H-1
Table of Contents
Low Voltage Switch Gear
LVSG
Selection Guide H-2
J7KNA-AR Mini Contactor Relays 4-pole H-7
J7KNA Mini Motor Contactor H-15
J7KN Motor Contactor H-27
J7TKN Thermal Overload Relay H-57
J7MN Motor Protection Circuit Breaker (MPCB) H-69
Appendix H-83
H-2
Selection Guide
Low Voltage Switch Gear
Classification Mini Contactor Relays Mini Motor Contactors
Model J7KNA - AR J7KNA J7KNA-4
4-pole 3-pole 4-pole
Appearance
Remarks AC and DC operated
4-, 6- and 8-contacts in different
configurations
Positively guided contacts
Screw fixing and snap fitting (DIN rail)
AC and DC operated
3 main poles
1 auxiliary contact
integrated (1NO or 1NC)
AC operated
4 main poles
Accessoirs Auxiliar contact modules Auxiliar contact modules
Suppressors
Link module MPCB - contactor
Auxiliar contact modules
Suppressors
Link module MPCB - contactor
Maximum power (AC3-380/415V) No 4 kW; 5,5 kW 4 kW
Rated current (AC3-380/415V) 10 A (I th2) 9/12 A 9 A
AC operated Yes Yes Yes
DC operated Yes Yes No
4 - pole version Yes No Yes
Auxiliary contacts included No 1NO or 1NC No
Auxiliary contacts front
mounting
1NO/1NC
0NO/2NC
2NO/2NC
4NO/0NC
1NO/1NC
0NO/2NC
2NO/2NC
1NO/1NC
0NO/2NC
2NO/2NC
Auxiliary contacts side mounting No No No
Mechanical life span
(AC operated)
5 Mio. 5 Mio. 5 Mio.
Mechanical life span
(DC operated)
15 Mio. 15 Mio. 15 Mio.
Setting range (in A) No No No
Page No. H-7 H-15 H-15
H-3
LVSG
Motor Contactors
J7KN 10..KN 22 J7KN 24..KN 40 J7KN 50..KN 74 J7KN 85..KN 110
3-pole 3-pole 3-pole 3-pole
AC and DC operate
3 main poles
1 auxiliary contact integrated (1NO or
1NC)
max 4 auxiliary contacts front mounted
AC and DC operate
3 main poles
max 4 auxiliary contacts front mounted
2 auxiliary contacts side mounted (1NO
or 1NC)
AC and DC operate
3 main poles
max 4 auxiliary contacts front mounted
2 auxiliary contacts side mounted (1NO
or 1NC)
AC and DC operate
3 main poles
4 auxiliary contacts integrated
(1NO/1NC)
Auxiliar contact modules
Mechanical interlock
Suppressors
Link module MPCB-contactor
Pneumatic timers
Auxiliar contact modules
Mechanical interlock
Suppressors
Link module MPCB-contactor
Pneumatic timers
Auxiliar contact modules
Mechanical interlock
Suppressors
Pneumatic timers
Mechanical interlock
Suppressors
4 kW; 5,5 kW; 7,5 kW; 11 kW 11 kW; 15 kW; 18,5 kW 22 kW; 30kW; 37 kW 45 kW; 55 kW
10/14/18/22 A 24/32/40 A 50/62/74 A 85/110 A
Yes Yes Yes Yes
Yes Yes Yes Yes
No No No No
1NO or 1NC No No 2NO + 2NC
max 4
NO/NC
max 4
NO/NC
max 4
NO/NC
No
No 1NO + 1NC 1NO + 1NC 1NO + 1NC
10 Mio. 10 Mio. 10 Mio. 5 Mio.
10 Mio. 10 Mio. 10 Mio. 5 Mio.
No No No No
H-27 H-27 H-27 H-27
H-4
Selection Guide
Low Voltage Switch Gear
Classification Motor Contactors Thermal Overload Relays
Model J7KN 150..KN 175 J7KN 200 J7TKN-A
3-pole 3-pole
Appearance
Remarks AC and DC operate
3 main poles
2 auxiliary contacts integrated (1NO/
1NC)
AC and DC operate
3 main poles
4 auxiliary contacts integrated (1NO/
1NC)
Direct mounting
1 auxiliary contact (change over)
Accessoirs No No No
Maximum power (AC3-380/415V) 75 kW; 90 kW 110 kW
Rated current (AC3-380/415V) 150/175 A 210 A
AC operated Yes Yes
DC operated No No
4 - pole version No No
Auxiliary contacts included 1NO + 1NC 2NO + 2NC 1NO + 1NC
Auxiliary contacts front
mounting
No No
Auxiliary contacts side mounting 1NO + 1NC 2NO + 2NC
Mechanical life span
(AC operated)
10 Mio. 10 Mio.
Mechanical life span
(DC operated)
10 Mio. 10 Mio.
Setting range (in A) No No 0,12..30 A
Page No. H-27 H-27 H-57
H-5
LVSG
Thermal Overload Relays Motor Protection Circuit Breakers (MPCB)
J7TKN-B..TKN-D J7TKN-E..TKN-F J7MN12 J7MN25
Direct mounting
Auto, -manual, -reset button
2 auxiliary contacts (1NO/1NC)
Separate mounting
2 auxiliary contacts (1NO/1NC)
Rocker operating switch
Short circuit release
Over load release
I cu = 100 kA (0,16..6,3 A)
Rotary operating switch
Short circuit release
Over load release
I cu = 100 kA (0,16..12,5 A)
Sets for single mounting
Busbar sets
Sets for single mounting
Busbar sets
Trip indicating contact
Plastic enclosures
2 contacts side mounted
2 contacts front mounted
Bus bar system
Trip indicating contact
Plastic enclosures
3 contacts side mounted
2 contacts front mounted
Bus bar system
1NO + 1NC 1NO + 1NC 1NO + 1NC 1NO + 1NC
1NO + 1NC 1NO + 1NC
100000 100000
0,12..74 A 60..220 A 0,11..12 A 0,11..25 A
H-57 H-57 H-69 H-69
H-6
Selection Guide
Low Voltage Switch Gear
Classification Motor Protection Circuit Breakers (MPCB)
Model J7MN50 J7MN100
Appearance
Remarks Rotary operating switch
Short circuit release
Over load release
I cu = 50 kA
Rotary operating switch
Short circuit release
Over load release
I cu = 50 kA
Accessoirs Trip indicating contact
Plastic enclosures
2 contacts side mounted
3 contacts front mounted
Bus bar system
Trip indicating contact
Plastic enclosures
2 contacts side mounted
3 contacts front mounted
Bus bar system
Maximum power (AC3-380/415V)
Rated current (AC3-380/415V)
AC operated
DC operated
4 - pole version
Auxiliary contacts included
Auxiliary contacts front
mounting
1NO + 1NC 1NO + 1NC
Auxiliary contacts side mounting 1NO + 1NC 1NO + 1NC
Mechanical life span
(AC operated)
50000 50000
Mechanical life span
(DC operated)
Setting range (in A) 22..50 A 45..100 A
Page No. H-69 H-69
Mini Contactor Relays 4-pole J7KNA-AR H-7
LVSG
Mini Contactor Relays 4-pole
J7KNA-AR
Main contactor
AC & DC operated
4-, 6- and 8-pole versions in different configurations
Positively guided contacts
Screw fixing and snap fitting (35 mm DIN rail)
Rated current = 10A (Ith)
Suitable for electronic devices (DIN 19240)
Finger proof (VBG 4)
Accessories
2- and 4-pole additional auxiliary contacts in different
configurations
)
Approved Standards
Ordering Information
Model Number Legend
1. Mini Contactor Relays
1) Mini Contactor
2) AR: Contactor Relay
3) Combination of NO / NC contacts
22: 2 NO 2 NC
31: 3 NO 1NC
40: 4 NO 0NC
4) Coil voltage (AC operated)
24: AC24V 50/60Hz
48: AC48V 50Hz
110: AC110-115V 50Hz,AC120-125V 60Hz
230: AC220-230V 50Hz,AC240V 60Hz
240: AC230V-240V 50Hz
400: AC380-400V 50Hz,AC440V 60Hz
415: AC400-415V 50Hz
550: AC525-550V 50Hz,AC600V 60Hz
Coil voltage (DC operated)
24D: DC24V
48D: DC48V
60D: DC60V
110D: DC110V
125D: DC125V
24VS: DC24V with diode
48VS: DC48V with diode
110VS: DC110V with diode
2. Aux. Contact Modules for Mini Contactor Relays
1) Auxiliary Contact Modules
2) A: for mini contactor relay
3) Combination of NO/NC contacts
11: 1 NO 1 NC
02: 0 NO 2 NC
22: 2 NO 2 NC
40: 4 NO 0 NC
Standard Guide No (US,C)
UL NKCR, NKCR7
ICE 947-5-1
VDE 0660
EN 60947-5-1
7KNA-##-##-#####
123 4
73KN-##-##-#
123
4
H-8 Mini Contactor Relays 4-pole J7KNA-AR
System overview
Mini Contactor Relays 4-pole
AC Operated
Contacts Distinc.
