. Type: ELRM44V-30 Earth Leakage Relay (Variable) - Type A 44mm (2.5 modules) wide DIN rail housing Designed to monitor and detect true RMS earth fault currents (up to 30A) in conjunction with a separate toroid LED bargraph provides constant indication of any leakage current Microprocessor controlled with internal monitoring (self-checking) Adjustable Sensitivity (In) - 30mA to 30A Adjustable Time Delay (t) - 0 (instantaneous)* to 10 seconds Separate "Test" and "Reset" push buttons Connection facility for remote "Test" and "Reset" push buttons or N.O. contacts Toroid open circuit detection forces unit to trip (Red LED flashes during this condition) Dims: to DIN 43880 2 Relay outputs - Standard Output (S.O.) and Positive Safety Output (P.S.O.) W. 44mm LED indication of Supply status and fault condition after unit has tripped * FUNCTION DIAGRAM Supply voltage Un (5, 6, 7): 12 - 125V DC (85 - 110% of U) (see connection diagram) 24, 115/230, 400V AC (85 - 115% of Un) All AC supplies are galvanically isolated between the supply and the Please state Supply voltage toroid and remote test/reset connections. when ordering. Frequency range: 50/60/400Hz (AC supplies) fault current Trip level (In) Reset level failure of connection to toroid Standard output Positive safety output * * * * * "Test" button pressed INSTALLATION Installation work must be carried out by qualified personnel. BEFORE INSTALLATION, ISOLATE THE SUPPLY. Connect the unit as shown in the diagram below (N.B. certain features may not be required and therefore do not need to be connected). Apply power, the green "supply on" LED will illuminate and the "positive safety output" relay will energise. The relay will de-energise if: a, the fault current level exceeds the set trip level (In) ** b, there is a failure of the connection between the relay and the toroid ** (Note the red "tripped" LED will flash during this condition) c, the supply to the unit is removed d, the relay fails internally ** causes the "standard output" relay to energise in response to the fault condition. Prior to a fault occurring, the LED bargraph will indicate the % of In being detected (the display is scaled between 25, 50, and 75% of the actual trip level). After all 3 LED's have illuminated and the unit trips due to an excessive fault current, the red "tripped" LED will illuminate. The unit will now remain in a latched condition. Fault simulation (Test mode) * * The unit can be placed into a fault condition by pressing the "Test" button on the front of the unit (or by pressing the remote "Test" button - if fitted). The output relays operate accordingly. Press the "Reset" button on the front of the unit (or remotely - if fitted) to reset the unit. The output relays revert back to their "non-tripped" state. The unit can also be reset by interrupting the power supply. To satisfy regulations, it is recommended that the device be tested periodically to ensure correct operation. * * Troubleshooting * The operating function of this unit is classed as a Type A for which tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether applied suddenly or slowly rising. Additionally, this unit is protected against nuisance tripping . This unit will also satisfy the requirements for Type AC devices which only need to detect residual alternating currents. This unit should be installed in conjunction with the latest wiring regulations and practices (IEE, etc). 50m* max. test reset * CONNECTION DIAGRAM L1 L2 L3 N E 3 4 5 115V* AC Only 8 9 10 11 12 13 14 positive safety output 6 7 standard output Note: 1. For In setting of 30mA, the time delay is fixed to 0 (instantaneous) and is not adjustable (i.e. any other time delay cannot be selected when 30mA is set). 2. The unit is factory set to 30mA trip and instantaneous delay. Adjustment of these settings can be made if necessary to suit the requirements of the installation. A seal is supplied allowing the user to secure the clear window and hence prevent any unnecessary adjustment of the settings. Reset time: LED indication: Power supply present: Bargraph: Tripped: 2S (from supply interruption) Memory: storage of the leakage fault and reset with the "Reset" push button Ambient temp: Relative humidity: -20 to +55C (-5 to +40C in accordance with IEC 60755) +95% Green Green x 3 (25, 50 and 75% of actual trip level) Red (see "INSTALLATION" to the left) Output : Output rating: 1 x SPNO, 1 x SPDT relays S.O. (12, 13, 14) AC1 (250V) 8A (2000VA) AC15 (250V) 2.5A DC1 (25V) 8A (200W) Electrical life: 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2 / 50S) IEC 60664 P.S.O. (10, 11) 6A (1500VA) 4A 6A (150W) Remote "Test" / "Reset" (1, 2, 3) Requires N.O. contacts. (i.e. push buttons) Minimum trigger time: >80mS (Actual trigger time = 80mS + t setting for remote "test") Housing: Weight: Mounting option: Terminal conductor size: Grey flame retardant Lexan UL94 VO 190g (AC power supplies) 110g (DC power supply) On to 35mm symmetric DIN rail to BS5584:1978 (EN50 002, DIN 46277-3) 2.5mm2 stranded, 4mm2 solid Approvals: Conforms to: IEC60755, 60947, 62020, 61543. 0 *Dual voltage only available as 115V/230V AC. For 115V, connect across terminals 6 and 7 For all other voltages, connect across terminals 5 and 7. Both relays are shown in the de-energised state (i.e. where power is not present on the supply terminals) * Options 1. For other supply voltages, alternative trip levels or time delays, please consult the sales office. * Accessories - Toroids Toroid Type: BZCT035 BZCT070 BZCT120 BZCT210 Internal diameter: 35mm 70mm 120mm 210mm In (min.) A 0.03 0.03 0.1 0.3 * MOUNTING DETAILS 30mm 44mm 49.5mm 63.5mm 45mm 50m* max. A3 2 0 to 30A (15 - 400Hz) (through external toroid with 1000:1 ratio and connected to terminals 8 and 9) 61mm C.T. A1 12 - 125V DC 24V AC 230V* AC (+ve) 400V AC 1 Monitored leakage current: CE and Compliant. ( ) Numbers in brackets shown above refer to terminal numbers on the relay housing. Note: A2 (-ve) Over voltage cat. III 800V (24V AC supplies ), 2.5kV (115V AC supplies) 4kV (230V, 400V AC supplies) 6VA (AC supplies) 5W (DC supplies) IEC 61000-4-2, -3, -4, -5 , -6, -12 and -16. CISPR 22. If the unit fails to operate correctly check that all wiring and connections are good. The Earth MUST NOT pass through the C.T. For single phase applications, only the live and neutral need to be passed through the C.T. *Cabling: For distances >1m, use twisted pair cable between the unit and C.T. Isolation: Rated impulse withstand voltage: (1.2 / 50S) IEC 60664 Power consumption (max.): Sensitivity In (see Accessories) 30, 100, 300, 500mA, 1, 3, 5, 10, 20, 30A (user selectable) Trip level limits: 80 - 90% of In Reset Value: 85% of tripped level Time delay t: 0*, 60, 150, 250, 500, 800mS, 1, 2.5, 5, 10 sec. (user selectable) *Actual delay for "0" or "Instantaneous" is <25mS when fault current @ 5 x In. t "Reset" button pressed Terminal Protection to IP20 * TECHNICAL SPECIFICATION supply interrupted 85mm q q q q q q q q q q q E ELRM44V30-2-A Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 012356 Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user's own risk.