Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multi-function Types DPB01, PPB01 DPB01 * TRMS 3-phase over and under voltage, phase sequence and phase loss monitoring relays * Detect when all 3 phases are present and have the correct phase sequence (except for N versions) * Available versions (W4) supplied between phase and neutral * Detect if all the 3-phase-phase or phase-neutral voltages are within the set limits * Upper and lower limits separately adjustable * Measure on own power supply * Selection of measuring range by DIP-switches * Adjustable voltage on relative scale * Adjustable delay function (0.1 to 30 s) * Output: 8 A SPDT relay N.E. * For mounting on DIN-rail in accordance with DIN/EN 50 022 (DPB01) or plug-in module (PPB01) * 22.5 mm Euronorm housing (DPB01) or 36 mm plug-in module (PPB01) * LED indication for relay, alarm and power supply ON PPB01 Product Description Ordering Key 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, over and under voltage (separately adjustable set Housing Function Type Item number Output Power supply points) with built-in time delay function. Supply ranges from 208 to 480 VAC covered by two multivoltage relays. DPB 01 C M23 Type Selection Mounting Phase sequence Output detection Supply: 208 to 240 VAC Supply: 380 to 415 VAC Supply: 380 to 480 VAC DIN-rail Plug-in Plug-in DIN-rail Plug-in Plug-in yes yes yes no no no DPB 01 C M23 PPB 01 C M23 DPB 01 C M48 W4 PPB 01 C M48 W4 PPB 01 C M48 DPB 01 C M48 N W4 PPB 01 C M48 N W4 PPB 01 C M48 N DPB 01 C M48 SPDT SPDT SPDT SPDT SPDT SPDT DPB 01 C M23 N PPB 01 C M23 N DPB 01 C M48 N Input Specifications Input L1, L2, L3, N DPB01: Terminals L1, L2, L3, N PPB01: Terminals 5, 6, 7, 11 Measure on own supply Note: Connect the neutral only if it is intrinsically at the star centre Measuring ranges 177 to 275 VL-L AC 208 to 240 VAC M23 versions 380 to 415 VAC 323 to 475 VL-L AC PPB01CM48 PPB01CM48N D/P PB01CM48W4 D/P PB01CM48NW4 380 to 480 VAC 323 to 550 VL-L AC DPB01CM48 DPB01CM48N Specifications are subject to change without notice (16.10.06) Ranges Upper level Lower level +2 to +22% of the nominal voltage -22 to -2% of the nominal voltage Note: The input voltage must not exceed the maximum rated voltage or drop below the minumum rated voltage reported above. Hysteresis Set points from 2 to 5% 1% Set points from 5 to 22% 2% 1 DPB01, PPB01 Output Specifications Output Rated insulation voltage Contact ratings (AgSnO2) AC 1 Resistive loads DC 12 Small inductive loads AC 15 DC 13 Mechanical life Electrical life SPDT relay 250 VAC 8 A @ 250 VAC 5 A @ 24 VDC 2.5 A @ 250 VAC 2.5 A @ 24 VDC 30 x 106 operations 105 operations (at 8 A, 250 V, cos = 1) 7200 operations/h Operating frequency Dielectric strength Dielectric voltage 2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 s) Supply Specifications Power supply Rated operational voltage through terminals: L1, L2, L3, N (DPB01) 5, 6, 7, 11 (PPB01) D/P PB01CM23, D/P PB01CM23N Overvoltage cat. III (IEC 60664, IEC 60038) 208 to 240 VL-L AC 15% 45 to 65 Hz D/P PB01CM48W4, 380 to 415 VL-L AC 15% D/P PB01CM48NW4, (220 to 240 VL-N AC 15%) PPB01CM48, PPB01CM48N 45 to 65 Hz DPB01CM48, DPB01CM48N 380 to 480 VL-L AC 15% (220 to 277 VL-N AC 15%) 45 to 65 Hz Rated operational power DPB01CM23x, PPB01CM23x 13 VA @ 230 VAC, 50 Hz DPB01CM48x, PPB01CM48x 13 VA @ 400 VAC, 50 Hz Supplied by L1 and L2 DPB01CM48xW4 13 VA @ 400 VAC, 50 Hz DPB01CM48xW4 Supplied by L1 and N General Specifications Power ON delay Reaction time Incorrect phase sequence or total phase loss Voltage level Alarm ON delay Alarm OFF delay Accuracy Temperature drift Delay ON alarm Repeatability Indication for Power supply ON Alarm ON Output relay ON Environment Degree of protection Pollution degree Operating temperature @ Max. voltage, 50 Hz @ Max. voltage, 60 Hz Storage temperature Housing Dimensions DPB01 PPB01 Weight Screw terminals Tightening torque Approvals CE Marking EMC Immunity Emissions 1 s 0.5 s or 6 s 0.5 s < 200 ms (input signal variation from -20% to +20% or from +20% to -20% of set value) < 200 ms (delay < 0.1 s) < 200 ms (delay < 0.1 s) (15 min warm-up time) 1000 ppm/C 10% on set value 50 ms 0.5% on full-scale LED, green LED, red (flashing 2 Hz during delay time) LED, yellow IP 20 3 (DPB01), 2 (PPB01) -20 to 60C, R.H. < 95% -20 to 50C, R.H. < 95% -30 to 80C, R.H. < 95% 22.5 x 80 x 99.5 mm 36 x 80 x 94 mm Approx. 120 g Max. 0.5 Nm according to IEC 60947 UL, CSA (except for W4 versions) Yes Electromagnetic Compatibility According to EN 61000-6-2 According to EN 61000-6-3 Mode of Operation Connected to the 3 phases (and neutral) DPB01 and PPB01 operate when all 3 phases are present at the same time, the phase sequence is correct (not N versions) and the phasephase (or phase-neutral) voltage levels are within set limits. If one or more phase-phase or phase-neutral voltages exceeds the upper set level or drops below the lower set level, the red LED starts 2 flashing 2 Hz and the output relay releases after the set time period. In any case if phase-neutral measurement is selected both phasephase and phase-neutral voltages are monitored. If the phase sequence is wrong or one phase is lost, the output relay releases immediately. Only 200 ms delay occurs. The failure is indicated by the red LED flashing 5 Hz during the alarm condition. Example 1 (mains network monitoring) Example 2 (load monitoring) The relay monitors over and under voltage, phase loss phase and correct sequence. In case of N versions, the relay monitors over and under voltage. The relay releases in case of interruption of one or more phases, when one or more voltages drop below the lower set level or exceed the upper set level. Specifications are subject to change without notice (16.10.06) DPB01, PPB01 Function/Range/Level and Time Delay Setting Adjust the input range setting the DIP switches 3 and 4 as shown below. To access the DIP swiches open the grey plastic cover as shown below Select the desired function setting the DIP switches 1 and 2 as shown below. Selection of level and time delay: Upper knob: Setting of lower level on relative scale. Centre knob: Setting of upper level on relative scale. Lower knob: Setting of delay on alarm time on absolute scale (0.1 to 30 s). Power ON delay ON: 6 s 0.5 s OFF: 1 s 0.5 s Monitored voltage ON: Phase-Neutral OFF: Phase-Phase Measuring range SW3 ON ON OFF OFF ON OFF ON OFF SW4 M23 Ph-Ph 208 VAC 220 VAC 230 VAC 240 VAC Voltage M48 Ph-Ph 380 VAC 400 VAC 415 VAC 480 VAC Voltage DPB01CM48, DPB01CM48N only M48 Ph-N 220 VAC 230 VAC 240 VAC 277 VAC Voltage DPB01CM48, DPB01CM48N only Operation Diagrams Specifications are subject to change without notice (16.10.06) 3 DPB01, PPB01 Operation Diagrams (cont.) (*) (*) N versions don't detect incorrect phase sequence. Wiring Diagrams DPB01 4 PPB01 Specifications are subject to change without notice (16.10.06) DPB01, PPB01 Note When DPB01 or PPB01 is used with phase indicator lamps (see examples in the following diagrams), the lamp H1 or H2 might be dimly lit when there is a phase loss in L1 or L2. This might happen if the lamps used are the typical low power indicator lamps, and there are no other loads present. This fact can be avoided by using W4 models. Note that the neutral must be always connected to the device. DPB01 PPB01 N L3 L2 L1 N L3 L2 L1 m L1 L2 L3 m<3 L1 16 m 18 m<3 U H1 H2 H3 L1 L2 N 15 5 U 6 7 4 3 H1 L2 11 H2 H3 1 Dimensions Plug-in DIN-rail 94 90 63 28.5 Specifications are subject to change without notice (16.10.06) 80 36 63 99.5 83.5 80 22.5 28.5 5