Number
acc. to
DIN EN
50011
Ratings Thermal
Rated
Current
Ith
A
Type Pack
pcs.
Weight
kg/pc.NO NC
AC15
230V
A
400V
A
24
230
Coil voltage 1)
24V 50/60Hz
220-230V 50Hz
4-pole, With Screw Terminals
4- 40E 3 2 10 J7KNA-AR-40 24 10 0,16
J7KNA-AR-40 230
3131E 3 2 10 J7KNA-AR-31 24 10 0,16
J7KNA-AR-31 230
2222E 3 2 10 J7KNA-AR-22 24 10 0,16
J7KNA-AR-22 230
1) Other coil voltages see page 10
DC Solenoid Operated
Contacts Distinc.
Number
acc. to
DIN EN
50011
Ratings Thermal
Rated
Current
Ith
A
Type Pack
pcs.
Weight
kg/pc.NO NC
AC15
230V
A
400V
A Coil voltage 24V DC 2,5W
4-pole, With Screw Terminals
4- 40E 3 2 10 J7KNA-AR-40 24D (-VS)1) 10 0,19
3131E 3 2 10 J7KNA-AR-31 24D (-VS)1) 10 0,19
2222E 3 2 10 J7KNA-AR-22 24D (-VS)1) 10 0,19
1) VS = with diode
Auxiliary Contact Blocks for Contactor Relays J7KNA-AR
Contacts Ratings Thermal
Rated
Current
Ith
A
Type Pack
pcs.
Weight
kg/pc.NO NC
AC15
230V
A
400V
A
11 3 2 10 J73KN-A-11 10 0,04
-2 3 2 10 J73KN-A-02 10 0,04
4- 3 2 10 J73KN-A-40 10 0,04
22 3 2 10 J73KN-A-22 10 0,04
Mini Contactor Relays 4-pole J7KNA-AR H-9
LVSG
System overview
Mini Contactor Relays 4-pole
AC Operated
Wiring Diagrams Distinc.
Number
acc. to
DIN EN
50011
Auxiliary Contact Blocks Contactor Relay with Auxiliary Contact Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
Type NO NC
Block
Distinc. Number
according to
DIN EN 50011 NO NC
4-pole, With Screw Terminals
40E J73KN-A-11 1 1 51E 5 1 Preferable combinations with
distinctive letter „E“
according to DIN EN 50011
J73KN-A-02 0242E 42
J73KN-A-40 4080E 80
J73KN-A-22 2262E 62
31E J73KN-A-11 1142Y 42
J73KN-A-02 0233Y 33
J73KN-A-40 4071Y 71
J73KN-A-22 2253Y 53
22E J73KN-A-11 1133Y 33
J73KN-A-02 0224Y 24
J73KN-A-40 4062Y 62
J73KN-A-22 2244Y 44
DC Solenoid Operated
Wiring Diagrams Distinc.
Number
acc. to
DIN EN
50011
Auxiliary Contact Blocks Contactor Relay with Auxiliary Contact
Type NO NC
Block
Distinc. Number
according to
DIN EN 50011 NO NC
4-pole, With Screw Terminals
40E J73KN-A-11 1 1 51E 5 1 Preferable combinations with
distinctive letter „E“
according to DIN EN 50011
J73KN-A-02 0242E 42
J73KN-A-40 4080E 80
J73KN-A-22 2262E 62
31E J73KN-A-11 1142Y 42
J73KN-A-02 0233Y 33
J73KN-A-40 4071Y 71
J73KN-A-22 2253Y 53
22E J73KN-A-11 1133Y 33
J73KN-A-02 0224Y 24
J73KN-A-40 4062Y 62
J73KN-A-22 2244Y 44
Auxiliary Contact Blocks for Contactor Relays J7KNA-AR
Wiring diagrams Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
J73KN-A-11 J73KN-A-02 J73KN-A-40 J73KN-A-22
H-10 Mini Contactor Relays 4-pole J7KNA-AR
Specifications
Coil Voltages
Standard voltages in bold type letters. Coil not exchangeable
Suffix Voltage Marking Rated Control Voltage Us
to contactor type
e.g. at the coil
range for
50Hz 60Hz
J7KNA-09-10-24
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
12 12 12 11 12 12 12
24 24 24 22 24 24 24
42 42 42 38.5 42 42 42
48 48-50 48 48 50 48 50
60 60 60 52 66 54 60
90 90-95 100-105 90 95 100 105
95 95-100 105-110 95 100 105 110
100 100 110-115 100 105 110 115
105 105-110 115-120 105 110 115 120
110 110-115 120-125 110 115 120 125
200 200 210-220 195 205 210 220
Suffix Voltage Marking Rated Control Voltage Us
to contactor type
e.g. at the coil
range for
50Hz 60Hz
J7KNA-09-10- 230
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
210 205-215 220-230 205 215 220 230
220 210-220 230-240 210 220 230 240
230 220-230 240 220 230 240 250
240 230-240 230 240 250 260
400 380-400 440 380 400 415 440
500 475-500 520-545 475 500 520 545
550 525-550 600 525 550 570 600
Mini Contactor Relays 4-pole J7KNA-AR H-11
LVSG
Engineering data and Characteristics
Mini Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Ty p e J7KNA-AR... J7KNA-AR...D J7KNA-AR...VS J73KN-A...
Rated insulation voltage Ui V AC 690*1 690*1 690*1 690*1
Thermal rated current Ith to 690V
Ambient temperature 40°C A 10 10 10 10
60°C A 6 6 6 6
Power loss per pole at Ith W 0.5 0.5 0.5 0.5
Utilization category AC15
Rated operational current Ie220-240V A 3 3 3 3
380-415V A 2 2 2 2
440V A 1.6 1.6 1.6 1.6
500V A 1.2 1.2 1.2 1.2
660-690V A 0.6 0.6 0.6 0.6
Utilization category DC13
Rated operational current Ie60V A 2 2 2 2
110V A 0.4 0.4 0.4 0.4
220V A 0.1 0.1 0.1 0.1
Maximum ambient temperature
Operation open °C -40 to +60 (+90)*2
enclosed °C -40 to +40
Storage °C -40 to +90
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 20 20
Power consumption of coils
AC operated inrush VA 25 - - -
sealed VA 4 - 5 - - -
W1.2 - - -
DC operated inrush W - 2.5 2.5 -
sealed W - 2.5 2.5 -
Operation range of coils
in multiples of control voltage Us0.85 - 1.1 0.8 - 1.1 0.8 - 1.1 -
Switching time at control voltage Us ±10%*3,*4
AC operated make time ms 15 - 25 - - -
release time ms 8 - 25 - - -
arc duration ms 10 -15 - - -
DC operated make time ms - 15 - 19 - -
release time ms - 8 - 25 - -
arc duration ms - 10 -15 - -
H-12 Mini Contactor Relays 4-pole J7KNA-AR
Cable cross-section
all connectors solid mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible with multicore cable end mm² 0.5 - 1.5 0.5 - 1.5 0.5 - 1.5 0.5 - 2.5
Clamps per pole 2 2 2 2
solid or stranded AWG 18 - 14 18 - 14 18 - 14 18 - 14
*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced thermal rated current Ith to Ie/AC15
*3) Summary switching time = release time + arc duration
*4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used
(Varistor, RC-units, Diode units).
