User-defined single-point indications or taggings........ ... ...................................................... 38
3.2.2 Measured values ........... .... ... ... ................ ... .... ... ... ... .... ... ... ... .... ................ ... ... ... .... ... ... ......... 39
3.2.3 Statistic values......................................................................................................................39
3.2.4 Metered measurands............................................................................................................40
3.2.5 Event list...............................................................................................................................40
4 Standard mapping 3-3 . .... ... ... ... ................. ... ... ... ... .... ... ... ... .... ... ................ ... ... .... ... ... ... .... ............... 41
4.1 Message in output direction ....... ............................. ............................. ............................. .. 42
4.1.1 Event list ........................................................................................................................... .. 42
4.1.2 Double commands .............................................................................................................. 42
4.1.3 Internal commands ............................................................................................................. 43
4.1.4 User-defined single commands or taggings ........... .... ... ... ... .... ... ... ................ ... .... ... ... ... ... .. 44
4.2 Message in input direction ................ ... ... ... .... ... ... ... .... ... ... ... ................ .... ... ... ... .... ... ... ... ..... 45
4.2.1 Annunciations ..................................................................................................................... 45
4.2.1.1 Double-point indications ..................................................................................................... 45
4.2.1.2 Trips ............................................................................................................................ ... ..... 46
4.2.1.3 Alarms ............................................................................................................................ ... .. 46
4.2.1.4 Changing the setting group ..................... ... .... ... ... ... .... ... ... ... .... ................ ... ... ... .... ... ... ...... .. 47
4.2.1.5 Diagnosis ............................................................................................................................ 47
4.2.1.6 User-defined single-point indications or taggings .......................... ... ... .... ... ................ ... ... .. 48
4.2.2 Measured values ................................................................................................................ 49
4.2.3 Statistic values ............................................................................................................... ..... 49
4.2.4 Metered measurands .......................................................................................................... 50
4.2.5 Event list ........................................................................................................................... .. 50
Glossary ............. ................ ................ ................ ................ ................ ................ ....................... ... ... .. 51
Index.................................................................................................................................................... 53
11SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Data in the PROFIBUS DP messages 1
This chapter gives explanations to the descriptions of the Profibus DP messages’ data
of the standard mapping an d note s on the evaluation of selected SIPROTEC objects
and on the configuration of the standard mapping in the PROFIBUS DP master.
1.1 Explanations 12
1.2 Messages in output direction: PROFIBUS DP master to SIPROTEC device 14
1.3 Messages in input direction: SIPROTEC device to PROFIBUS DP master 15
1.4 Configuration data of the standard mappings 17
1.5 Notes on SIPROTEC objects 21
Data in the PROFIBUS DP messages
12 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
1.1 Explanations
Chapters 2 to 3 define the data area of the PROFIBUS DP messages for data transfer
between the PROFIBUS DP slave of the SIPROTEC devices 7SJ80, 7SK80, 7RW80
and the PROFIBUS DP master.
Chapter 4 defines the data area of the PROFIBUS DP messages for data transfer
between the PROFIBUS DP slave of the SIPROTEC devices 7SJ80, 7SK80, 7RW80
and the PROFIBUS DP master.
The SIPROTEC objects listed in the PROFIBUS DP messages’ data area are sorted
by byte offset, beginning with 0.
Variables with data
type greater than or
equal to 1 byte
The offset defines the start of the most significant byte in the message, e.g.:
The measured value "Ia" is assigned to data byte 10 (most significant byte of the
measured value) and data byte 11 (least significant byte of the measured value) in the
PROFIBUS DP message.
Bit variables
(SP/SC, DP/DC) The offset indicates the byte which contains the bit value and the position of bit 0 of
the bit variable, e.g. (input message ):
Note:
The examples shown in this chapter 1.1 do not necessarily correspond to the real
allocation of the objects in the bus mapping.
Offset Designation of the
SIPROTEC objects Comment Scaling
(32767 corresponds
to ...)
Internal
object
no.
10 Ia = Current in phase A 3276.7 A 601
Offset Designation of the
SIPROTEC objects Comment Internal
object
no.
0 / 0 Breaker ON/OFF
OFF Circuit breaker -
0 / 1 Breaker ON/OFF
ON
Offset Designation of the
SIPROTEC objects Comment Internal
object
no.
2 / 0 50(N)/51(N)TRIP 1 = 50(N)/51(N) TRIP 1791
Data in the PROFIBUS DP messages
13
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
The checkback signal from the circuit breaker (as double-point indication) is located in
data byte 0, bit position 20 (bit 0) and 21 (bit 1).
The single-poin t ind ica tio n "50(N)/51(N)TRIP" is located in byte 2, bit position 20.
Note:
The definitio n of th e da ta type s (d ou b le- po int indic atio n , sing le- p oin t ind ication,
measured value, metered measur ands etc.) and information on setting parameters in
DIGSI are contained in the manual "SIPROTEC Communication module, PROFIBUS
DP - Communication profile" (ref. to page 3).
Data in the PROFIBUS DP messages
14 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
1.2 Messages in output direction:
PROFIBUS DP master to SIPROTEC device
The messages in PROFIBUS DP output direction (ref. to chap. 2.1, 3.1 and 4.1) allow:
command outputs throug h the output relays of the SIPROTEC devices
(external commands),
manipulation of taggings that can be changed with PROFIBUS DP
(internal commands).
Note:
The allocation of the output relays to the switching device s an d to the outpu t
channels is defined during the parameterization of the SIPROTEC de vices.
Depending on the device type and device composition, there may be less than
indicated output relays (and corresponding PROFIBUS DP message positions)
available in the SIPROT EC device.
Data in the PROFIBUS DP messages
15
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
1.3 Messages in input direction:
SIPROTEC device to PROFIBUS DP master
The messages in PROFIBUS DP input direction (ref. to chap. 2.2, 3.2 and 4.2) allow:
polling of switching devices' status and binary inputs,
transmission of annunciations, measured values and mete red measurands to the
PROFIBUS DP master.
