05/06/2015 174331 - HPL-ED2015 V12.0 EN 1 / 5
Speed�starters,�single-phase�power�supply�connection,�three-phase
motor�connection�at�230�V,�7�A�and�1,�5�kW�/�2�HP
Part�no. DE1-127D0FN-N20N
Article�no. 174331
Catalog�No. DE1-127D0FN-N20N
Delivery�programme
Product range PowerXL™ DE1 Speed Starters
Rated operational voltage Ue 230 V AC, 1-phase
Output voltage with V<sub>e</sub> U2 230 V AC, 3-phase
Mains voltage (50/60Hz) ULN V 200 (-10%) - 240 (+10%)
Rated�operational�current
At 150% overload IeA 7
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Note Overload cycle for 60 s every 600 s
Assigned�motor�rating
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 230 V, 50 Hz
150 % Overload P kW 1.5
150 % Overload IeA 6.3
Note at 220 - 240 V, 60 Hz
150 % Overload P HP 2
150 % Overload IeA 6.8
Degree of Protection IP20/NEMA 0
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU
Fitted with Radio interference suppression filter
Frame size FS1
Connection to SmartWire-DT with SmartWire-DT module DX-NET-SWD3
Technical�data
General
Standards Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications CE, UL, cUL, c-Tick
Production quality RoHS, ISO 9001
Climatic proofing ρw% < 95%, average relative humidity (RH), non-condensing, non-corrosive (EN50178)
Ambient temperature °C
operation (150 % overload) ϑ °C -10 - +50, max. +60
Storage ϑ °C -40 - +70
Radio interference level
Radio interference class (EMC) C1, C2, C3, depending on the motor cable length, the connected load, and ambient
conditions. External radio interference suppression filters (optional) may be
necessary.
Environment (EMC) 1st and 2nd environments
maximum motor cable length I m C1 ≤ 5 m
C2 ≤ 10 m
C3 ≤ 25 m
Mechanical shock resistance g 15 (11 m/s, EN 60068-2-27)
05/06/2015 174331 - HPL-ED2015 V12.0 EN 2 / 5
Vibration EN 61800-5-1
Altitude m 0 - 1000 m above sea level
above 1000m with 1 % performance reduction per 100m
max. 2000 m
Degree of Protection IP20/NEMA 0
Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof)
Main�circuit
Supply
Rated operational voltage Ue 230 V AC, 1-phase
Mains voltage (50/60Hz) ULN V 200 (-10%) - 240 (+10%)
Input current (150% overload) ILN A 17.4
Supply frequency fLN Hz 50/60
Frequency range fLN Hz 45 - 66
Mains switch-on frequency Maximum of one time every 30 seconds
Power section
Overload current (150% overload) ILA 10.5
max. starting current (High Overload) IH% 200
Note about max. starting current for 1.875 seconds every 600 seconds
Output voltage with VeU2 230 V AC, 3-phase
Output Frequency f2Hz 0 - 50/60 (max. 300)
Switching frequency fPWM kHz 16
adjustable 4 - 32 (audible)
Operation Mode U/f control
Speed control with slip compensation
Frequency resolution (setpoint value) Δf Hz 0.025
Rated operational current
At 150% overload IeA 7
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Maximum leakage current to ground (PE) without motor IPE mA < 3,5 AC, < 10 DC
Fitted with Radio interference suppression filter
Frame size FS1
Motor feeder
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 230 V, 50 Hz
150 % Overload P kW 1.5
Note at 220 - 240 V, 60 Hz
150 % Overload P HP 2
Apparent power
Apparent power at rated operation 230 V S kVA 2.79
Apparent power at rated operation 240 V S kVA 2.91
Braking function
Standard braking torque max. 30 % MN
DC braking torque 100 %, adjustable
Control�section
Reference voltage UsV 10 V DC (max. 0.2 mA)
Analog inputs 1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Digital inputs 4, parameterizable, 10 - 30 V DC
Relay outputs 1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU
Assigned�switching�and�protective�elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Typ B, gG) FAZ-B20/1N
UL (Class CC or J) A 20
05/06/2015 174331 - HPL-ED2015 V12.0 EN 3 / 5
Mains contactor