Mini Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Ty p e J7KNA-AR... J7KNA-AR...D J7KNA-AR...VS J73KN-A...
Mini Contactor Relays for North America
Data according to UL508
Main Contacts (cULus) Ty p e J7KNA-AR... J73KN-A...
Rated operational current "General Use" A 10 10
Rated operational power of three-phase motors 115V hp - -
at 60Hz (3ph) 200V hp - -
230V hp - -
460V hp - -
575V hp - -
Rated operational power of of AC motors 115V hp - -
at 60Hz (1ph) 200V hp - -
230V hp - -
Fuses A - -
Suitable for use on a capability of delivering not more than rms A - -
V- -
Rated voltage V AC 600 600
Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600
standard pilot duty DC Q600 Q600
Mini Contactor Relays 4-pole J7KNA-AR H-13
LVSG
Dimensions
AC and DC operated
with screw terminals
Auxiliary Contact Blocks
J7KNA-AR... J73KN-A...
H-14 Mini Contactor Relays 4-pole J7KNA-AR
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J507-E2-02
Mini Motor Contactor J7KNA H-15
LVSG
Mini Motor Contactor
J7KNA
Main contactor
AC & DC operated
Integrated auxiliary contacts
Screw fixing and snap fitting (35 mm DIN rail)
Range from 4 to 5.5 kW (AC 3, 380/415V)
4 -main pole version (4 kW AC and DC coil)
Auxiliary contacts suitable for electronic devices (DIN 19240)
Finger proof (VBG 4)
Accessories
2 and 4 pole additional auxiliary contacts in different
configurations
Mechanical interlock (in reversing contactor combination only)
RC Suppressors
)
Approved Standards
Ordering Information
Model Number Legend
1. Mini Motor Contactors
1) Mini Contactor
2) Rated Motor Current (AC3 400V)
09: 9A
12: 12A
3) Integrated auxiliary contact
10: 1 NO 0 NC
01: 0 NO 1 NC
4: 4 main pole type (no aux contact)
4) W: Reversing Contactor
5) Coil voltage (AC operated)1)
24: AC24V 50/60Hz
48: AC48V 50Hz
60: AC60V 50Hz
110: AC110-115V 50Hz, AC120-125V 60Hz
230: AC220-230V 50Hz, AC240V 60Hz
240: AC230V-240V 50Hz
400: AC380-400V 50Hz, AC440V 60Hz
415: AC400-415V 50Hz
Coil voltage (DC operated)
24D: DC24V
48D: DC48V
60D: DC60V
110D: DC110V
24VS: DC24V with diode
48VS: DC48V with diode
110VS: DC110V with diode
2. Aux. Contact Modules for Mini Motor Contactors
1) Auxiliary Contact Modules
2) AM: for mini motor contactor
3) Combination of NO/NC contacts
11: 1 NO 1 NC
02: 0 NO 2 NC
22: 2 NO 2 NC
40: 4 NO 0 NC
4) for Reversing Contactors
v: left side
x: right side
Standard Guide No (US,C)
UL NLDX, NLDX7
ICE 947-5-1
VDE 0660
EN 60947-5-1
1) RC-suppressor unit go to page H-29, section 6 or
page H-35, suppressor units
J7KNA-##-##-#-#####
123
45
J73KN-##-##-#
123
4
H-16 Mini Motor Contactor J7KNA
System overview
Mini Motor Contactors
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept
Overlod
Relay see
page H-58
Coil Voltage*1
24 24V 50/60Hz
230 220-230V 50Hz pcs. kg/pc.
3-pole, With Screw Terminals
4449201- J7TKN-A J7KNA-09-10-##### 10 0.16
5.5 5.5 5.5 12 20 1 - J7TKN-A J7KNA-12-10-##### 10 0.16
444920- 1J7TKN-A J7KNA-09-01-##### 10 0.16
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-##### 10 0.16
4-pole, With Screw Terminals
444920- - J7TKN-A J7KNA-09-4-##### 10 0.19
*1) Other coil voltages see page H-20
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept
Overlod
Relay see
page H-58
DC Coil Voltage
24D 24V 50/60Hz
24VS 24V 50/60Hz w. diode*1 pcs. kg/pc.
3-pole, With Screw Terminals
4449201- J7TKN-A J7KNA-09-10-###D(-VS) 10 0.19
5.5 5.5 5.5 12 20 1 - J7TKN-A J7KNA-12-10-###D(-VS) 10 0.19
444920- 1J7TKN-A J7KNA-09-01-###D(-VS) 10 0.19
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-###D(-VS) 10 0.19
*1) with built-in coil suppressor (zener diode)
Contacts Rated Current Thermal Rated Current Type Pack Weight
NO NC
AC15
230V
A
400V
AApcs. kg/pc.
11 3210 J73KN-AM-11 10 0.04
-2 3210 J73KN-AM-02 10 0.04
22 3210 J73KN-AM-22 10 0.04
Mini Motor Contactor J7KNA H-17
LVSG
System overview
Mini Motor Contactors
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...
Wiring Diagrams Auxiliary Contact Blocks Contactor with Auxiliary Contact
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
Block
Distinc. Number
according to DIN
EN 50012 Type NO NC
Distinc. Number
according to DIN
EN 50012 NO NC
3-pole, With Screw Terminals
10
J73KN-AM-11 1121 21Prefered combinations according
to DIN EN 50012
J73KN-AM-02 0212 12
J73KN-AM-22 2232 32
01
J73KN-A-11 11- 12
Contacts according to
DIN EN 50005
J73KN-A-02 02- 03
J73KN-A-40 40- 41
J73KN-A-22 22- 23
4-pole, With Screw Terminals
00
J73KN-A-11 11- 11
Contacts according to
DIN EN 50005
J73KN-A-02 02- 02
J73KN-A-40 40- 40
J73KN-A-22 22- 22
1
2
3
4
5
6
7
8
A1
A2
Wiring Diagrams Auxiliary Contact Blocks Contactor with Auxiliary Contact
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
Block
Distinc. Number
according to DIN
EN 50012 Type NO NC
Distinc. Number
according to DIN
EN 50012 NO NC
3-pole, With Screw Terminals
10
J73KN-AM-11 1121 21Prefered combinations according
to DIN EN 50012
J73KN-AM-02 0212 12
J73KN-AM-22 2232 32
01
J73KN-A-11 11- 12
Contacts according to
DIN EN 50005
J73KN-A-02 02- 03
J73KN-A-40 40- 41
J73KN-A-22 22- 23
Wiring Diagrams Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
J73KN-AM-11 J73KN-AM-02 J73KN-AM-22 J73KN-A-11 J73KN-A-02 J73KN-A-40 J73KN-A-22
H-18 Mini Motor Contactor J7KNA
System overview
Mini Reversing Contactors, Mechanical Interlocked
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09-01-W...(D) and
J7KNA-12-01-W...(D)
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept
Overlod
Relay see
page H-58
Coil Voltage*1
24 24V 50/60Hz
230 220-230V 50Hz pcs. kg/pc.
3-pole, With Screw Terminals
444920- 1J7TKN-A J7KNA-09-01-W-##### 10.32
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-W-##### 10.32
*1) Other coil voltages see page H-20
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept
Overlod
Relay see
page H-58
DC Coil Voltage
24D 24V 50/60Hz
24VS 24V 50/60Hz w. diode*1 pcs. kg/pc.