1.3.1 Annunciations
1.3.2 Measured values
The given default scaling values for the measured values in the standard mapping
apply to installations with the following nominal operating values:
Full Scale Voltage (parameter address 1101):
1.01 ... 100.00 kV
Full Scale Current (parameter address 110 2):
10.01 ... 1000.00 A
Product of
Rated Primary Voltage (parameter address 0202) and
Matching ratio Phase-VT to Open-Delta-VT (parameter address 0206):
1.01 ... 100.00 kV
Note:
The allocation of the input channels to the binary inputs is defined during the
parameterizatio n of the devices.
Depending on the device type and device composition and the existing protection
packages, not all of the indicated binary inputs or protection annunciations (and
corresponding PROFIBUS DP message positions) may be available in the
SIPROTEC device.
Note:
Depending on the device composition, not all of the indicated analog inputs
(and corresponding PROFIBUS DP message positions) may be available in the
SIPROTEC device.
Data in the PROFIBUS DP messages
16 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Ignd-CT rated primary current (parameter a ddress 0217)
10.01 ... 1000.00 A
Power values
Product of Full Scale Voltage and Full Scale Current multiplies by 
10.01 ... 1000.00 MW (MVAR)
1.3.3 Metered measurands
Scaling The scaling of the metered measurands, which are derived from measured values,
refers to:
60000 impulses per hour for V = Vnom and I = Inom
Vnom = Full Scale Voltage (parameter address 1101)
Inom = Full Scale Current (parameter address 1102)
Example In the para meter set is configured:
Inom = 100 A and Vnom = 12 kV,
60000 impulses correspond so that:
1 h * 100 A * 12 kV *  = 2078.46 kWh
Note:
Changes of the scaling of the measured values are possible in adaptation to the
concrete installation environment.
You find information about this in the manual "SIPROTEC Communication module,
PROFIBUS DP - Communication profile" (ref. to page 3).
Note:
The type of update (cyclic, with or without deletion) and the update interval must be
programmed fo r the metered measura nds using the parameterization software
DIGSI.
The scaling of the m etered measura nds at binary inpu ts (pulse counter s) depends
on the externally connected pulse generator.
Data in the PROFIBUS DP messages
17
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
1.4 Configuration data of the standard mappings
There are two standard mappings (standard mapping 3-1 to standard mapping 3-2)
available for the parameterization of the SIPROTEC devices 7SJ80, 7SK80 and
7RW80, and one standard mapping (standard mapping 3-3) available for SIPROTEC
devices 7SJ80, 7SK80 and 7RW80, which differ in the data size of the PROFIBUS DP
messages.
Standard mapping
3-1 Standard mappin g 3- 1 co nt ain s:
Output direction:
8 double commands
16 single commands
Input direction:
8 double-point indications
64 single-point indications
19 measured values (integer)
1 counter of operating hours (unsigned long)
4 metered measurands (unsigned long)
Standard mapping
3-2 Standard mappin g 3- 2 co nt ain s:
Output direction:
Handshake byte for event list via PROFIBUS DP
8 double commands
16 single commands
Input direction:
8 double-point indications
64 single-point indications
19 measured values (integer)
1 counter of operating hours (unsigned long)
4 metered measurands (unsigned long)
Handshake byte and three message blocks for event list via PROFIBUS DP
Standard mapping
3-3 Standard mappin g 3- 3 co nt ain s:
Output direction:
Handshake byte for event list via PROFIBUS DP
8 double commands
16 single commands
Input direction:
8 double-point indications
64 single-point indications
Data in the PROFIBUS DP messages
18 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
19 measured values (integer)
1 counter of ope ra tin g ho ur s (u ns ign ed lon g)
4 metered measurands (unsigned long)
Handshake byte and three message blocks fo r event list via PROFIBUS DP
PROFIBUS DP
Configuration data Standard mapping 3-1: 1FH 1FH 1FH 1FH 13H 25H
(68 bytes input, 6 bytes output direction)
Standard mapping 3-2: 1FH 1FH 1FH 1FH 13H DFH 27H
(100 bytes input, 8 bytes output direction)
Standard mapping 3-3: 1FH 1FH 1FH 1FH 13H DFH 27H
(100 bytes input, 8 bytes output direction)
Data in the PROFIBUS DP messages
19
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
PROFIBUS DP
master When co nf ig urin g a PRO FI B US DP slave of the SIPROTEC devices in the
parameterization system of the PROFIBUS DP master, the following modules for the
7SJ80, 7SK80 and 7RW80 standard mappings 3-1, 3-2 and 3-3 must be selected and
associated addresses in the I/O addre ss range of the PROFIBUS DP master must be
allocated:
Standard map pin g 3- 1:
Standard map pin g 3- 2:
Standard map pin g 3- 3:
Adr_Ix and Adr_Ox indicate arbitrary (usually even) addresses in the I/O address
range of the PROFIBUS DP master.
Module Order number Input address Output
address
0 Input - 16 bytes Adr_Ix
1 Input - 16 bytes Adr_Ix + 16
2 Input - 16 bytes Adr_Ix + 32
3 Input - 16 bytes Adr_Ix + 48
4 Input - 4 bytes Adr_Ix + 64
7 Output - 6 by te s Adr_Ox
Module Order number Input address Output
address
0 Input - 16 bytes Adr_Ix
1 Input - 16 bytes Adr_Ix + 16
2 Input - 16 bytes Adr_Ix + 32
3 Input - 16 bytes Adr_Ix + 48
4 Input - 4 bytes Adr_Ix + 64
5 Input - 16 words, consistent Adr_Ix + 68
6 Output - 8 by te s Adr_Ox
Module Order number Input address Output
address
0 Input - 16 bytes Adr_Ix
1 Input - 16 bytes Adr_Ix + 16
2 Input - 16 bytes Adr_Ix + 32
3 Input - 16 bytes Adr_Ix + 48
4 Input - 4 bytes Adr_Ix + 64
5 Input - 16 words, consistent Adr_Ix + 68
6 Output - 8 by te s Adr_Ox
Data in the PROFIBUS DP messages
20 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Adr_Ix (base address of the inputs) is identical with offset 0 of the PROFIBUS DP
message data of the SIPROTEC device in input direction (r ef. to chap. 2.2 and 3.2).
Adr_Ix (base address of the outputs) is identical with offset 0 of the PROFIBUS DP
message data of the SIPROTEC de vice in o utput dir ectio n (re f. to chap . 2.1 and 3.1 ).
