General
Specifications
<<Contents>> <<Index>>
■ Overview
This panel-mounted power and energy meter with a
large, three-row LED display integrates all the measur-
ing functions required for power management in
locations such as factories and buildings into a single
unit.
With the objective of working toward the preservation
of the global environment by saving energy and
performing equipment maintenance, the PR300 is
designed to display and output the energy of various
types of electrical equipment.
■ Features
•Saves on cost, wiring, and space
Integrates a wide selection of functions for measuring things
like energy (active, regenerative, reactive, and apparent),
power (active, regenerative, reactive, and apparent),
voltage, current, frequency, and power factor into a single
unit.
•Employs a large, three-row LED display
Capable of displaying three-phase current and voltage
simultaneously, and the measurement items you assign.
•Analog output function
Equipped with a transducer function for power (active,
regenerative, reactive, and apparent), voltage, current,
frequency, and power factor (4 to 20 mA DC).
•Demand measurement
Measures the average power and current within a specified
period. It also allows you to set up alarm points to output
alarms.
•Equipped with a multitude of functions
Enables measurement of the maximum and minimum
values of voltage and the maximum value of current, as well
as, for example, the use of external digital input to measure
energy at arbitrary times.
•Pulse output
Capable of outputting pulses proportional to energy (one
measurement item from active, regenerative, reactive, and
apparent energy).
•Converts the phase and wire system of an AC power
system and an input voltage circuit to a universal
format
The PR300 can handle from the single-phase two-wire
system and single-phase three-wire system to the three-
phase three-wire system and three-phase four-wire system,
and also universally cope with input voltage circuits up to
600 V AC.
•Compatible with ANSI 4-inch round form size and
DIN 96-square instrument size
The ability to attach and detach JIS/ANSI-mounting kit
makes the PR300 compatible with panel cutouts of ANSI 4-
inch round form, JIS 110-square instrument size, and DIN
96-square instrument size.
•Standard equipped with an RS-485 communication
function and capable of Ethernet communication
•Compatible with overseas requirements
Power line indications A, B, and C provided for overseas
use, in addition to R, S, and T
GS 77C01E01-01E
GS 77C01E01-01E
©Copyright Apr. 2006 (KP)
5th Edition Dec. 10, 2008 (KP)
Model PR300
Power and Energy Meter
■ Model and Suffix Codes
PR300 -0
Model
Phase and wire system
3:
Universal three-phase three-wire system
(single-phase two-wire, single-phase three-wire,
a
nd three-phase three-wire systems)
4:
Universal three-phase four-wire system
(single-phase two-wire, single-phase
three-wire, three-phase three-wire, and
three-phase four-wire systems)
5: Three-phase four-wire system
(2.5 element
)
*
1
Input voltage/input current
1: Universal voltage input*
2
(150 V, 300V, 600 V) / 1 A AC
2: Universal voltage input*
2
(150 V, 300 V, 600 V) / 5 A AC
Additional input and output function
0: 1 digital input
1: 1 digital input, 1 analog output
2: 1 digital input, 1 pulse output
3:
1 digital input, 1 analog output, 1 pulse output
Communication function
0: RS-485 communication
3:
RS-485 communication, Ethernet communication
*
3
Optional measuring function
0: None
3: Demand measurement (1 demand alarm output)
Power supply
6:
100-240 V AC 10% (50/60 Hz) or 130-300 V DC 15%
Phase indication format
A: A, B, and C indications
R: R, S, and T indications
*1 In cases where
“Three-phase four-wire system (2.5 element)” is
specified, the input current specification of 1 A AC is not applicable.
(PR300-51xxx-xx-0 cannot be ordered.)
Can be used only when the voltage is in a state of equilibrium.
The phase and wire system cannot be changed.
*2 Set the voltage range (150 V, 300 V, or 600 V) according to the
rated input voltage to be measured.
(Refer to “Rated Input
Voltage” of the Input Specifications on page 6.)
*3
For Ethernet communication, the RS-485 communication interface
is exclusively for the Ethernet-serial gateway function.
■Ordering Information
Specify the model and suffix codes.
Example: PR300-31000-6A-0
The ability to attach and detach JIS/ANSI-mounting kit
ensures compatibility with two sizes.
ANSI 4-inch round form size
DIN 96-square instrument size