3-pole, With Screw Terminals
444920- 1J7TKN-A J7KNA-09-01-W-###D
10.38
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-W-###D
10.38
*1) with built-in coil suppressor (zener diode)
Contacts Rated Current Thermal Rated Current Type Pack Weight
NO NC
AC15
230V
A
400V
AApcs. kg/pc.
11 3210 J73KN-AM-11V 10 0.04
11 3210 J73KN-AM-11X 10 0.04
Mini Motor Contactor J7KNA H-19
LVSG
System overview
Mini Motor Contactors
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09-01-W...(D) and
J7KNA-12-01-W...(D)
Wiring Diagrams Auxiliary Contact Blocks suitable for
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
left hand side right hand side
Distinc. Number
according to DIN
EN 50012
Contactor K1
Ty p e N O N C
Contactor K2
Type NO NC
3-pole, With Screw Terminals
01
J73KN-AM-11V 11J73KN-AM-11X 11
Wiring Diagrams Auxiliary Contact Blocks suitable for
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
left hand side right hand side
Distinc. Number
according to DIN
EN 50012
Contactor K1
Ty p e N O N C
Contactor K2
Type NO NC
3-pole, With Screw Terminals
01
J73KN-AM-11V 11J73KN-AM-11X 11
Wiring Diagrams Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
J73KN-AM-11V J73KN-AM-11X
13
14
31
32
31
32
13
14
H-20 Mini Motor Contactor J7KNA
Specifications
Coil Voltages
Standard voltages in bold type letters. Coil not exchangeable
Suffix Voltage Marking Rated Control Voltage Us
to contactor type
e.g. at the coil
range for
50Hz 60Hz
J7KNA-09-10-24
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
12 12 12 11 12 12 12
24 24 24 22 24 24 24
48 48-50 48 48 50 48 50
60 60 60 52 66 54 60
90 90-95 100-105 90 95 100 105
95 95-100 105-110 95 100 105 110
100 100 110-115 100 105 110 115
105 105-110 115-120 105 110 115 120
110 110-115 120-125 110 115 120 125
200 200 210-220 195 205 210 220
Suffix Voltage Marking Rated Control Voltage Us
to contactor type
e.g. at the coil
range for
50Hz 60Hz
J7KNA-09-10 -230
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
210 205-215 220-230 205 215 220 230
220 210-220 230-240 210 220 230 240
230 220-230 240 220 230 240 250
240 230-240 230 240 250 260
400 380-400 440 380 400 415 440
500 475-500 520-545 475 500 520 545
550 525-550 600 525 550 570 600
Mini Motor Contactor J7KNA H-21
LVSG
Engineering data and Characteristics
Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Ty p e J7KNA-09-... J7KNA-12-...
Rated insulation voltage UiV AC 690*1) 690 ’1)
Making capacity Ieff at Ue = 690V AC A 165 165
Breaking capacity Ieff 400V AC A 100 100
cosϕ = 0,65 500V AC A 90 90
690V AC A 80 80
Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open A 20 20
Rated operational power of three-phase resistive loads 230V kW 7.9 7.9
50-60Hz, cosϕ = 1 240V kW 8.3 8.3
400V kW 13.8 13.8
415V kW 14.3 14.3
Rated operational current Ie (=Ithe) at 60°C, enclosed A 16 16
Rated operational power of three-phase resistive loads 230V kW 6.3 6.3
50-60Hz, cosϕ = 1 240V kW 6.7 6.7
400V kW 11 11
415V kW 11.5 11.5
Minimum cross-section of conductor at load with Ie (=Ith) mm² 2.5 2.5
Utilization category AC2 and AC3
Switching of three-phase motors
Rated operational current Ie220V A 12 15
open and enclosed 230V A 11.5 14.5
240V A 11 14
380-400V A 9 12
415-440V A 8 11
500V A 7 9
660-690V A 5 6.5
Rated operational power of three-phase motors 220-240V kW 3 4
50-60Hz 380-440V kW 4 5.5
500-690V kW 4 5.5
Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie220V A 12 15
open and enclosed 230V A 11.5 14.5
240V A 11 14
380-400V A 9 12
415-440V A 8 11
500V A 7 9
660-690V A 5 6.5
Rated operational power of three-phase motors 220-240V kW 3 4
50-60Hz 380-440V kW 4 5.5
500-690V kW 4 5.5
H-22 Mini Motor Contactor J7KNA
Utilization category DC1
Switching of resistive load 1 pole 24V A 20 20
Time constant L/R 1ms 60V A 20 20
Rated operational current Ie110V A 5 5
220V A 0.6 0.6
3 poles in series 24V A 20 20
60V A 20 20
110V A 20 20
220V A 16 16
Utilization category DC3 and DC5
Switching of shunt motors 1 pole 24V A 20 20
and series motors 60V A 5 5
Time constant L/R 15ms 110V A 1 1
Rated operational current Ie220V A 0.15 0.15
3 poles in series 24V A 20 20
60V A 20 20
110V A 20 20
220V A 2 2
Maximum ambient temperature
Operation open °C -40 to +60 (+90)*2
enclosed °C -40 to +40
with thermal overload relay open °C -25 to +60
enclosed °C -25 to +40
Storage °C -50 to +90
Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without hazard of persons
max. fuse size gL (gG) A 40 40
Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size gL (gG) A 25 25
Contact welding not accepted
max. fuse size gL (gG) A 10 10
For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0.5 - 2.5 0.5 - 2.5
flexible mm² 0.5 - 2.5 0.5 - 2.5
flexible with multicore cable end mm² 0.5 - 1.5 0.5 - 1.5
Cables per clamp 2 2
solid or stranded AWG 18 - 14 18 - 14
Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Ty p e J7KNA-09-... J7KNA-12-...
Mini Motor Contactor J7KNA H-23
LVSG
Frequency of operations z without load 1/h 10000 10000
Contactors without thermal overload relay AC3, Ie1/h 600 700
AC4, Ie1/h 120 150
DC3, Ie1/h 600 700
Mechanical life AC operated S x 10655
DC operated S x 10615 15
Short time current 10s-current A 96 120
Power loss per pole at Ie/AC3 400V W 0.15 0.25
Resistance to shock according to IEC 68-2-27
Shock time 20ms sine-wave
AC operated NO g 5 5
NC g 5 5
DC operated NO g 8 8
NC g 6 6
*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced rated current Ie/AC1according to Ie/AC3
Mini Motor Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Ty p e J7KNA-09-... J7KNA-12-...
H-24 Mini Motor Contactor J7KNA
Mini Motor Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Ty p e
J7KNA-09...
J7KNA-12...
J7KNA-09...D(VS)
J7KNA-12...D(VS) J73KN-A...
Rated insulation voltage Ui V AC 690*1 690*1 690*1
Thermal rated current Ith to 690V
Ambient temperature 40°C A 10 10 10
60°C A 6 6 6
Power loss per pole at Ith W 0.5 0.5 0.5
Utilization category AC15
Rated operational current Ie220-240V A 3 3 3
380-415V A 2 2 2
440V A 1.6 1.6 1.6
500V A 1.2 1.2 1.2
660-690V A 0.6 0.6 0.6
Utilization category DC13
Rated operational current Ie60V A 2 2 2
110V A 0.4 0.4 0.4
220V A 0.1 0.1 0.1
Maximum ambient temperature
Operation open °C -40 to +60 (+90)*2
enclosed °C -40 to +40
Storage °C -40 to +90
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 20
For contactors with thermal overload relay the
device with the smaller admissible control fuse
(contactor or thermal overload relay)
determines the fuse size.