Note:
Depending on the PROFIBUS DP master, there may also be the demand to put the
base address of the inputs (Adr_Ix) on a value divisible by four so that accesses to the
metered measurands (unsigned long values) of the SIPROTEC device (ref. to chap.
2.2.4 and 3.2.4) can be carried out correctly in the PROFIBUS DP master.
Data in the PROFIBUS DP messages
21
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
1.5 Notes on SIPROTEC objects
This chapter contains notes concerning the use and evaluation of certain SIPROTEC
objects.
1.5.1 Changing the setting group
In order to change the setting gr oup, the value "10 " = ON must be transmitted for the
corresponding pair of bits and afterwards be reset to "00" = "Quiescent status"
(controlled by an impulse from the PROFIBUS DP master).
Switching ON one setting group automatically switches OFF the currently active
setting group.
Transmission of the value "01" = OFF is insignificant for the change of the setting
group and is refused by the SIPROTEC device.
A change of the setting group via PROFIBUS DP is only possible if the parameter
Change to Another Setting Group (parameter address = 0302) has the value
Protocol.
References Standard map pin g 3- 1: ref. to chap. 2.1.2
Standard map pin g 3- 2: ref. to chap. 3.1.3
Standard mapping 3-3: ref. to chap. 4.1.3
Note:
The description of the standard mappings (ref. to chap. 2 and 3) contains the pre-
allocation of the mapping files at delivery or at first assignment of a mapping in
DIGSI to the SIPROTEC device.
Changes of the allocation and the scaling of the measured value s are possible in
adaptation to the concrete installation environment.
You find information about this in the manual "SIPROTEC Communication module,
PROFIBUS DP - Communication profile" (ref. to page 3).
If a mapping file is assigned to a SIPROTEC device and if the data size of the
PROFIBUS DP message of this SIPROTEC device is changed by choice of a new
mapping file, then assig nments which are not available in the existing mapping file
remain unassigned furthermore.
These must afterwards be routed again on "Source system interface" or
"Destination system interface" using the DIGSI Configuration matrix.
Data in the PROFIBUS DP messages
22 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
21SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Standard mapping 3-1 2
This chapter descr ibes the PROFIBUS DP messages’ data between the
PROFIBUS DP master and the SIPROT EC devices 7SJ80, 7SK80 and 7RW80 if
standard mapping 3-1 is selected.
2.1 Message in output direction 22
2.2 Message in input direction 25
Standard mapping 3-1
22 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.1 Message in output direction
2.1.1 Double commands
User-defined double commands with double-point indications as checkback
indication can be routed on these positions as a "Source system interface" using
the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
0 / 0 52 Breaker
OFF 52 Breaker -
0 / 1 52 Breaker
ON
0 / 2 <user-defined>
OFF not pre-allocated -
0 / 3 <user-defined>
ON
0 / 4 <user-defined>
OFF not pre-allocated -
0 / 5 <user-defined>
ON
0 / 6 <user-defined>
OFF not pre-allocated -
0 / 7 <user-defined>
ON
1 / 0 <user-defined>
OFF not pre-allocated -
1 / 1 <user-defined>
ON
1 / 2 <user-defined>
OFF not pre-allocated -
1 / 3 <user-defined>
ON
1 / 4 <user-defined>
OFF not pre-allocated -
1 / 5 <user-defined>
ON
1 / 6 <user-defined>
OFF not pre-allocated -
1 / 7 <user-defined>
ON
Standard mapping 3-1
23
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.1.2 Internal commands
Ref. to chap. 1.5.1 for additional notes regarding "Changing the setting group".
2.1.3 User-defined single commands or taggings
User-defined single commands or taggings can be routed on these positions as a
"Source system interface" using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 Group A -
2 / 1 Group A Activation of setting group A
2 / 2 Group B -
2 / 3 Group B Activation of setting group B
2 / 4 Group C -
2 / 5 Group C Activation of setting group C
2 / 6 Group D -
2 / 7 Group D Activation of setting group D
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
3 / 0 <user-defined> OFF not pre-allocated -
3 / 1 <user-defined> ON
3 / 2 <user-defined> OFF not pre-allocated -
3 / 3 <user-defined> ON
3 / 4 <user-defined> OFF not pre-allocated -
3 / 5 <user-defined> ON
3 / 6 <user-defined> OFF not pre-allocated -
3 / 7 <user-defined> ON
4 / 0 <user-defined> OFF not pre-allocated -
4 / 1 <user-defined> ON
4 / 2 <user-defined> OFF not pre-allocated -
4 / 3 <user-defined> ON
4 / 4 <user-defined> OFF not pre-allocated -
4 / 5 <user-defined> ON
4 / 6 <user-defined> OFF not pre-allocated -
4 / 7 <user-defined> ON
5 / 0 <user-defined> OFF not pre-allocated -
5 / 1 <user-defined> ON
Standard mapping 3-1
24 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
5 / 2 <user-defined> OFF not pre-allocated -
5 / 3 <user-defined> ON
5 / 4 <user-defined> OFF not pre-allocated -
5 / 5 <user-defined> ON
5 / 6 <user-defined> OFF not pre-allocated -
5 / 7 <user-defined> ON
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Standard mapping 3-1
25
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2 Message in input direction
2.2.1 Annunciations
2.2.1.1 Double-point indications
User-defined double-point indications (e.g., checkback indications of double
commands) can be routed on these positions as a "Destination system interface"
using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
0 / 0 52 Breaker
OFF Checkback indication 52 Breaker -
0 / 1 52 Breaker
ON
0 / 2 <user-defined>
OFF not pre-allocated -
0 / 3 <user-defined>
ON
0 / 4 <user-defined>
OFF not pre-allocated -
0 / 5 <user-defined>
ON
0 / 6 <user-defined>
OFF not pre-allocated -
0 / 7 <user-defined>
ON
1 / 0 <user-defined>
OFF not pre-allocated -
