Current Transducer LA 55-P/SP1
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN Primary nominal r.m.s. current 50 A
IPPrimary current, measuring range 0 .. ± 100 A
R M Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 12 V @ ± 50 A max 0215 0210
@ ± 100 A max 035 030
with ± 15 V @ ± 50 A max 0335 30 330
@ ± 100 A max 095 30 90
ISN Secondary nominal r.m.s. current 25 mA
K N Conversion ratio 1 : 2000
VCSupply voltage (± 5 %) ± 12 .. 15 V
ICCurrent consumption 10 (@ ± 15 V) + ISmA
VdR.m.s. voltage for AC isolation test, 50 Hz, 1 mn 2.5 kV
Accuracy - Dynamic performance data
XAccuracy @ IPN , TA = 25°C @ ± 15 V (± 5 %) ± 0.65 %
@ ± 12 .. 15 V (± 5 %) ± 0.90 %
εLLinearity < 0.15 %
Typ Max
IOOffset current @ IP = 0, TA = 25°C ± 0.10 mA
IOM Residual current 1) @ IP = 0, after an overload of 3 x IPN ± 0.15 mA
IOT Thermal drift of IO0°C .. + 70°C ± 0.05 ± 0.25 mA
- 25°C .. + 85°C ± 0.05 ± 0.30 mA
tra Reaction time @ 10 % of IP max < 500 ns
trResponse time 2) @ 90 % of IP max < 1 µs
di/dt di/dt accurately followed > 200 A/µs
fFrequency bandwidth (- 1 dB) DC .. 200 kHz
General data
TAAmbient operating temperature - 25 .. + 85 °C
TSAmbient storage temperature - 40 .. + 90 °C
R S Secondary coil resistance @ TA = 70°C 145
TA = 85°C 150
mMass 18 g
Standards 3) EN 50178
Notes : 1) Result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) A list of corresponding tests is available
Features
Closed loop (compensated) current
transducer using the Hall effect
Printed circuit board mounting
Insulated plastic case recognized
according to UL 94-V0.
Special features
IP=0 .. ± 100 A
K N =1 : 2000.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
IPN =50 A
981130/9
LEM Components www.lem.com
Secondary terminals
Terminal +:supply voltage +12 .. 15 V
Terminal -:supply voltage -12 .. 15 V
Terminal M:measure
Connection
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
90°C.
Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
In order to achieve the best magnetic coupling, the primary
windings have to be wound over the top edge of the device.
Mechanical characteristics
General tolerance ± 0.2 mm
Primary through-hole 12.7 x 7 mm
Fastening & connection of secondary 3 pins
0.63 x 0.56 mm
Recommended PCB hole 0.9 mm
Bottom view
Front view
Left view
Dimensions LA 55-P/SP1 (in mm. 1 mm = 0.0394 inch)
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Standard 00 Year Week
or N° SP..
swiss
made