Power consumption of coils
AC operated inrush VA 25 - -
sealed VA 4 - 5 - -
W1.2 - -
DC operated inrush W - 2.5 -
sealed W - 2.5 -
Operation range of coils
in multiples of control voltage Us
19 - 30V DC
0.85 - 1.1 0.8 - 1.1 -
Switching time at control voltage Us ±10%*3,*4
AC operated make time ms 15 - 25 - -
release time ms 8 - 25 - -
arc duration ms 10 -15 - -
DC operated make time ms - 15 - 19 -
release time ms - 8 - 25 -
arc duration ms - 10 -15 -
Mini Motor Contactor J7KNA H-25
LVSG
Cable cross-section
all connectors solid mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible with multicore cable end mm² 0.5 - 1.5 0.5 - 1.5 0.5 - 2.5
Clamps per pole 2 2 2
solid or stranded AWG 18 - 14 18 - 14 18 - 14
*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) With reduced control voltage range 0.9 up to 1.0 x Us and with reduced thermal rated current Ith to Ie/AC15
*3) Summary switching time = release time + arc duration
*4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used
(Varistor, RC-units, Diode units).
Mini Motor Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Ty p e
J7KNA-09...
J7KNA-12...
J7KNA-09...D(VS)
J7KNA-12...D(VS) J73KN-A...
Mini Contactors for North America
Data according to UL508
Main Contacts (cULus) Ty p e J7KNA-09... J7KNA-12... J73KN-A...
Rated operational current "General Use" A 15 20 10
Rated operational power of three-phase motors 115V hp 2 -
at 60Hz (3ph) 200V hp 3 3 -
230V hp 3 3 -
460V hp 5 -
575V hp 10 -
Rated operational power of of AC motors 115V hp ½ ¾ -
at 60Hz (1ph) 200V hp 1 -
230V hp 2 -
Fuses A3030-
Suitable for use on a capability of delivering not more than rms A 5000 5000 -
V 600 600 -
Rated voltage V AC 600 600 600
Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600 A600
standard pilot duty DC Q600 Q600 Q600
H-26 Mini Motor Contactor J7KNA
Dimensions
AC and DC operated
with screw terminals
Auxiliary Contact Blocks
J7KNA-09...
J7KNA-12...
J73KN-A...
Reversing Contactors
J7KNA-09-01-W...
J7KNA-12-01-W...
J7KNA-09-01-W... + J7TKN-A
J7KNA-12-01-W...+ J7TKN-A
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J506-E2-02
Motor Contactor J7KN H-27
LVSG
Motor Contactor
J7KN
Main contactor
AC & DC operated
Integrated auxiliary contacts
Screw fixing and snap fitting (35 mm DIN rail) up to 45 kW
Range from 4 to 110 kW (AC 3, 380/415V)
Finger proof (VBG 4)
Accessories
front mounted single pole additional auxiliary contacts
(1 NO or 1 NC)
Side mounted additional auxiliary contacts (1 NO/1 NC)
Mechanical interlock
Suppressors (RC and varistor)
Pneumatic timer modules
Link modules MPCB - Motor contactor
Approved Standards
Standard Guide No (US,C)
UL NLDX, NLDX7
ICE 947-4-1
VDE 0660
EN 60947-4-1
H-28 Motor Contactor J7KN
Motor Contactor J7KN H-29
LVSG
Ordering Information
Model Number Legend
1. Motor Contactors
1) Motor Contactor
2) Rated Motor Current (AC3 400V)
10: 10A
14: 14A
18: 18A
22: 22A
24: 24A
32: 32A
40: 40A
50: 50A
62: 62A
74: 74A
85: 85A
110: 110A
150: 150A
175: 175A
200: 200A
3) Integrated auxiliary contact
10: 1NO 0NC
01: 0NO 1NC
21: 2NO 1NC
22: 2NO 2NC
: 0NO 0NC
4) Coil voltage (AC operated)
24: AC24V 50/60Hz
48: AC48V 50Hz
110: AC110V 50Hz, AC110-120V 60Hz
180: AC180-210V 50Hz, AC200-240V 60Hz
230: AC220-240V 50Hz, AC240V 60Hz
400: AC380-415V 50Hz, AC415-440V 60Hz
500: AC500-550V 50Hz, AC550-600V 60Hz
Coil voltage(DC operated)
24D: DC24V
48D: DC48V
110D: DC110V
125D: DC125V
2. Aux. Contact Modules for Motor Contactors
1) Auxiliary Contact Modules
2) B: for motor contactor (4-37kW)
C: for motor contactor (11-37kW)
3) Combination of NO/NC contacts
10: 1NO 0NC
01: 0NO 1NC
11: 1NO 1NC
4) S: side mounting
: front mounting
3. Accessories for Motor Contactors
(Link Modules MPCB - Motor Contactor)
1) Accessories for Motor Contactors
2) VD: Link module type
HU: DIN-rail adapter type
3) 12: for motor contactor (4 - 7.5kW)
25: for motor contactor (11 - 15kW)
4. Accessories for Motor Contactors
(Pneumatic Timers)
1) Accessories for Motor Contactors
2) B: Motor Contactor (4-11kW)
3) TP: Pneumatic Timer
4) 40: 40 sec
180: 180 sec
5) DA: ON-delayed
IA: OFF-delayed
5. Accessories for Motor Contactors (Mechanical Interlock)
1) Accessories for Motor Contactors
2) B: Motor Contactor (4-18.5kW)
C: Motor Contactor (11-37kW)
D: Motor Contactor (45-55kW)
3) ML: Mechanical Interlock
6. Accessories for Motor Contactors (RC Suppressor units)
1) Accessories for Motor Contactors
2) A: for Mini Motor Contactor and Motor Contactor
(4-18.5kW)
(between DIN-rail and Contactor)
B: for Mini Motor Contactor and Motor Contactor
(4-55kW)
C: for Motor Contactor (4-37kW) to snap on the contactor
3) RC: RC-surge suppressors
4) 48: 24 - 48 VAC/DC (A+B type)
230: 110 - 230 VAC/DC (A+B type)
400: 250 - 415 VAC/DC (A+B type)
24: 12 - 48 VAC/DC (C type)
110: 48 - 127 VAC/DC (C type)
230: 110 - 250 VAC/DC (C type)
7. Accessories for Motor Contactors (Varistor units)
1) Accessories for Motor Contactors
2) A: for Motor Contactor (4-11kW) to snap on
to coil terminals
B: for Motor Contactor (4-37kW) to snap on to contactor
3) VG: Varistor Suppressors
4) 230: 110-230VAC/DC
400: 250-415VAC/DC
J7KN-###-##-####
123
4
J73KN-#-##-#
123
4
J74KN-##-##
123
J74KN-#-## ### ##
123
45
J74KN-#-##
123
J74KN-#-## ###
123
4
J74KN-#-## ###
123
4
H-30 Motor Contactor J7KN
List of Models
Contactors 3-pole
Up to 210A AC3
Up to 350A AC1
DIN-rail mounting up to AC3 74A
International Approvals
Data according to IEC 947 /
EN 60947
Ratings
AC3 400V Motor 10A 14A 18A 22A 24A 32A 40A 50A 62A 74A
380-400V 4kW 5,5kW 7,5kW 11kW 11kW 15kW 18,5kW 22kW 30kW 37kW
660-690V 5,5kW 7,5kW 10kW 10kW 15kW 18,5kW 18,5kW 30kW 37kW 45kW
AC1 690V at 40°C 25A 25A 32A 32A 50A 65A 80A 110A 120A 130A
Type J7KN-
10-10
J7KN-
14-10
J7KN-
18-10
J7KN-
22-10
J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
Auxiliary contacts 1NO1NO1NO1NO------
Type J7KN-
10-01
J7KN-
14-01
J7KN-
18-01
J7KN-
22-01
------
Auxiliary contacts 1NC1NC1NC1NC------
Cable cross-section
Solid mm20,75 - 6 1,5 - 25 4 - 50
Flexible mm21 - 4 2,5 - 16 10 - 35
Cables per clamp 2 1 + 1 1 + 1
Auxiliary contact
Ith 40°C A 16 - -
AC15 230V A 12 - -
400V A 4 - -
Power consumption of coils
Inrush VA 33 - 45 90 - 115 140 - 165
Hold VA 7 - 10 9 - 13 13 - 18
Operation range of coils 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1
Mounting 35mm DIN-rail or base
Additional aux. contact blocks
Front mounting Type J73KN-B-10 J73KN-B-01
contacts 1NO 1NC
f. low level switching f. low level switching
maximal 4 J73KN-B..