1 / 1 <user-defined>
ON
1 / 2 <user-defined>
OFF not pre-allocated -
1 / 3 <user-defined>
ON
1 / 4 <user-defined>
OFF not pre-allocated -
1 / 5 <user-defined>
ON
1 / 6 <user-defined>
OFF not pre-allocated -
1 / 7 <user-defined>
ON
Standard mapping 3-1
26 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2.1.2 Trips
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
2.2.1.3 Alarms
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 50(N)/51(N)TRIP 1 = 50(N)/51(N) TRIP 1791
2 / 1 <user-defined> not pre-allocated -
2 / 2 <user-defined> not pre-allocated -
2 / 3 <user-defined> not pre-allocated -
2 / 4 <user-defined> not pre-allocated -
2 / 5 <user-defined> not pre-allocated -
2 / 6 <user-defined> not pre-allocated -
2 / 7 <user-defined> not pre-allocated -
3 / 0 <user-defined> not pre-allocated -
3 / 1 <user-defined> not pre-allocated -
3 / 2 <user-defined> not pre-allocated -
3 / 3 <user-defined> not pre-allocated -
3 / 4 <user-defined> not pre-allocated -
3 / 5 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
3 / 6 50(N)/51(N) PU 1 = 50(N)/51(N) O/C PICKUP 1761
3 / 7 <user-defined> not pre-allocated -
4 / 0 <user-defined> not pre-allocated -
4 / 1 <user-defined> not pre-allocated -
4 / 2 <user-defined> not pre-allocated -
4 / 3 <user-defined> not pre-allocated -
4 / 4 <user-defined> not pre-allocated -
4 / 5 <user-defined> not pre-allocated -
4 / 6 <user-defined> not pre-allocated -
4 / 7 <user-defined> not pre-allocated -
5 / 0 <user-defined> not pre-allocated -
Standard mapping 3-1
27
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2.1.4 Changing the setting group
2.2.1.5 Diagnosis
5 / 1 <user-defined> not pre-allocated -
5 / 2 <user-defined> not pre-allocated -
5 / 3 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
5 / 4 P-GrpA act 1 = Setting Group A is active -
5 / 5 P-GrpB act 1 = Setting Group B is active -
5 / 6 P-GrpC act 1 = Setting Group C is active -
5 / 7 P-GrpD act 1 = Setting Group D is active -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
6 / 0 Device OK 1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart 51
6 / 1 ProtActive 1 = At least one protection function is active 52
6 / 2 Settings Calc. 1 = Settings calculation is running 70
6 / 3 Error Sum Alarm 1 = Error with a summary alarm ON 140
6 / 4 Alarm Sum Event 1 = Alarm summary event ON 160
6 / 5 Relay PICKUP 1 = Relay PICKUP (group signal) 501
6 / 6 Relay TRIP 1 = Relay GENERAL TRIP command 511
6 / 7 Data valid 1 = Data in the PROFIBUS DP message are valid.
(This indication is created by the PROFIBUS DP
slave; not available in DIGSI and not relocata ble.) -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Standard mapping 3-1
28 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2.1.6 User-defined single-point indications or taggings
User-defined pr ot ection annunci at ion s, si ngle-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
7 / 0 <user-defined> not pre-allocated -
7 / 1 <user-defined> not pre-allocated -
7 / 2 <user-defined> not pre-allocated -
7 / 3 <user-defined> not pre-allocated -
7 / 4 <user-defined> not pre-allocated -
7 / 5 <user-defined> not pre-allocated -
7 / 6 <user-defined> not pre-allocated -
7 / 7 <user-defined> not pre-allocated -
8 / 0 <user-defined> not pre-allocated -
8 / 1 <user-defined> not pre-allocated -
8 / 2 <user-defined> not pre-allocated -
8 / 3 <user-defined> not pre-allocated -
8 / 4 <user-defined> not pre-allocated -
8 / 5 <user-defined> not pre-allocated -
8 / 6 <user-defined> not pre-allocated -
8 / 7 <user-defined> not pre-allocated -
9 / 0 <user-defined> not pre-allocated -
9 / 1 <user-defined> not pre-allocated -
9 / 2 <user-defined> not pre-allocated -
9 / 3 <user-defined> not pre-allocated -
9 / 4 <user-defined> not pre-allocated -
9 / 5 <user-defined> not pre-allocated -
9 / 6 <user-defined> not pre-allocated -
9 / 7 <user-defined> not pre-allocated -
Standard mapping 3-1
29
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2.2 Measured values
Ref. to chap. 1.3.2 for additional notes regarding scaling of metered measurands.
2.2.3 Statistic values
Offset Designation of the
SIPROTEC objects Comment Scaling
(32767 corresponds
to ...)
Internal
object
no.
10 Ia = Ia 3276.7 A 601
12 Ib = Ib 3276.7 A 602
14 Ic = Ic 3276.7 A 603
16 In = In 3276.7 A 604
18 Va-b = Va-b 327.67 kV 624
20 Vb-c = Vb-c 327.67 kV 625
22 Vc-a = Vc-a 327.67 kV 626
24 VN = VN 327.67 kV 627
26 P = P (active power) 327.67 MW 641
28 Q = Q (reactive power) 327.67 MVAR 642
30 S = S (apparent power) 327.67 MVA 645
32 Freq = Frequency 327.67 Hz 644
34 PF = Power Factor 3.2767 901
36 <user-defined> not pre-allocated - -
38 <user-defined> not pre-allocated - -
40 <user-defined> not pre-allocated - -
42 <user-defined> not pre-allocated - -
44 <user-defined> not pre-allocated - -
46 <user-defined> not pre-allocated - -
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
48 Op.Hours = Counter of operating hou rs of the primary
equipment 231-1 hours 1020
Standard mapping 3-1
30 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
2.2.4 Metered measurands
Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measu rands.
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
52 WpForward = Wp Forward
(metered measurand derived from measured
values) 231-1 impulses 924
56 WqForward = Wq Forward
(metered measurand derived from measured
values) 231-1 impulses 925
60 WpReverse = Wp Reverse
(metered measurand derived from measured
values) 231-1 impulses 928
64 WqReverse = Wq Reverse
(metered measurand derived from measured
values) 231-1 impulses 929
31SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Standard mapping 3-2 3
This chapter descr ibes the PROFIBUS DP messages’ data between the
PROFIBUS DP master and the SIPROT EC devices 7SJ80, 7SK80 and 7RW80 if
standard mapping 3-2 is selected.
