10 Motor Contactor J7KN
Contactors
Data according to IEC 60947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type
J7KN(G)-10(D) J7KN(G)-14(D) J7KN(G)-18(D) J7KN(G)-22(D)
J7KN(G)-24 J7KN(G)-32 J7KN(G)-40 J7KN-50
Rated insulation voltage Ui*1
*1 Suitable at 690V for: earthed-neutral systems, overvoltage I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
V AC 690 690 690 690 690 690 690 690
Making capacity Ieff at Ue =
690V AC
A 200 200 200 200 400 500 500 700
Breaking capacity Ieff 400V AC A 180 180 200 200 380 400 400 600
J7KN-09 to J7KN-22
cos
= 0,65
500V AC A 150 150 180 180 300 370 370 500
J7KN-24 to J7KN-860
cos
= 0,35
690V AC A 100 100 150 150 260 340 340 400
1000V AC A ––––––––
Utilization category AC1
Switching of resistive load
Rated operational current
Ie (=Ith) at 40°C, open
690V A 25253232506580110
Rated operational power
of three-phase resistive
loads
50-60Hz, cos = 1
220V kW 9,5 9,5 12,2 12,2 19,0 24,7 30,4 41,9
230V kW 9,9 9,9 12,7 12,7 19,9 25,9 31,8 43,8
240V kW 10,4 10,4 13,3 13,3 20,8 27,0 33,2 45,7
380V kW 16,4 16,4 21,0 21,0 32,9 42,7 52,6 72,3
400V kW 17,3 17,3 22,1 22,1 34,6 45,0 55,4 76,1
415V kW 17,9 17,9 23,0 23,0 35,9 46,7 57,4 79,0
440V kW 19,0 19,0 24,4 24,4 38,1 49,5 60,9 83,7
500V kW 21,6 21,6 27,7 27,7 43,3 56,2 69,2 95,2
660V kW 28,5 28,5 36,5 36,5 57,1 74,2 91,3 125,6
690V kW 29,8 29,8 38,2 38,2 59,7 77,6 95,5 131,3
1000VkW––––––––
Rated operational current
Ie (=Ithe) at 60°C, enclosed
690VA 2525323240556590
Rated operational power
of three-phase resistive
loads
50-60Hz, cos = 1
220V kW 9,5 9,5 12,2 12,2 15,2 20,9 24,7 34,3
230V kW 9,9 9,9 12,7 12,7 15,9 21,9 25,9 35,8
240V kW 10,4 10,4 13,3 13,3 16,6 22,8 27,0 37,4
380V kW 16,4 16,4 21,0 21,0 26,3 36,2 42,7 59,2
400V kW 17,3 17,3 22,1 22,1 27,7 38,1 45,0 62,3
415V kW 17,9 17,9 23,0 23,0 28,7 39,5 46,7 64,6
440V kW 19,0 19,0 24,4 24,4 30,4 41,9 49,5 68,5
500V kW 21,6 21,6 27,7 27,7 34,6 47,6 56,2 77,9
660V kW 28,5 28,5 36,5 36,5 45,7 62,8 74,2 102,8
690V kW 29,8 29,8 38,2 38,2 47,7 65,7 77,6 107,4
1000VkW––––––––
Minimum cross-section of conductor
at load with Ie (=Ith)
mm²446610162535
Utilization category AC2 and AC3
Switching of three-phase motors
Rated operational current I
e
open and enclosed
220VA 1215182224304050
230VA11,514,5182224304050
240VA 1114182224324050
380-400V A 10 14 18 22 24 32 40 50
415V A 9 14 18 22 23 30 40 50
440V A 9 14 18 22 23 30 40 50
500VA 799917,5212133
660-690V A 6,5 8,5 8,5 8,5 17 20 20 31
1000VA ––––––––
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 345668,51112,5
240VkW34577911,513,5
380-400V kW 4 5,5 7,5 11 11 15 18,5 22
415VkW4,5 68,51212162024
440VkW4,5 68,51212162024
500V kW 5,5 7,5 10 10 15 18,5 18,5 30
660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30
1000VkW––––––––