Additional aux. contact blocks
Side mounting Type---- J73KN-C-11S
contacts 1NO+1NC
f. low level switching
max. 2 J73KN-C-11S
Overload Relay (thermal)
Single phase protection
Temperature compensation
Trip and alarm contacts
Type J7TKN-B J7TKN-A J7TKN-C J7TKN-D
Setting Ranges Setting Ranges Setting Ranges
0,12 - 0,18A 1,8 - 2,7A 28 - 42A 20 - 28A
0,18 - 0,27A 2,7 - 4A 28 - 42A
0,27 - 0,4A 4 - 6A 40 - 52A
0,4 - 0,6A 6 - 9A 52 - 65A
0,6 - 0,9A 8 - 11A 60 - 74A
0,8 - 1,2A 10 - 14A
1,2 - 1,8A 13 - 18A
17 - (23)24A (22)23 - (30)32A
Motor Contactor J7KN H-31
LVSG
Ratings
AC3 400V Motor 85A 110A 150A 175A 210A
380-400V 45kW 55kW 75kW 90kW 110kW
660-690V 55kW 55kW 75kW 110kW 132kW
AC1 690V at 40°C 150A 170A 200A 250A 350A
Type J7KN-
85-22
J7KN-
110-22
J7KN-
150-11
J7KN-
175-11
J7KN-200-
22
Auxiliary contacts 2NO+2NC 2NO+2NC 1NO+1NC 1NO+1NC 2NO+2NC
Type -----
Auxiliary contacts -----
Cable cross-section
Solid mm210 - 70 10 - 70 busbar busbar busbar
Flexible mm216 - 50 16 - 50 18x5 18x5 22x4
Cables per clamp 1 1 1 1 1
Auxiliary contact
Ith 40°C A 16 10
AC15 230V A 12 3
400V A 6 2
Power consumption of coils
Inrush VA 350 - 420 550 550 1100
hold VA 23 - 29 130 130 66
Operation range of coils 0,85 - 1,1 0,85 - 1,1
Mounting base
Additional aux. contact blocks
Front mounting Type
contacts
Additional aux. contact blocks
Side mounting Type - - - - -
contacts
Overload Relay (thermal)
Single phase protection
Temperature compensation
Trip and alarm contacts
Type J7TKN-E J7TKN-F
Setting Ranges Setting Ranges
60 - 90A 100 - 150A
80 - 120A 140 - 220A
Busbar Sets
J74TK-SU-175, J74TK-SU-200
H-32 Motor Contactor J7KN
Contactors 3-pole
AC Operated
Ratings Rated
Current
Aux. Contacts Type Pack Weight
AC2, AC3 AC1 Built-in Additional
380V
400V
415V
kW
500V
kW
660V
690V
kW
690V
ANO NC
see
page 34
Ty p e
Coil Voltage*1
24 24V 50/60Hz
110 110V 50Hz
230 220-240V 50Hz
*1) Coil voltage range and other coil voltages see page 37
pcs. kg/pc.
45.5 5.5 25 1 - max. 4
J73KN-B
J7KN-10-10#### 1 0.23
45.5 5.5 25 - 1 J7KN-10-01#### 1 0.23
5.5 7.5 7.5 25 1 - J7KN-14-10#### 1 0.23
5.5 7.5 7.5 25 - 1 J7KN-14-01#### 1 0.23
7.5 10 10 32 1 - J7KN-18-10#### 1 0.23
7.5 10 10 32 - 1 J7KN-18-01#### 1 0.23
11 10 10 32 1 - J7KN-22-10#### 1 0.23
11 10 10 32 - 1 J7KN-22-01#### 1 0.23
11 15 15 50 - - max. 4
J73KN-B +
2 J73KN-
C-11S
J7KN-24#### 1 0.48
15 18.5 18.5 65 - - J7KN-32#### 1 0.48
18.5 18.5 18.5 80 - - J7KN-40#### 1 0.48
22 30 30 110 - - max. 4
J73KN-B +
2 J73KN-
C11S
J7KN-50#### 1 0.85
30 37 37 120 - - J7KN-62#### 1 0.85
37 45 45 130 - - J7KN-74#### 1 0.85
Ratings Rated
Current
Aux. Contacts Type Pack Weight
AC2, AC3 AC1 Built-in
380V
415V
kW
500V
kW
660V
690V
kW
690V
ANO NC
Coil Voltage*1
230 220-230V 50Hz
400 380-400V 50Hz pcs. kg/pc.
45 55 55 150 2 2 J7KN-85-22#### 11.8
55 75 55 170 2 2 J7KN-110-22#### 11.9
75 75 75 200 1 1 J7KN-150-11#### 15
90 90 90 250 1 1 J7KN-175-11#### 15
110 132 132 350 2 2 J7KN-200-22#### 17.3
Motor Contactor J7KN H-33
LVSG
Contactors 3-pole
DC Operated
Type Coil voltage Aux. Contacts Weight Accept Overload
Relay
Busbar Set for
Overload Relay
Wiring Diagram
Built-in Additional*1)
*1) Only 3 additional Aux. Contacts are possible! (See also the wiring diagrammms coil circuit DC operated page 36)
page 57 page 59
24
60
110
220
24V DC
60V DC
110V DC
220V DC NO NC Ty p e kg/pc. Ty p e Ty p e
Coil Circuits see page 36
Terminal Markings
J7KN-10-10####D1- max. 3
J73KN-B
0.25 J7TKN-B
J7TKN-A
--10
J7KN-10-01####D- 1 0.25 -
J7KN-14-10####D1 - 0.25 -
J7KN-14-01####D- 1 0.25 -
J7KN-18-10####D1 - 0.25 - -01
J7KN-18-01####D- 1 0.25 -
J7KN-22-10####D1 - 0.25 -
J7KN-22-01####D- 1 0.25 -
J7KN-24####D--max. 3
J73KN-B
+
2 J73KN-
C-11S
0.55 J7TKN-B
J7TKN-C
--11
-- -
J7KN-32####D- - 0.55 -
-- -
J7KN-40####D- - 0.55 - -21
-- -
J7KN-50####D
J7KN-62####D
J7KN-74####D
--max. 3
J73KN-B
+
2 J73KN-
C-11S
0.9 J7TKN-D
-- 0.9
21 1.6
Type Coil voltage Aux. Contacts Weight Accept Overload
Relay
Busbar Set for
Overload Relay
-22
Built-in page H-59 page H-59
110
220
110V DC
220V DC NO NC kg/pc. Ty p e Ty p e
J7KN-85-21####D2 1 - 1.8 J7TKN-E
J7KN-110-21####D21- 1.9
J73TK-SU-175
J7TKN-F J73TK-SU-200
H-34 Motor Contactor J7KN
Contactors 4-pole
AC Operated
Auxiliary Contact Blocks for contactors J7KN-10... to -74... type J73KN for low level switching*1
Auxiliary Contact Blocks for contactors J7KN-24... to -74... type J73KN for low level switching*1
Pneumatic Timer for contactors J7KN-10... to -22...
Ratings Rated
Current
Aux. Contacts Type Pack Weight
AC2,
AC3
AC1 AC1
Built-in Additional
see
below
Ty p e
380V
400V
415V
kW
400V
kW
690V
ANO NC
Coil Voltage*1
24 24V 50/60Hz
110 110V 50Hz
230 220-240V 50Hz
*1) Coil voltage range and other coil voltages see page 37
pcs. kg/pc.
417.5 25 - - max. 4
J73KN-B
J7KN-10-4#### 1 0.22
1. suitable according to DIN 19240 (test ratings 17V DC, 5mA)
Technical data see page 51
Front mounting Rated Operational Current Contacts Ty p e Pack Weight
AC15
230V
AC15
400V
AC1
690V
EM LB
A A A NO NC pcs. kg/pc.
