Axial Lead & Cartridge Fuses
2AG > Fast Acting > 224/225 Series
224/225 Series
Please refer to www.littelfuse.com/series/224.html
or /225.html for current information.
224/225 Series
224/225 Series Lead-Free 2AG, Fast-Acting
The 2AG Fast-Acting Fuses are available in cartridge
form or with axial leads. 2AG Fuses provide the same
performance characteristics as their 3AG counterpart, while
occupying one-third the space. Sleeved fuses are available.
Agency Approvals
Agency Agency File Number Ampere Range
E10480 375mA - 3.5A
E10480 4A - 10A
LR 29862 375mA - 10A
PS
E
NBK200405-E10480
NBK060405-E10480
Cartridge: 1A - 10A
Pigtail: 1A - 10A
375mA - 10A
Features
Electrical Characteristics for Series
t *OBDDPSEBODF
with underwriter’s
Laboratories Standard
UL 248-14
t "WBJMBCMFJODBSUSJEHF
and axial lead form and
with various forming
dimensions
t 3P)4DPNQMJBOUBOE
Lead-free
Applications
% of Ampere
Rating Opening Time
100% 4 hours, Minimum
135% 1 hour, Maximum
200% 1 sec., Maximum
Amp
Code
Ampere
Rating
(A)
Voltage
Rating
(V)
Interrupting
Rating
Nominal
Cold
Resistance
(Ohms)
Nominal
Melting
I2t (A2 sec)
Agency Approvals
PS
E
.375 0.375 250
35A@250Vac
10KA@125Vac
10KA@125Vdc
0.3950 0.171 x x x
.500 0.5 250 0.2650 0.365 x x x
.750 0.75 250 0.1520 1.050 x x x
001. 1 250 0.1027 2.220 x x x x
01.5 1.5 250 0.0712 0.800 x x x x
002. 2 250 100A@250Vac
10KA@125Vac
10KA@125Vdc
0.0497 1.500 x x x x
02.5 2.5 250 0.0372 2.680 x x x x
003. 3 250 0.0317 4.620 x x x x
03.5 3.5 250 0.0265 6.700 x x x x
004. 4 125 100A@250Vac
500A@125Vac
0.0240 9.400 xxxx
005.5125 0.018617.0 xxxx
005. 5 250 0.0186 17.0 x x x
006. 6 125
500A@125Vac
0.0154 22.1 xxxx
007. 7 125 0.0130 40.0 xxxx
008. 8 125 0.0107 56.0 xxxx
010. 10125 0.0075116.0 xxxx
Electrical Characteristic Specications by Item
Used as supplementary protection in appliance or
utilization equipment to provide individual protection for
components or internal circuits.
PS
E
Description
* 10A with 500A @ 125 Vdc internal breaking capacity testing.