Transducers
C
41
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
NTI
DIN RAIL / PANEL MOUNT, TRUE RMS
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
True RMS AC Voltage Transducer
OUTPUT
SUPPLY
INPUT 1
+-
+-
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
INPUT 1 OUTPUT 1
+ -
SUPPLY
CR4520 Single Phase - 4 - 20 mADC Output
L1 L2 L3
L1-L2
L2-L3
L3-L1
+-
1
2
3
4
5
6
7
8
9
SUPPLY
CR4560 3 Phase, 3 Wire - 4-20 mADC Output
L1 L2 L3
L1-L2
L2-L3
L3-L1
+-
1
2
3
4
5
6
7
8
9
SUPPLY
SUPPLY
L1 L2 L3 N
L1-N
L2-N
L3-N
+
+
+
+
-
-
-
-
9
8
7
6
5
1
2
3
4
CR4580 3 Phase, 4 Wire - 4 - 20 mADC Output
L1 L2 L3 N
1
2
3
4
5
6
7
8
9
L1-N
L2-N
L3-N
+ -
SUPPLY
CR4510 Single Phase - 0 - 5 VDC Output
CR4511 Single Phase - 0 - 10 VDC Output
CR4550 3 Phase, 3 Wire - 0 - 5 VDC Output
CR4570 3 Phase, 4 Wire - 0 - 5 VDC Output
CONNECTION DIAGRAM
SPECIFICATIONS
Basic Accuracy:........................ 0.5%
Linearity:................................ 10% to 100% FS
Calibration:............................... True RMS Sensing
Thermal Drift:........................... 500 PPM/°C
Operating Temperature:........... 0°C to +60°C
Installation Category:............... CAT II
Vibration Tested To:................. IEC 60068-2-6,1995
Pollution Degree:..................... 2
Response Time:....................... 250 ms
Altitude:.................................... 2000 meter max.
Insulation Voltage:.................... 2500 Vdc
Supply Voltage:........................ 24 Vdc ±10%
Frequency Range:................... 20 Hz - 5 KHz
Cleaning:.................................. Water-dampened cloth
MTBF:......................... Greater than 100 K hours
Output Load:............... 4-20 mADC - 0 to 300 Ω
0-5 VDC - 2K Ω or Greater
Relative Humidity:......... 80% for temperatures up to
31°C and decreasing linearly to
50% at 40°C
Supply Current:
CR4510:........................ Typical 15mA Max 25mA
CR4520:........................ Typical 25mA Max 40mA
CR4550/70:................... Typical 20mA Max 60mA
CR4560/80:................... Typical 55mA Max 110mA
Torque Specs.:.............. 3.0 inch lbs. (0.4Nm)
Weight:.......................... 0.5 lbs.
OUTLINE DRAWING
(73)
2.99 (76)
0.20
(5.1) (83)
3.268
for CR4640
2.20 (56) for CR4620
Dimensions for Models CR4550, CR4560, CR4570, CR4580
(shown)
1.22
(31)
(36) 0.14
(3.5)
1.06
(26.8)
2.874
(73) 0.79
(20)
5
6
7
8
9
1
2
3
4
1.16 (29.5)
CR4510/11/20
2.99 (76)
CR4550/60/70/80
USE CR MAGNETICS LOW AND MEDIUM VOLTAGE POTENTIAL TRANSFORMERS
(SECTION G)