3 2 10 1 - - - J73KN-B-10 10 0.02
3 2 10 - 1 - - J73KN-B-01 10 0.02
Side mounting Rated Operational Current Contacts Ty p e Pack Weight
AC15
230V
AC15
400V
AC1
690V
A A A for side mounting NO NC pcs. kg/pc.
3 2 10 max. 2 1 1 J73KN-C-11S 10 0.02
Function Time range Contacts Ty p e Pack Weight
spcs. kg/pc.
On-delay 0.1 - 40 1 1 - - J74KN-B-TP40DA 1 0.09
On-delay 10 - 180 1 1 - - J74KN-B-TP180DA 1 0.09
Off-delay 0.1 - 40 - - 1 1 J74KN-B-TP40IA 1 0.09
Off-delay 10 - 180 - - 1 1 J74KN-B-TP180IA 1 0.09
NO NC
NO NC
Motor Contactor J7KN H-35
LVSG
Mechanical Interlocks
Suppressor Units
Interlocks contactor with contactor Mounting Ty p e Pack Weight
Ty p e +Ty p e pcs. kg/pc.
J7KN10 - J7KN40 + J7KN10 - J7KN40 horizontal J74KN-B-ML 1 0.006
J7KN24 - J7KN74 + J7KN24 - J7KN74 horizontal J74KN-C-ML 1 0.010
J7KN85 - J7KN110 + J7KN85 - J7KN110 horizontal J74KN-D-ML 1 0.076
Voltage Range Mounting Ty p e Pack Weight
Vpcs. kg/pc.
Varistor for contactors J7KN-10 to J7KN-22
110 - 230V AC/DC to snap on to coil terminals J74KN-A-VG230 10 0.01
250 - 415V AC/DC to snap on to coil terminals J74KN-A-VG400 10 0.01
Varistor for contactors J7KN-10 to J7KN-74
110 - 230V AC/DC to snap on the contactor J74KN-B-VG230 10 0.02
250 - 415V AC/DC to snap on the contactor J74KN-B-VG400 10 0.02
RC-unit for contactors J7KN-10 to J7KN-40, J7KNA
110 - 230V AC/DC between DIN-rail and contactor J74KN-A-RC230 1 0.036
RC-units for contactors J7KN-10 to J7KN-110
24 - 48V AC/DC universal (fixing band, adhesive strip) J74KN-B-RC48 5 0.02
110 - 230V AC/DC universal (fixing band, adhesive strip) J74KN-B-RC230 5 0.02
250 - 415V AC universal (fixing band, adhesive strip) J74KN-B-RC400 5 0.02
RC-units for contactors J7KN-10 to J7KN-74
12 - 48V AC (50/60Hz) & DC to snap on the contactor J74KN-C-RC24 10 0.02
48 - 127V AC (50/60Hz) & DC to snap on the contactor J74KN-C-RC110 10 0.036
110 - 250V AC (50/60Hz) & DC to snap on the contactor J74KN-C-RC230 10 0.036
H-36 Motor Contactor J7KN
Wiring Diagrams Coil Circuit
AC operated DC operated
with double winding coil*1
*1) Only 3 additional Aux. Contacts are possible! (See also
page 33)
J7KN-10...
to
J7KN-175...
J7KN-10...D
to
J7KN-22...D
J7KN-200... J7KN-24...D
to
J7KN-74...D
J7KN-85-...D
to
J7KN-110...D
Motor Contactor J7KN H-37
LVSG
Specifications
Coil Voltages
Type-suffix for contactor types J7KN-10... to J7KN-74...
Type-suffix for contactor types J7KN-85... to J7KN-110...
Type-suffix for contactor types J7KN-150... to J7KN-200...
Suffix
to contactor
type e.g.
Voltage Marking Rated Control Voltage Us
at the coil range for
50Hz 60Hz
J7KN-10-10-24 for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
24 24 24 22 24 24 27
48 48 47 52 52 58
110 110 110-120 100 110 110 122
180 180-210 200-240 180 210 200 240
230 220-240 240 220 240 240 264
400 380-415 415-440 380 415 415 460
500 500-550 550-600 500 550 550 600
Standard voltages in bold type letter
Suffix
to contactor
type e.g.
Voltage Marking Rated Control Voltage Us
at the coil range for
50Hz 60Hz
J7KN-85-22-24 for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
24 24 24 27 29 32
48 48 60 47 52 56 62
110 110-120 110 122 132 146
180 180-200 208-240 180 200 208 240
230 220-240 277 220 240 264 288
400 380-415 460-480 380 415 455 498
500 500-550 600-660 500 550 600 660
Standard voltages in bold type letter
Suffix Voltage Marking Rated Control Voltage Us
to contactor
type e.g.
at the coil range for
50Hz 60Hz
J7KN-150-110 for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
24 24 24 24 - -
48 48 48 48 - -
110 110 110 110 110 110 110
180 180 220 180 180 220 220
230 220-230 220 220 230 220 220
240 240 240 240 240 240 240
400 380-400 380 400 - -
440 440 - - 440 440
Standard voltages in bold type letter
H-38 Motor Contactor J7KN
Engineering data and characteristics
Approximate Values for three-phase Motors
Motor Full Load Currents
Approximate values of motor F.L.C. and minimum „slow blow“ respectively „gL“ short-circuit fuse
The motor F.L.C. be valid for standard internal and surface cooled three-pole
motors with 1500 min-1. The fuses values be valid for the motor F.L.C. shown in
the table and D.O.L.-start: starting current max. 6x motor F.L.C., starting time
max. 5s; star-delta-start: starting current max. 2x motor F.L.C., starting time
max. 15s. For motors with higher F.L.C., higher starting current and / or longer
starting time, larger short-circuit fuses are required.
The maximum admissible value is dependent on the switchgear
respectively thermal overload relay.
Motor rating 220-230V Motor 240V Motor 380-400V Motor 415V Motor 500V Motor 660-690V Motor
Range according to BS for 415V Value of fusing at
motor start
Value of fusing at
motor start
Value of fusing at
motor start
Value of fusing at
motor start
Value of fusing at
motor start
Value of fusing at
motor start
kW PS~hp hp cosϕ%
F. L . C .
A
D.O.L.
A
YD
A
F. L . C .
A
D.O.L.
A
YD
A
F. L . C .
A
D.O.L.
A
YD
A
F. L . C .
A
D.O.L.
A
YD
A
F. L . C .
A
D.O.L.
A
YD
A
F. L . C .
A
D.O.L.
