Suggested Copy for Lapp Limited in Farnell Catalogue
Unitronic® LiYCY (TP)
(Farnell: Overall screened twisted pair data cables)
Application
UNITRONIC® LiYCY (TP) is a screened, paired, flexible cable for control and data transmissions, for weak- current
applications. The fine wired conductor (7-wired for 0.34mm2) and the robust ductile outer sheath gives the cable
strength as well as high flexibility. By the pair twisting the electric circuits are well decoupled and with the screen of a
tinned copper braiding the cabel is protected against external electrical influences.
The cable is intended for static laying and flexible use in dry and damp interiors. Design and electrical characteristics
similar to VDE 0812.
Design
Conductor fine-wire strands of bare copper wire; 0.14 mm2 to 1.5 mm2 , 7-wired for 0.34 mm2
Insulation PVC compound YI2 according to V DE 0207 part 4,
Coding according to DIN 47100
Pair stranding cores twisted into pairs
Core stranding pairs twisted in layers, wrapping by plastic foil
Screening braiding of tinned copper wires, coverage approx. 85%
Sheath PVC YM2 according to V DE 0207 part 5, flame retardant, grey, RAL 7032
Technical Data
Conductor Loop resistance Mutual capacitance *) Impedance **)at
cross section core/core 800 Hz 50 kHz 100 kHz 1 MHz
[mm²] [max.)./km] [nom. pF/m] nom.[] nom.[] nom.[]
0,14 148 95 115 93 76
0,25 79,9 97 110 90 74
0,34 57,5 97 108 90 74
0,5 38,9 100 98 85 70
0,75 26 112 89 75 65
1,0 19,5 125 83 70 62
1,5 13,3 135 74 62 55
Inductivity mH/km appr. 0.65
Specific insulation resistance min. Gxcm 20
Operating Voltage for 0.14 mm² (not for power purposes) V 350
for 0,25 mm² (not for power purposes) V 500
Test voltage for 0.14 mm² Ueff V 1200
for 0,25 mm² Ueff V 1500
Temperature range static °C -30 to + 80
Flexing -5 to + 70
Minimum bending radius static 6 x Ø cable
flexing 15 x Ø cable
Flame propagation flame retardant to VDE 0482, part 265-2-1/IEC 60 332-1
*) valid for 4 pairs and more
**) values for f:! 1 MHz are for the orientation, because the cables are only limited suitable for f:! 500 kHz