C
40
Transducers
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
NTI
True RMS AC Voltage Transducer
DIN RAIL / PANEL MOUNT, TRUE RMS
CR4510 CR4511 CR4520
Single Element
1.0 to 600 VAC Input Range
CR4550 CR4560
CR4570 CR4580
Three Element
1.0 to 600 VAC Input Range
50 - 0-50 VAC
150 - 0-150 VAC
250 - 0-250 VAC
500 - 0-500 VAC
Ranges available up to and
including 600 VAC
* UL Recognized up to 300 Vac
Add suffix for input range
CR Magnetics has a wide selection of Potential Transformers to extend the range of any part. Contact factory for more information.
The CR4500 Series, True RMS Voltage Transducers and
Transmitters are designed for applications where AC voltage
waveforms are not purely sinusoidal. More precise and
accurate than other devices, these units are ideal in chopped
wave and phase fired control systems.
Applications
Phase fired controlled devices
Quickly varying voltage supplies
Chopped waveform drivers
Harmonic voltages
Features
35mm DIN rail mount or panel mount
Available with 0-5 VDC, 0-10VDC or 4-20 mADC output
24 VDC powered
Highest precision available
Outputs isolated from inputs
Connection diagram printed on case
Regulatory Agencies
Recognized to meet UL 61010B-1
Constructed to meet CAN/CSA-C22.2, No. 61010-1-2004
Meets requirement of IEC 61010-1 and BS EN 61010-1
PART NUMBERS
CR4510
-
Single element with 0 - 5 VDC output
CR4511
-
Single element with 0 - 10 VDC output
CR4520
-
Single element with 4 - 20 mADC output
CR4550
-
3-Phase 3-Wire with 0 to 5 VDC Output
CR4560
-
3-Phase 3-Wire with 4 - 20 mADC Output
CR4570
-
3-Phase 4-Wire with 0 to 5 VDC Output
CR4580
-
3-Phase 4-Wire with 4 - 20 mADC Output
E199795
Transducers
C
41
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
NTI
DIN RAIL / PANEL MOUNT, TRUE RMS
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
True RMS AC Voltage Transducer
OUTPUT
SUPPLY
INPUT 1
+-
+-
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
INPUT 1 OUTPUT 1
+ -
SUPPLY
CR4520 Single Phase - 4 - 20 mADC Output
L1 L2 L3
L1-L2
L2-L3
L3-L1
+-
1
2
3
4
5
6
7
8
9
SUPPLY
CR4560 3 Phase, 3 Wire - 4-20 mADC Output
L1 L2 L3
L1-L2
L2-L3
L3-L1
+-
1
2
3
4
5
6
7
8
9
SUPPLY
SUPPLY
L1 L2 L3 N
L1-N
L2-N
L3-N
+
+
+
+
-
-
-
-
9
8
7
6
5
1
2
3
4
CR4580 3 Phase, 4 Wire - 4 - 20 mADC Output
L1 L2 L3 N
1
2
3
4
5
6
7
8
9
L1-N
L2-N
L3-N
+ -
SUPPLY
CR4510 Single Phase - 0 - 5 VDC Output
CR4511 Single Phase - 0 - 10 VDC Output
CR4550 3 Phase, 3 Wire - 0 - 5 VDC Output
CR4570 3 Phase, 4 Wire - 0 - 5 VDC Output
CONNECTION DIAGRAM
SPECIFICATIONS
Basic Accuracy:........................ 0.5%
Linearity:................................ 10% to 100% FS
Calibration:............................... True RMS Sensing
Thermal Drift:........................... 500 PPM/°C
Operating Temperature:........... 0°C to +60°C
Installation Category:............... CAT II
Vibration Tested To:................. IEC 60068-2-6,1995
Pollution Degree:..................... 2
Response Time:....................... 250 ms
Altitude:.................................... 2000 meter max.
Insulation Voltage:.................... 2500 Vdc
Supply Voltage:........................ 24 Vdc ±10%
Frequency Range:................... 20 Hz - 5 KHz
Cleaning:.................................. Water-dampened cloth
MTBF:......................... Greater than 100 K hours
Output Load:............... 4-20 mADC - 0 to 300
0-5 VDC - 2K or Greater
Relative Humidity:......... 80% for temperatures up to
31°C and decreasing linearly to
50% at 40°C
Supply Current:
CR4510:........................ Typical 15mA Max 25mA
CR4520:........................ Typical 25mA Max 40mA
CR4550/70:................... Typical 20mA Max 60mA
CR4560/80:................... Typical 55mA Max 110mA
Torque Specs.:.............. 3.0 inch lbs. (0.4Nm)
Weight:.......................... 0.5 lbs.
OUTLINE DRAWING
(73)
2.99 (76)
0.20
(5.1) (83)
3.268
for CR4640
2.20 (56) for CR4620
Dimensions for Models CR4550, CR4560, CR4570, CR4580
(shown)
3.5)
1.42
(36)
1.16 (29.5)
CR4510/11/20
2.99 (76)
CR4550/60/70/80
USE CR MAGNETICS LOW AND MEDIUM VOLTAGE POTENTIAL TRANSFORMERS
(SECTION G)