https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) AxiolineF, Digital I/O module, Digital inputs: 8, 24 VDC, connection method: 1-conductor, Digital outputs:8, 24 VDC, 500 mA, connection method:1-conductor, transmission speed in the local bus:100 Mbps, degree of protection:IP20, including bus base module and AxiolineF connectors Product Description The module is designed for use within an AxiolineF station. It is used to acquire and output digital signals. You can adjust the filter times of the inputs to increase noise immunity. Filter times of 100s enable you to implement a counter function with a maximum input frequency of 5kHz in the application. The outputs are protected against short circuit and overload. Your advantages 8 digital inputs according to EN61131-2 type1 and type3 24VDC, 2.4mA Connection of sensors in 1-conductor technology Filter times can be adjusted in three increments: <100s, 1000s or 3000s Maximum input frequency: 5 kHz 8 digital outputs 24VDC, 500mA Connection of actuators in 1-conductor technology Minimum update time of < 100 s Device rating plate stored Key Commercial Data Packing unit 1 pc GTIN GTIN 4046356872935 Weight per Piece (excluding packing) 180.000 g Custom tariff number 85389091 04/20/2021Page1/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Country of origin Germany Technical data Note Utilization restriction EMC: class A product, see manufacturer's declaration in the download area Dimensions Caption Dimensions Width 35 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH35-7,5 DIN rail is used (according to EN60715). Ambient conditions Ambient temperature (operation) -25 C ... 60 C Ambient temperature (storage/transport) -40 C ... 85 C Permissible humidity (operation) 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000m above sea level) Degree of protection IP20 Connection data Designation AxiolineF connector Connection method Push-in connection Note on the connection method Please observe the information provided on conductor cross sections in the "AxiolineF: system and installation" user manual. Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 1.5 mm Conductor cross section flexible min. 0.2 mm Conductor cross section flexible max. 1.5 mm Conductor cross section AWG min. 24 Conductor cross section AWG max. 16 Stripping length 8 mm General Mounting type DIN rail Color traffic grey A RAL 7042 Net weight 133 g Note on weight specifications with connectors and bus base module Degree of pollution 2 (IEC60664-1, EN60664-1) 04/20/2021Page2/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Technical data General Mounting position any (no temperature derating) Interfaces Designation AxiolineFlocal bus Number of interfaces 2 Connection method Bus base module Transmission speed 100 Mbps Axioline potentials Designation AxiolineF local bus supply (UBus) Supply voltage 5 VDC (via bus base module) Current consumption max. 120 mA (up to HW01) max. 60 mA (as of HW02) Power consumption max. 600 mW (up to HW01) max. 300 mW (as of HW02) Designation Supply for digital input and output modules (UIO) Supply voltage 24 VDC Supply voltage range 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current consumption max. 4 A (provide external protection) Power consumption max. 96 W (of which 1.35W internal losses) Protective circuit Surge protection electronic (35 V, 0.5 s) Reverse polarity protection parallel diode; with external 5A fuse (only for commissioning) Protection max. 8 A (polarity reversal protection up to 5A) Digital inputs Input name Digital inputs Description of the input EN 61131-2 types 1 and 3 Connection method Push-in connection Connection technology 1-conductor Number of inputs 8 Protective circuit Polarity reversal protection of the inputs parallel diode (30V, 5s) Nominal input voltage UIN 24 VDC Nominal input current at UIN 2.4 mA Input filter time 3000 s (Default) 1000 s < 100 s Input voltage range "0" signal -3 VDC ... 5 VDC Input voltage range "1" signal 11 VDC ... 30 VDC 04/20/2021Page3/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Technical data Digital outputs Output name Digital outputs Connection method Push-in connection Connection technology 1-conductor Number of outputs 8 Protective circuit Short-circuit protection, overload protection of the outputs electronic Output voltage 24 VDC Nominal output voltage 24 VDC Nominal load, inductive max. 12 VA (1.2 H, 48 , with nominal voltage) Nominal load, lamp max. 12 W (at nominal voltage) Nominal load, ohmic max. 12 W (48 , with nominal voltage) Switching frequency max. 10000 per second (with at least 50mA load current) Load min. 10 k Output voltage when switched off max. 1 V Output current when switched off max. 300 A Behavior with overload Shutdown with automatic restart Behavior with inductive overload Output can be destroyed Reverse voltage resistance to short pulses limited protection up to 0.5 A for 1 s Electrical isolation Test section 5V supply of the local bus (UBus) / 24V supply (I/Os) 500 VAC 50 Hz 1 min. 5V supply of the local bus (UBus) / functional ground 500 VAC 50 Hz 1 min. 24V supply (I/O) / functional ground 500 VAC 50 Hz 1 min. Standards and Regulations Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A, Field intensity: 10 V/m Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B, DC supply lines: 