150 % overload (CT/IH, at 50 °C) DILEM-… + P1DILEM
DILEM-…+P1DILEM
110 % overload (VT/IL, at 40 °C) DILM7-… + DILM12-XP1
Main choke
150 % overload (CT/IH, at 50 °C) DX-LN1-018
Radio interference suppression filter (external) DX-EMC12-019-FS1
Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable
lengths and for use in different EMC environments
Motor feeder
motor choke
150 % overload (CT/IH, at 50 °C) DX-LM3-008
Sine filter
150 % overload (CT/IH, at 50 °C) DX-SIN3-010
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 7
Equipment heat dissipation, current-dependent Pvid W 59
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical�data�ETIM�5.0
Low-voltage industrial components (EG000017) / Frequency controller =< 1 kV (EC001857)
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency converter = < 1 kv (ecl@ss8-27-02-31-01 [AKE177010])
Mains voltage V 200 - 240
Mains frequency 50/60 Hz
Number of phases input 1
Number of phases output 3
05/06/2015 174331 - HPL-ED2015 V12.0 EN 4 / 5
Max. output frequency Hz 300
Rated output voltage V 230
Measuring output current A 7
Output power at rated output voltage kW 0.5
Max. output at quadratic load at rated output voltage kW 0.5
Max. output at linear load at rated output voltage kW 0.5
With control unit No
Application in industrial area permitted Yes
Application in domestic- and commercial area permitted Yes
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for KNX No
Supporting protocol for MODBUS Yes
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems Yes
Number of HW-interfaces industrial Ethernet 0
Number of HW-interfaces PROFINET 0
Number of HW-interfaces RS-232 0
Number of HW-interfaces RS-422 0
Number of HW-interfaces RS-485 1
Number of HW-interfaces serial TTY 0
Number of HW-interfaces USB 0
Number of HW-interfaces parallel 0
Number of HW-interfaces other 0
With optical interface No
With PC connection Yes
Integrated braking resistance No
4-quadrant operation possible No
Type of converter U converter
Degree of protection (IP) IP20
Height mm 230
Width mm 45
Depth mm 168
Relative symmetric net frequency tolerance % 5
Relative symmetric net current tolerance % 10
Approvals
Product Standards UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No. E172143
05/06/2015 Eaton Industries GmbH
http://www.eaton.eu
© 04/2015 by Eaton Industries GmbH
174331 - HPL-ED2015 V12.0 EN
5 / 5
UL Category Control No. NMMS, NMMS7
CSA File No. UL report applies to both US and Canada
North America Certification UL listed, certified by UL for use in Canada
Specially designed for North America No
Suitable for Branch circuits
Max. Voltage Rating 1~ 240 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
Degree of Protection IEC: IP20
Dimensions
Additional�product�information�(links)
IL040005ZU�Variable�frequency�drives�DE1
IL040005ZU Variable frequency drives DE1 ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL040005ZU2014_07.pdf
MN040011�DE1�Variable�speed�starter,�Manual
MN040011 Drehzahlstarter DE1, Handbuch -
Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_DE.pdf
MN040011 DE1 Variable speed starter, Manual
- English
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_EN.pdf
MN040011 Démarreur à vitesse variable DE1,
manuel d'utilisation - français
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_FR.pdf
MN040011 Avviatore a velocità variabile DE1,
Manuale - italiano
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_IT.pdf
MN040011 DE1 Variable speed starter, Manual ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_NO.pdf
MN040011 Rozrusznik silnikowy z regulacją
prędkości DE1, podręcznik - polski
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_PL.pdf
MN040011 DE1 Variable speed starter, Manual ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN040011_RO.pdf