3.1 Message in output direction 32
3.2 Message in input direction 35
Standard mapping 3-2
32 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.1 Message in output direction
3.1.1 Event list
Information regarding the handshake bytes as well as the retrieval methods of the
event list via PROFIB US DP can be found in the ma nu a l “SIPROTEC
Communication module, PROFIBUS DP - Communication profile”.
3.1.2 Double commands
User-defined do ub le -co mm an ds with do ub le -p oin t ind ica tio ns as checkb ack
indication can be routed on these positions as a "Source system interface" using
the DIGSI Configuration matrix.
Offset Designation Comment Internal
object
no.
0 Control_O Handshake byte for event list via PROFIBUS DP -
1 SPARE reserved for future use
(the value in this position is ignored) -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 52 Breaker
OFF 52 Breaker -
2 / 1 52 Breaker
ON
2 / 2 <user-defined>
OFF not pre-allocated -
2 / 3 <user-defined>
ON
2 / 4 <user-defined>
OFF not pre-allocated -
2 / 5 <user-defined>
ON
2 / 6 <user-defined>
OFF not pre-allocated -
2 / 7 <user-defined>
ON
3 / 0 <user-defined>
OFF not pre-allocated -
3 / 1 <user-defined>
ON
Standard mapping 3-2
33
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.1.3 Internal commands
Ref. to chap. 1.5.1 for additional notes regarding "Changing the setting group".
3 / 2 <user-defined>
OFF not pre-allocated -
3 / 3 <user-defined>
ON
3 / 4 <user-defined>
OFF not pre-allocated -
3 / 5 <user-defined>
ON
3 / 6 <user-defined>
OFF not pre-allocated -
3 / 7 <user-defined>
ON
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
4 / 0 Group A -
4 / 1 Group A Activation of setting group A
4 / 2 Group B -
4 / 3 Group B Activation of setting group B
4 / 4 Group C -
4 / 5 Group C Activation of setting group C
4 / 6 Group D -
4 / 7 Group D Activation of setting group D
Standard mapping 3-2
34 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.1.4 User-defined single commands or taggings
User-defined single commands or taggings can be routed on these positions as a
"Source system interface" using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
5 / 0 <user-defined> OFF not pre-allocated -
5 / 1 <user-defined> ON
5 / 2 <user-defined> OFF not pre-allocated -
5 / 3 <user-defined> ON
5 / 4 <user-defined> OFF not pre-allocated -
5 / 5 <user-defined> ON
5 / 6 <user-defined> OFF not pre-allocated -
5 / 7 <user-defined> ON
6 / 0 <user-defined> OFF not pre-allocated -
6 / 1 <user-defined> ON
6 / 2 <user-defined> OFF not pre-allocated -
6 / 3 <user-defined> ON
6 / 4 <user-defined> OFF not pre-allocated -
6 / 5 <user-defined> ON
6 / 6 <user-defined> OFF not pre-allocated -
6 / 7 <user-defined> ON
7 / 0 <user-defined> OFF not pre-allocated -
7 / 1 <user-defined> ON
7 / 2 <user-defined> OFF not pre-allocated -
7 / 3 <user-defined> ON
7 / 4 <user-defined> OFF not pre-allocated -
7 / 5 <user-defined> ON
7 / 6 <user-defined> OFF not pre-allocated -
7 / 7 <user-defined> ON
Standard mapping 3-2
35
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2 Message in input direction
3.2.1 Annunciations
3.2.1.1 Double-point indications
User-defined double-point indications (e.g., checkback indications of double
commands) can be routed on these positions as a "Destination system interface"
using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
0 / 0 52 Breaker
OFF Checkback indication 52 Breaker -
0 / 1 52 Breaker
ON
0 / 2 <user-defined>
OFF not pre-allocated -
0 / 3 <user-defined>
ON
0 / 4 <user-defined>
OFF not pre-allocated -
0 / 5 <user-defined>
ON
0 / 6 <user-defined>
OFF not pre-allocated -
0 / 7 <user-defined>
ON
1 / 0 <user-defined>
OFF not pre-allocated -
1 / 1 <user-defined>
ON
1 / 2 <user-defined>
OFF not pre-allocated -
1 / 3 <user-defined>
ON
1 / 4 <user-defined>
OFF not pre-allocated -
1 / 5 <user-defined>
ON
1 / 6 <user-defined>
OFF not pre-allocated -
1 / 7 <user-defined>
ON
Standard mapping 3-2
36 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2.1.2 Trips
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
3.2.1.3 Alarms
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 50(N)/51(N)TRIP 1 = 50(N)/51(N) TRIP 1791
2 / 1 <user-defined> not pre-allocated -
2 / 2 <user-defined> not pre-allocated -
2 / 3 <user-defined> not pre-allocated -
2 / 4 <user-defined> not pre-allocated -
2 / 5 <user-defined> not pre-allocated -
2 / 6 <user-defined> not pre-allocated -
2 / 7 <user-defined> not pre-allocated -
3 / 0 <user-defined> not pre-allocated -
3 / 1 <user-defined> not pre-allocated -
3 / 2 <user-defined> not pre-allocated -
3 / 3 <user-defined> not pre-allocated -
3 / 4 <user-defined> not pre-allocated -
3 / 5 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
3 / 6 50(N)/51(N) PU 1 = 50(N)/51(N) O/C PICKUP 1761
3 / 7 <user-defined> not pre-allocated -
4 / 0 <user-defined> not pre-allocated -
4 / 1 <user-defined> not pre-allocated -
4 / 2 <user-defined> not pre-allocated -
4 / 3 <user-defined> not pre-allocated -
4 / 4 <user-defined> not pre-allocated -
4 / 5 <user-defined> not pre-allocated -
4 / 6 <user-defined> not pre-allocated -
4 / 7 <user-defined> not pre-allocated -
5 / 0 <user-defined> not pre-allocated -
Standard mapping 3-2
37
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2.1.4 Changing the setting group
3.2.1.5 Diagnosis
5 / 1 <user-defined> not pre-allocated -
5 / 2 <user-defined> not pre-allocated -
5 / 3 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
5 / 4 Group A 1 = Group A is active -
5 / 5 Group B 1 = Group B is active -
5 / 6 Group C 1 = Group C is active -
5 / 7 Group D 1 = Group D is active -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
6 / 0 Device OK 1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart 51
6 / 1 ProtActive 1 = At least one protection function is active 52
6 / 2 Settings Calc. 1 = Settings calculation is running 70
6 / 3 Error Sum Alarm 1 = Error with a summary alarm ON 140
6 / 4 Alarm Sum Event 1 = Alarm summary event ON 160
6 / 5 Relay PICKUP 1 = Relay PICKUP (group signal) 501
6 / 6 Relay TRIP 1 = Relay GENERAL TRIP command 511
6 / 7 Data valid 1 = Data in the PROFIBUS DP message are valid.