0.5 kV/0.5 kV (symmetrical/asymmetrical) Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A, Test voltage 10 V Interference emission Noise emission test according to EN 61000-6-3 Class B Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g Shock in acc. with EN60068-2-27/IEC60068-2-27 30g 04/20/2021Page4/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Technical data Standards and Regulations Continuous shock according to EN60068-2-27/IEC60068-2-27 10g Protection class III (IEC61140, EN61140, VDE0140-1) Overvoltage category II (IEC60664-1, EN60664-1) Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 50 years For details about hazardous substances go to tab "Downloads", Category "Manufacturer's declaration" Drawings Connection diagram IN1 +24 V Connection diagram 00 01 02 03 00 01 02 03 10 11 12 13 10 11 12 13 20 21 22 23 30 31 32 33 IN1 OUT2 20 21 22 23 30 31 32 33 +24 V OUT8 IN7 +24 V OUT2 OUT8 IN7 +24 V +24 V +24 V Typical connection of sensors and actuators when using external busbars Connection in 1-conductor technology 122,4 54 126,1 35 Diagram Energy consumption [J] Dimensional drawing 0,4 Only with external free running circuit 0,35 0,3 0,25 0,2 0,15 0,1 0,05 1 = 0,5 A 2 = 0,4 A 3 = 0,3 A 4 = 0,2 A 5 = 0,1 A 1 2 3 4 5 0 0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2 2,3 2,4 Inductance [H] Maximum outputs power consumption when inductive loads are switched off Dimensions 04/20/2021Page5/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Block diagram UBus C Local bus FE IN OUT 01 ... 08 01 ... 08 D UIO E1 E2 31 30 01 00 UIO 24 V 33 32 30 03 01 03 02 10 Input circuit 31 00 01 11 00 13 12 20 23 21 22 30 31 33 32 02 Output circuit 33 32 03 02 Internal wiring of the terminal points Classifications eCl@ss eCl@ss 10.0.1 27242604 eCl@ss 11.0 27242604 eCl@ss 4.0 27240400 eCl@ss 4.1 27240400 eCl@ss 5.0 27242200 eCl@ss 5.1 27242600 eCl@ss 6.0 27242600 eCl@ss 7.0 27242604 eCl@ss 9.0 27242604 ETIM ETIM 4.0 EC001599 ETIM 6.0 EC001599 04/20/2021Page6/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Classifications ETIM ETIM 7.0 EC001599 UNSPSC UNSPSC 6.01 43172015 UNSPSC 7.0901 43201404 UNSPSC 11 39121311 UNSPSC 12.01 39121311 UNSPSC 13.2 32151602 UNSPSC 18.0 32151602 UNSPSC 19.0 32151602 UNSPSC 20.0 32151602 UNSPSC 21.0 32151602 Approvals Approvals Approvals PRS / BV / LR / KR / ABS / BSH / RINA / EAC / DNV GL / cULus Listed Ex Approvals Approval details PRS http://www.prs.pl/ TE/1117/880590/20 BV http://www.veristar.com/portal/veristarinfo/generalinfo/ approved/approvedProducts/equipmentAndMaterials 36433/B2 BV LR http://www.lr.org/en LR2001902TA 04/20/2021Page7/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Approvals KR http://www.krs.co.kr/eng/main/main.aspx HMB17372-AC002 ABS http://www.eagle.org/eagleExternalPortalWEB/ 20-2059154-PDA BSH 840 RINA http://www.rina.org/en ELE030120XG EAC EAC-Zulassung DNV GL https://approvalfinder.dnvgl.com/ TAA00000DF cULus Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705 Accessories Accessories Device marking Insert label-EMT (35X28)R-0801602 Insert label, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK ROLL X1, THERMOMARK ROLL 2.0, THERMOMARK ROLL, mounting type: snapped into marker carrier, lettering field size: 35 x 28 mm, Number of individual labels: 500 DIN rail connector 04/20/2021Page8/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Accessories Bus connector-AXL F BS H-2700992 AxiolineF bus base module for housing type H System cable Round cable-VIP-CAB-FLK14/AXIO/0,14/0,5M-2901604 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 0.5 m Round cable-VIP-CAB-FLK14/AXIO/0,14/1,0M-2901605 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 1 m Round cable-VIP-CAB-FLK14/AXIO/0,14/1,5M-2901606 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 1.5 m Round cable-VIP-CAB-FLK14/AXIO/0,14/2,0M-2901607 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 2 m 04/20/2021Page9/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Accessories Round cable-VIP-CAB-FLK14/AXIO/0,14/2,5M-2901608 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 2.5 m Round cable-VIP-CAB-FLK14/AXIO/0,14/3,0M-2901609 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 3 m Round cable-VIP-CAB-FLK14/AXIO/0,14/4,0M-2901610 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 4 m Round cable-VIP-CAB-FLK14/AXIO/0,14/6,0M-2901611 Round cable set; controller: Axioline Realtime I/O; connection 1: Single wires (8-position) (The wires are marked and fitted with ferrules); connection 2: IDC/FLK socket strip (1x 14-position, 90 -out put); cable length: 6 m Terminal marking Zack marker strip-ZB 20,3 AXL UNPRINTED-0829579 Zack marker strip for AxiolineF (device labeling), in 2 x 20.3 mm pitch, unprinted, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or CMS-P1-PLOTTER 04/20/2021Page10/11 https://www.phoenixcontact.com/us/products/2701916 I/O module-AXL F DI8/1 DO8/1 1H-2701916 Accessories Zack Marker strip, flat-ZBF 10/5,8 AXL UNPRINTED-0829580 Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: PLOTMARK, CMS-P1-PLOTTER, mounting type: snap into flat marker groove, for terminal block width: 10.15 mm, lettering field size: 4 of 10.15 x 5 mm and 1 of 5.8 x 5 mm, Number of individual labels: 50 Phoenix Contact 2021 (c) - all rights reserved http://www.phoenixcontact.com 04/20/2021Page11/11