www.stancor.com
Step-Down
Auto Transformers
230 to 115 Volts
ELECTROCUTION HAZARD
Disconnect electric power to system at
main fuse or circuit breaker box before
servicing. Failure to do so could result
in death or serious injury.
FIRE HAZARD
Do not exceed transformer ratings.
Higher voltage may damage control
and could cause personal injury or
property damage.
WARNING
!
NOTES:
1. All dimensions in inches, unless otherwise specified.
2. All dimensions ±.062, unless otherwise specified.
3. Plug cord 5 1/2 feet long min.
4. Receptacle cord 8 inches long min.
PART NO. 37-6200C
Replaces 37-6200B
0837
INPUT:
OUTPUT:
INSULATION RATING:
TEMPERATURE RISE:
DIELECTRIC STRENGTH:
230VAC, 50/60Hz
115 VAC (See Output Amp rating &
VA Capacity in table below)
Class A (105˚C)
65˚C Max. rise over
40˚C Max. ambient
1500 VRMS
RECEPTACLE
NEMA 5-15R
GND.
GND.
2
1'
D
MAX.
H
MAX.
MD
INPUT PLUG
NEMA 6-15P
13
MW W
MAX.
MS ±.031
(4 PLACES)
230V
115V
COM
COM
INPUT LINE CORD
GROUND OUTPUT LINE CORD
GROUND
3
2
1
1'
VIN CORD &
PLUG SET
VOUT CORD &
RECEPTACLE SET
SCHEMATIC DIAGRAM
STANCOR Output V.A. Dimensions - Inches Wt.
Part No. Amps Cap. H W D MW MD MS Lbs.
P-6287 0.35 40 3.19 2.56 2.75 2.00 1.75 .203 X .687 2.20
GSD-75 0.65 75 3.19 2.56 2.88 2.00 1.75 .203 X .687 3.00
P-8630 0.74 85 3.19 2.56 2.88 2.00 1.75 .203 X .687 2.50
GSD-100 0.87 100 3.19 2.56 3.25 2.00 2.06 .203 X .687 3.70
P-8631 1.10 125 3.19 2.56 3.13 2.00 2.06 .203 X .687 3.00
GSD-150 1.30 150 3.94 3.19 3.25 2.50 2.22 .203 X .750 4.40
P-8632 1.74 200 3.94 3.19 3.25 2.50 2.25 .203 X .750 4.20
GSD-250 2.20 250 3.94 3.19 3.63 2.50 2.22 .203 X .750 5.80
GSD-300 2.60 300 3.94 3.19 3.63 2.50 2.22 .203 X .750 5.80
GSD-350 3.00 350 3.94 3.19 4.31 2.50 2.72 .203 X .750 7.30
P-8634 3.50 400 3.94 3.19 4.25 2.50 2.72 .203 X .750 7.00
GSD-500 4.30 500 4.69 3.81 4.44 3.00 3.19 .203 X .500 10.6
GSD-750 6.50 750 4.69 3.81 5.38 3.00 3.94 .203 X .750 14.4
GSD-1000 8.70 1000 4.69 3.81 6.06 3.00 4.69 .203 X .750 17.0
GSD-1500 13.0 1500 5.44 4.44 6.00 3.50 4.00 .203 X .750 20.0