(This indication is created by the PROFIBUS DP
slave; not available in DIGSI and not relocata ble.) -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Standard mapping 3-2
38 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2.1.6 User-defined single-point indications or taggings
User-defined pr ot ection annunci at ion s, si ngle-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
7 / 0 <user-defined> not pre-allocated -
7 / 1 <user-defined> not pre-allocated -
7 / 2 <user-defined> not pre-allocated -
7 / 3 <user-defined> not pre-allocated -
7 / 4 <user-defined> not pre-allocated -
7 / 5 <user-defined> not pre-allocated -
7 / 6 <user-defined> not pre-allocated -
7 / 7 <user-defined> not pre-allocated -
8 / 0 <user-defined> not pre-allocated -
8 / 1 <user-defined> not pre-allocated -
8 / 2 <user-defined> not pre-allocated -
8 / 3 <user-defined> not pre-allocated -
8 / 4 <user-defined> not pre-allocated -
8 / 5 <user-defined> not pre-allocated -
8 / 6 <user-defined> not pre-allocated -
8 / 7 <user-defined> not pre-allocated -
9 / 0 <user-defined> not pre-allocated -
9 / 1 <user-defined> not pre-allocated -
9 / 2 <user-defined> not pre-allocated -
9 / 3 <user-defined> not pre-allocated -
9 / 4 <user-defined> not pre-allocated -
9 / 5 <user-defined> not pre-allocated -
9 / 6 <user-defined> not pre-allocated -
9 / 7 <user-defined> not pre-allocated -
Standard mapping 3-2
39
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2.2 Measured values
Ref. to chap. 1.3.2 for additional notes regarding scaling of metered measurands.
3.2.3 Statistic values
Offset Designation of the
SIPROTEC objects Comment Scaling
(32767 corresponds
to ...)
Internal
object
no.
10 Ia = Ia 3276.7 A 601
12 Ib = Ib 3276.7 A 602
14 Ic = Ic 3276.7 A 603
16 In = In 3276.7 A 604
18 Va-b = Va-b 327.67 kV 624
20 Vb-c = Vb-c 327.67 kV 625
22 Vc-a = Vc-a 327.67 kV 626
24 VN = VN 327.67 kV 627
26 P = P (active power) 327.67 MW 641
28 Q = Q (reactive power) 327.67 MVAR 642
30 S = S (apparent power) 327.67 MVA 645
32 Freq = Frequency 327.67 Hz 644
34 PF = Power Factor 3.767 901
36 <user-defined> not pre-allocated - -
38 <user-defined> not pre-allocated - -
40 <user-defined> not pre-allocated - -
42 <user-defined> not pre-allocated - -
44 <user-defined> not pre-allocated - -
46 <user-defined> not pre-allocated - -
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
48 Op.Hours = Counter of operating hou rs of the primary
equipment 231-1 hours 1020
Standard mapping 3-2
40 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
3.2.4 Metered measurands
Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measu rands.
3.2.5 Event list
Information regarding the handshake bytes as well as the retrieval methods of the
event list via PROFIB US DP can be found in the ma nua l "SIPRO TEC
Communication module, PROFIBUS DP - Communication profile".
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
52 WpForward = Wp Forward
(metered measurand derived from measured
values) 231-1 impulses 924
56 WqForward = Wq Forward
(metered measurand derived from measured
values) 231-1 impulses 925
60 WpReverse = Wp Reverse
(metered measurand derived from measured
values) 231-1 impulses 928
64 WqReverse = Wq Reverse
(metered measurand derived from measured
values) 231-1 impulses 929
Offset Designation Comment Internal
object
no.
68 Control_I Handshake byte for event list via PROFIBUS DP -
69 SPARE reserved for future use
(the value 0 is transmitted in this position) -
70
Message block #1
Identification #1
-
71 Value #1
72
-
79 Time stamp #1
80
Message block #2
Identification #2
-
81 Value #2
82
-
89 Time stamp #2
90
Message block #3
Identification #3
-
91 Value #3
92
-
99 Time stamp #3
41SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Standard mapping 3-3 4
This chapter describes the PROFIBUS DP messages’ data between the PROFIBUS
DP master and the SIPROTEC devices 7SJ80, 7SK80 and 7RW80 if standard
mapping 3-3 is selected. The main purpose for this mapping is the application of
7SK80 with up to 12 RTD inputs through an RTD box.
4.1 Message in output direction 42
4.2 Message in input direction 45
Standard mapping 3-3
42 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.1 Message in output direction
4.1.1 Event list
Information regarding the handshake bytes as well as the retrieval methods of the
event list via PROFIB US DP can be found in the ma nu a l “SIPROTEC
Communication module, PROFIBUS DP - Communication profile”.
4.1.2 Double commands
User-defined do ub le -co mm an ds with do ub le -p oin t ind ica tio ns as checkb ack
indication can be routed on these positions as a "Source system interface" using
the DIGSI Configuration matrix.
Offset Designation Comment Internal
object
no.
0 Control_O Handshake byte for event list via PROFIBUS DP -
1 SPARE reserved for future use
(the value in this position is ignored) -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 52 Breaker
OFF 52 Breaker -
2 / 1 52 Breaker
ON
2 / 2 <user-defined>
OFF not pre-allocated -
2 / 3 <user-defined>
ON
2 / 4 <user-defined>
OFF not pre-allocated -
2 / 5 <user-defined>
ON
2 / 6 <user-defined>
OFF not pre-allocated -
2 / 7 <user-defined>
ON
3 / 0 <user-defined>
OFF not pre-allocated -
3 / 1 <user-defined>
ON
Standard mapping 3-3
43
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.1.3 Internal commands
Ref. to chap. 1.5.1 for additional notes regarding "Changing the setting group".
