9874 Paired - Audio, Control and Instrumentation Cable
For more information please
call
1-800-Belden1
See Put-ups and Colors
Color Code Chart : No. 3 for
Paired Cables (Belden
Standard).pdf
Description:
20 AWG stranded (7x28) TC conductors, polypropylene insulation, twisted pairs, individually shielded w/Beldfoil® (100% coverage), 22
AWG stranded TC drain wire, overall PVC jacket.
PHYSICAL CHARACTERISTICS:
CONDUCTOR:
Number of Pairs 6
Total Number of Conductors 12
AWG 20
Stranding 7x28
Conductor Material TC - Tinned Copper
INSULATION:
Insulation Material PE - Polyethylene
Lay Length 1.75 in.
Twists/ft. 6.85
Pair Color Code Chart :
Number Color
1 Black & Red
2 Black & White
3 Black & Green
Number Color
4 Black & Blue
5 Black & Yellow
6 Black & Brown
INNER SHIELD:
Inner Shield Material Trade Name Beldfoil® (Z-Fold®)
Inner Shield Type Tape
Inner Shield Material Aluminum Foil-Polyester Tape
Inner Shield % Coverage 100 %
Inner Shield Drain Wire AWG 22
Inner Shield Drain Wire Stranding 19x34
Inner Shield Drain Wire Conductor Material TC - Tinned Copper
Page 1 of
3
9874 Paired - Audio, Control and Instrumentation Cable
OUTER JACKET:
Outer Jacket Material PVC - Polyvinyl Chloride
OVERALL NOMINAL DIAMETER:
Overall Nominal Diameter .445 in.
MECHANICAL CHARACTERISTICS:
Operating Temperature Range -20°C To +80°C
UL Temperature Rating 80°C (UL AWM Style 2919)
Bulk Cable Weight 102 lbs/1000 ft.
Max. Recommended Pulling Tension 256 lbs.
Min. Bend Radius (Install) 4.7 in.
APPLICABLE SPECIFICATIONS AND AGENCY COMPLIANCE:
APPLICABLE STANDARDS:
NEC/(UL) Specification CM
CEC/C(UL) Specification CM
AWM Specification UL Style 2919 (30 V 80°C)
EU CE Mark (Y/N) Yes
EU RoHS Compliant (Y/N) Yes
EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
FLAME TEST:
UL Flame Test UL1685 UL Loading
PLENUM/NON-PLENUM:
Plenum (Y/N) N
ELECTRICAL CHARACTERISTICS:
Nom. Characteristic Impedance 50 Ohms
Nom. Inductance 0.18 µH/ft
Nom. Capacitance Conductor to Conductor @ 1 KHz 30 pF/ft
Nom. Cap. Cond. to Other Cond. & Shield @ 1 KHz 55 pF/ft
Nominal Velocity of Propagation 66 %
Nom. Conductor DC Resistance @ 20 Deg. C 10.5 Ohms/1000 ft
Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C 11.3 Ohms/1000 ft
Max. Operating Voltage - UL 30 V RMS (UL AWM Style 2919), 300 V RMS (CM)
Max. Recommended Current 2.7 Amps per conductor @ 25°C
PUT-UPS AND COLORS:
Item Description Put-Up (ft.) Ship Weight (lbs.) Jacket Color Notes
Page 2 of
3
9874 Paired - Audio, Control and Instrumentation Cable
9874 060100 6 FS PR #20 PP PVC
100 10.3 CHROME
C
9874 0601000 6 FS PR #20 PP PVC
1000 113 CHROME
C
9874 060250 6 FS PR #20 PP PVC
250 29 CHROME
9874 060500 6 FS PR #20 PP PVC
500 56.5 CHROME
C
C = CRATE REEL PUT-UP.
Revision Number: 1 Revision Date: 11-21-2005
© 2005 Belden Wire & Cable Company
All Rights Reserved.
Although Belden Electronics Division ("Belden") makes every reasonable effort to ensure their accuracy at the time of this publication,
information and specifications described herein are subject to error or omission and to change without notice, and the listing of such
information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described
herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden CDT Electronics Division believes this product to be in compliance with the following environmental regulations: California
Proposition 65 Consent Judgment For Wire & Cable Mfgs.(San Francisco Superior Court Nos. 312962 And 320342); EU RoHS
(Directive 2002/95/EC, 27-Jan-2003);Material manufactured prior to the compliance date may still be in stock at Belden facilities and in our
Distributor's inventory. EU ELV (Directive 2000/53/EC, 18-Sept-2000); EU WEEE (Directive 2002/96/EC, 27-Jan-2003); And EU BFR
(Directive 2003/11/EC, 6-Feb-2003). The information provided in this Product Disclosure, and the identification of materials listed as
reportable or restricted within the Product Disclosure, is correct to the best of Belden's knowledge, information and belief at the date of its
publication. The information provided in the Product Disclosure is designed only as a general guide for the safe handling, storage, and any
other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality
specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of
legislation and regulations based on their individual usage of the product.
Belden CDT Electronics Division declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended
by directive 93/68/EEC.
Page 3 of
3