3 / 2 <user-defined>
OFF not pre-allocated -
3 / 3 <user-defined>
ON
3 / 4 <user-defined>
OFF not pre-allocated -
3 / 5 <user-defined>
ON
3 / 6 <user-defined>
OFF not pre-allocated -
3 / 7 <user-defined>
ON
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
4 / 0 Group A -
4 / 1 Group A Activation of setting group A
4 / 2 Group B -
4 / 3 Group B Activation of setting group B
4 / 4 Group C -
4 / 5 Group C Activation of setting group C
4 / 6 Group D -
4 / 7 Group D Activation of setting group D
Standard mapping 3-3
44 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.1.4 User-defined single commands or taggings
User-defined single commands or taggings can be routed on these positions as a
"Source system interface" using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
5 / 0 <user-defined> OFF not pre-allocated -
5 / 1 <user-defined> ON
5 / 2 <user-defined> OFF not pre-allocated -
5 / 3 <user-defined> ON
5 / 4 <user-defined> OFF not pre-allocated -
5 / 5 <user-defined> ON
5 / 6 <user-defined> OFF not pre-allocated -
5 / 7 <user-defined> ON
6 / 0 <user-defined> OFF not pre-allocated -
6 / 1 <user-defined> ON
6 / 2 <user-defined> OFF not pre-allocated -
6 / 3 <user-defined> ON
6 / 4 <user-defined> OFF not pre-allocated -
6 / 5 <user-defined> ON
6 / 6 <user-defined> OFF not pre-allocated -
6 / 7 <user-defined> ON
7 / 0 <user-defined> OFF not pre-allocated -
7 / 1 <user-defined> ON
7 / 2 <user-defined> OFF not pre-allocated -
7 / 3 <user-defined> ON
7 / 4 <user-defined> OFF not pre-allocated -
7 / 5 <user-defined> ON
7 / 6 <user-defined> OFF not pre-allocated -
7 / 7 <user-defined> ON
Standard mapping 3-3
45
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2 Message in input direction
4.2.1 Annunciations
4.2.1.1 Double-point indications
User-defined double-point indications (e.g., checkback indications of double
commands) can be routed on these positions as a "Destination system interface"
using the DIGSI Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
0 / 0 52 Breaker
OFF Checkback indication 52 Breaker -
0 / 1 52 Breaker
ON
0 / 2 <user-defined>
OFF not pre-allocated -
0 / 3 <user-defined>
ON
0 / 4 <user-defined>
OFF not pre-allocated -
0 / 5 <user-defined>
ON
0 / 6 <user-defined>
OFF not pre-allocated -
0 / 7 <user-defined>
ON
1 / 0 <user-defined>
OFF not pre-allocated -
1 / 1 <user-defined>
ON
1 / 2 <user-defined>
OFF not pre-allocated -
1 / 3 <user-defined>
ON
1 / 4 <user-defined>
OFF not pre-allocated -
1 / 5 <user-defined>
ON
1 / 6 <user-defined>
OFF not pre-allocated -
1 / 7 <user-defined>
ON
Standard mapping 3-3
46 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2.1.2 Trips
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
4.2.1.3 Alarms
User-defined protection annuncations, single-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
2 / 0 50(N)/51(N)TRIP 1 = 50(N)/51(N) TRIP 1791
2 / 1 <user-defined> not pre-allocated -
2 / 2 <user-defined> not pre-allocated -
2 / 3 <user-defined> not pre-allocated -
2 / 4 <user-defined> not pre-allocated -
2 / 5 <user-defined> not pre-allocated -
2 / 6 <user-defined> not pre-allocated -
2 / 7 <user-defined> not pre-allocated -
3 / 0 <user-defined> not pre-allocated -
3 / 1 <user-defined> not pre-allocated -
3 / 2 <user-defined> not pre-allocated -
3 / 3 <user-defined> not pre-allocated -
3 / 4 <user-defined> not pre-allocated -
3 / 5 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
3 / 6 50(N)/51(N) PU 1 = 50(N)/51(N) O/C PICKUP 1761
3 / 7 <user-defined> not pre-allocated -
4 / 0 <user-defined> not pre-allocated -
4 / 1 <user-defined> not pre-allocated -
4 / 2 <user-defined> not pre-allocated -
4 / 3 <user-defined> not pre-allocated -
4 / 4 <user-defined> not pre-allocated -
4 / 5 <user-defined> not pre-allocated -
4 / 6 <user-defined> not pre-allocated -
4 / 7 <user-defined> not pre-allocated -
5 / 0 <user-defined> not pre-allocated -
Standard mapping 3-3
47
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2.1.4 Changing the setting group
4.2.1.5 Diagnosis
5 / 1 <user-defined> not pre-allocated -
5 / 2 <user-defined> not pre-allocated -
5 / 3 <user-defined> not pre-allocated -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
5 / 4 Group A 1 = Group A is active -
5 / 5 Group B 1 = Group B is active -
5 / 6 Group C 1 = Group C is active -
5 / 7 Group D 1 = Group D is active -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
6 / 0 Device OK 1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart 51
6 / 1 ProtActive 1 = At least one protection function is active 52
6 / 2 Settings Calc. 1 = Settings calculation is running 70
6 / 3 Error Sum Alarm 1 = Error with a summary alarm ON 140
6 / 4 Alarm Sum Event 1 = Alarm summary event ON 160
6 / 5 Relay PICKUP 1 = Relay PICKUP (group signal) 501
6 / 6 Relay TRIP 1 = Relay GENERAL TRIP command 511
6 / 7 Data valid 1 = Data in the PROFIBUS DP message are valid.
(This indication is created by the PROFIBUS DP
slave; not available in DIGSI and not relocata ble.) -
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
Standard mapping 3-3
48 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2.1.6 User-defined single-point indications or taggings
User-defined pr ot ection annunci at ion s, si ngle-point indications or taggings can be
routed on these positions as a "Destination system interface" using the DIGSI
Configuration matrix.
Offset Designation of the SIPROTEC objects Comment Internal
object
no.
7 / 0 <user-defined> not pre-allocated -
7 / 1 <user-defined> not pre-allocated -
7 / 2 <user-defined> not pre-allocated -
7 / 3 <user-defined> not pre-allocated -
7 / 4 <user-defined> not pre-allocated -
7 / 5 <user-defined> not pre-allocated -
7 / 6 <user-defined> not pre-allocated -
7 / 7 <user-defined> not pre-allocated -
8 / 0 <user-defined> not pre-allocated -
8 / 1 <user-defined> not pre-allocated -
8 / 2 <user-defined> not pre-allocated -
8 / 3 <user-defined> not pre-allocated -
8 / 4 <user-defined> not pre-allocated -
8 / 5 <user-defined> not pre-allocated -
8 / 6 <user-defined> not pre-allocated -
8 / 7 <user-defined> not pre-allocated -
9 / 0 <user-defined> not pre-allocated -
9 / 1 <user-defined> not pre-allocated -
9 / 2 <user-defined> not pre-allocated -
9 / 3 <user-defined> not pre-allocated -
9 / 4 <user-defined> not pre-allocated -
9 / 5 <user-defined> not pre-allocated -
9 / 6 <user-defined> not pre-allocated -
9 / 7 <user-defined> not pre-allocated -
Standard mapping 3-3
49
SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2.2 Measured values
Ref. to chap. 1.3.2 for additional notes regarding scaling of metered measurands.
4.2.3 Statistic values
Offset Designation of the
SIPROTEC objects Comment Scaling
(32767 corresponds
to ...)
Internal
object
no.
10 Ia = Ia 3276.7 A 601
12 Ib = Ib 3276.7 A 602
14 Ic = Ic 3276.7 A 603
16 In = In 3276.7 A 604
18 <user-defined> not pre-allocated - -
20 <user-defined> not pre-allocated - -
22 <user-defined> not pre-allocated - -
24 <user-defined> not pre-allocated - -
26 <user-defined> not pre-allocated - -
28 <user-defined> not pre-allocated - -
30 <user-defined> not pre-allocated - -
32 <user-defined> not pre-allocated - -
34 <user-defined> not pre-allocated - -
36 <user-defined> not pre-allocated - -
38 <user-defined> not pre-allocated - -
40 <user-defined> not pre-allocated - -
42 <user-defined> not pre-allocated - -
44 <user-defined> not pre-allocated - -
46 <user-defined> not pre-allocated - -
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
48 Op.Hours = Counter of operating hou rs of the primary
equipment 231-1 hours 1020
Standard mapping 3-3
50 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
4.2.4 Metered measurands
Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measu rands.
4.2.5 Event list
Information regarding the handshake bytes as well as the retrieval methods of the
event list via PROFIB US DP can be found in the ma nua l "SIPRO TEC
Communication module, PROFIBUS DP - Communication profile".
Offset Designation of the
SIPROTEC objects Comment Scaling
(231-1 corresponds
to ...)
Internal
object
no.
52 WpForward = Wp Forward
(metered measurand derived from measured
values) 231-1 impulses 924
56 WqForward = Wq Forward
(metered measurand derived from measured
values) 231-1 impulses 925
60 WpReverse = Wp Reverse
(metered measurand derived from measured
values) 231-1 impulses 928
64 WqReverse = Wq Reverse
(metered measurand derived from measured
values) 231-1 impulses 929
Offset Designation Comment Internal
object
no.
68 Control_I Handshake byte for event list via PROFIBUS DP -
69 SPARE reserved for future use
(the value 0 is transmitted in this position) -
70
Message block #1
Identification #1
-
71 Value #1
72
-
79 Time stamp #1
80
Message block #2
Identification #2
-
81 Value #2
82
-
89 Time stamp #2
90
Message block #3
Identification #3
-
91 Value #3
92
-
99 Time stamp #3
51SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Glossary
CFC Continuous Function Chart
DC Double Command
DIGSI Parameterization system for SIPROTEC devices
DP Double-Point indication
SC Single Command
SP Single-Point indication
DDB file The DDB file contains the Device Data Base (technical characteristics) of the
PROFIBUS DP communication module.
This file is required for configuration and is supplied together with the SIPROTEC
device.
Input data/
input direction Data from the PROFIBUS DP slave to the PROFIBUS DP master.
Octet One octet corresponds to 8 bits.
OLM Optical Link Module
Modules that facilitate the conversion of electrical PROFIBUS interfaces (RS485
levels) into optical PROFIBUS interfaces and vice versa.
Output data/
output direction Data from the PROFIBUS DP master to the PROFIBUS DP slave.
PNO PROFIBUS user organization
PROFIBUS DP PROFIBUS - Decentralized Peripherals
PSE PROFIBUS interface module with (electrical) isolated RS485 interface for the
Siemens SIPROTEC devices.
PSO PROFIBUS interface module with optical interface for the Siemens SIPROTEC
devices.
Glossary
52 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Programmable
Logic
Controller
Programmable logic controllers (PLC) are electronic control systems the function of
which is stored as a program in the control unit.
The programmable logic controller has the structure of a computer. It consists of a
central processing unit (CPU) with memory, input/output modules, power supply unit
and a mounting rack (with bus system).
The periphery and the program language are designed to meet the requirements of
the control system.
PLC see Programmable Logic Controller
53SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4
Index
A
Annunciations .........................................15, 28, 38
C
Changing the setting group .................................19
Commands ..........................................................14
Configuration data ...............................................17
D
Double commands ....................................... 22, 32
Double-point indications ............................... 25, 35
E
Event list ....................................................... 32, 40
M
Measured values ....................................15, 29, 39
Scaling ..........................................................16
Metered measurands .............................16, 30, 40
Scaling ..........................................................16
P
PROFIBUS DP
Configuration data .........................................17
Configuration in the master system ..............18
Event list ................................................. 32, 40
Q
Qualified pers onnel (definition) .............................5
S
Statistic values ............................................. 29, 39
T
Target audience of the manual .............................4
Typographic conventions ......................................5
V
Validity of this manual ...........................................4
Index
54 SIPROTEC PROFIBUS DP - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2140-A320-4