A
YD
A
0.06 0.08 - 0.7 59 0.38 1 1 0.35 1 1 0.22 11- - -0.1611- - -
0.09 0.12 - 0.7 60 0.55 2 2 0.5 2 2 0.33 11- - -0.2411- - -
0.12 0.16 - 0.7 61 0.76 2 2 0.68 2 2 0.42 22- - -0.3311- - -
0.18 0.24 - 0.7 61 1.1 2 2 1 2 2 0.64 22- - -0.4611- - -
0.25 0.34 - 0.7 62 1.4 4 2 1.38 4 2 0.88 22- - -0.5922- - -
0.37 0.5 - 0.72 64 2.1 4 4 1.93 4 4 1.22 42- - -0.85220.722
0.55 0.75 - 0.75 69 2.7 4 4 2.3 4 4 1.5 42- - -1.2420.922
0.75110.8743.3643.164
2442 441.48421.122
1.1 1.5 1.5 0.83 77 4.9 10 6 4.1 6 6 2.6 442.5442.1441.542
1.5 2 2 0.83 78 6.2 10 10 5.6 10 10 3.5 643.5642.6442 44
2.2 3 3 0.83 81 8.7 16 10 7.9 16 10 510 6 5 10 6 3.8 6 6 2.9 6 4
2.5 3.4 - 0.83 81 9.8 16 16 8.9 16 10 5.7 1010---4.366---
3440.848111.6201610.62016
6.6 16 10 6.5 16 10 5.1 10 10 3.5 6 4
3.7550.848214.22520132516
8.2 16 10 7.5 16 10 6.2 16 10 - - -
4 5.5 - 0.84 82 15.3 25 20 14 25 20 8.5 16 10 - - - 6.5 16 10 4.9 10 6
5.5 7.5 7.5 0.85 83 20.6 35 25 18.9 35 25 11.5 20 16 11 20 16 8.9 16 10 6.7 16 10
7.51010 0.868527.4353524.83535
15.5 25 20 14 25 16 11.9 20 16 9 16 10
8 11 - 0.86 85 28.8 50 35 26.4 35 35 16.7 25 20 - - - 12.7 20 16 - - -
11 15 15 0.86 87 39.2 63 50 35.3 50 50 22 35 25 21 35 25 16.7 25 20 13 25 16
12.5 17 - 0.86 87 43.8 63 50 40.2 63 50 25 35 35 - - - 19 35 25 - - -
15 20 20 0.86 87 52.6 80 63 48.2 80 63 30 50 35 28 35 35 22.5 35 25 17.5 25 20
18.5 25 25 0.86 88 64.9 100 80 58.7 80 63 37 63 50 35 50 50 28.5 50 35 21 35 25
20 27 - 0.86 88 69.3 100 80 63.4 80 80 40 63 50 - - - 30.6 50 35 - - -
22 30 30 0.87 89 75.2 100 80 68 100 80 44 63 50 40 63 50 33 50 50 25 35 35
25 34 - 0.87 89 84.4 125 100 77.2 100 100 50 80 63 - - - 38 63 50 - - -
30 40 40 0.87 90 101 125 125 92.7 125 100 60 80 63 55 80 63 44 63 50 33 50 35
37 50 50 0.87 90 124 160 160 114 160 125 72 100 80 66 100 80 54 80 63 42 63 50
40 54 - 0.87 90 134 160 160 123 160 160 79 100 100 - - - 60 80 63 - - -
45 60 60 0.88 91 150 200 160 136 200 160 85 125 100 80 100 100 64.5 100 80 49 63 63
51 70 - 0.88 91 168 200 200 154 200 200 97 125 100 - - - 73.7 100 80 - - -
55 75 - 0.88 91 181 250 200 166 200 200 105 160 125 - - - 79 125 100 60 80 63
59 80 80 0.88 91 194 250 250 178 250 200 112 160 125 105 160 125 85.3 125 100 - - -
75 100 100 0.88 91 245 315 250 226 315 250 140 200 160 135 200 160 106 160 125 82 125 100
90 125 125 0.88 92 292 400 315 268 315 315 170 250 200 165 200 200 128 160 160 98 125 125
110 150 150 0.88 92 358 500 400 327 400 400 205 250 250 200 250 250 156 200 200 118 160 125
129 175 175 0.88 92 420 500 500 384 500 400 242 315 250 230 315 250 184 250 200 - - -
132 180 - 0.88 92 425 500 500 393 500 500 245 315 250 - - - 186 250 200 140 200 160
147 200 200 0.88 93 472 630 630 432 630 500 273 315 315 260 315 315 207 250 250 - - -
160 220 - 0.88 93 502 630 630 471 630 630 295 400 315 - - - 220 315 250 170 200 200
184 250 250 0.88 93 590 800 630 541 630 630 340 400 400 325 400 400 259 315 315 - - -
200 270 - 0.88 93 626 800 800 589 800 630 370 500 400 - - - 278 315 315 215 250 250
220 300 300 0.88 93 700 1000 800 647 800 800 408 500 500 385 500 400 310 400 400 - - -
250 340 - 0.88 93 803 1000 1000 736 1000 800 460 630 500 - - - 353 500 400 268 315 315
257 350 350 0.88 93 826 1000 1000 756 1000 800 475 630 630 450 630 500 363 500 400 - - -
295 400 400 0.88 93 948 1250 1000 868 1000 1000 546 800 630 500 630 630 416 500 500 - - -
315 430 - 0.88 93 990 1250 1250 927 1250 1000 580 800 630 - - - 445 630 500 337 400 400
355 483 - 0.89 95 - - - - - - 636 800 800 - - - 483 630 630 366 500 400
400 545 - 0.89 96 - - - - - - 710 1000 800 - - - 538 630 630 410 500 500
Motor Contactor J7KN H-39
LVSG
Approximate values of motor F.L.C. according to CSA and UL
Motor
rating
Motor F.L.C. at 110-120V Motor F.L.C. at 220-240V*1
*1) Determine the motor current for 200V and 208V by increasing the values for 220-240V at 200V about 15% and for 208V about 10%.
Motor F.L.C. at 440-480V Motor F.L.C. at 550-600V
1-phase 2-phase 3-phase 1-phase 2-phase 3-phase 1-phase 2-phase 3-phase 1-phase 2-phase 3-phase
hp A A A A A A A A A A A A
½ 9.8 4.0 4.4 4.9 2.0 2.2 2.5 1.0 1.1 2.0 0.8 0.9
¾ 13.8 4.8 6.4 6.9 2.4 3.2 3.5 1.2 1.6 2.8 1.0 1.3
1 16.0 6.4 8.4 8.0 3.2 4.2 4.0 1.6 2.1 3.2 1.3 1.7
20.0 9.0 12.0 10.0 4.5 6.0 5.0 2.3 3.0 4.0 1.8 2.4
2 24.0 11.8 13.6 12.0 5.9 6.8 6.0 3.0 3.4 4.8 2.4 2.7
3 34.0 16.6 19.2 17.0 8.3 9.6 8.5 4.2 4.8 6.8 3.3 3.9
5 56.0 26.4 30.4 28.0 13.2 15.2 14.0 6.6 7.6 11.2 5.3 6.1
80.0 38.0 44.0 40.0 19.0 22.0 21.0 9.0 11.0 16.0 8.0 9.0
10 100.0 48.0 56.0 50.0 24.0 28.0 26.0 12.0 14.0 20.0 10.0 11.0
15 135.0 72.0 84.0 68.0 36.0 42.0 34.0 18.0 21.0 27.0 14.0 17.0
20 - 94.0 108.0 88.0 47.0 54.0 44.0 23.0 27.0 35.0 19.0 22.0
25 - 118.0 136.0 110.0 59.0 68.0 55.0 29.0 34.0 44.0 24.0 27.0
30 - 138.0 160.0 136.0 69.0 80.0 68.0 35.0 40.0 54.0 28.0 32.0
40 - 180.0 208.0 176.0 90.0 104.0 88.0 45.0 52.0 70.0 36.0 41.0
50 - 226.0 260.0 216.0 113.0 130.0 108.0 56.0 65.0 86.0 45.0 52.0
60 - - - - 133.0 145.0 - 67.0 77.0 - 53.0 62.0
75 - - - - 166.0 192.0 - 83.0 96.0 - 66.0 77.0
100 - - - - 218.0 248.0 - 109.0 124.0 - 87.0 99.0
125-----312.0 - 135.0 156.0 - 108.0 125.0
150-----360.0 - 156.0 180.0 - 125.0 144.0
200-----480.0 - 208.0 240.0 - 167.0 192.0
250-----602.0 - - 302.0 - - 242.0
300--------361.0--289.0
350--------414.0--336.0
400--------477.0--382.0
500--------590.0--472.0
H-40 Motor Contactor J7KN
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type J7KN-10 J7KN-14 J7KN-18 J7KN-22 J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
Rated insulation voltage Ui
*1 V AC 690 690 690 690 690 690 690 690 690 690
Making capacity Ieff at Ue = 690V AC A 200 200 200 200 400 500 500 700 900 900
Breaking capacity Ieff 400V AC A 180 180 200 200 380 400 400 600 800 800
J7KN-10 to J7KN-22 cosϕ = 0,65 500V AC A 150 150 180 180 300 370 370 500 700 700
J7KN-24 to J7KN-72 cosϕ = 0,35 690V AC A 100 100 150 150 260 340 340 400 500 500
1000V ACA---------
Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open A25253232506580110120130
Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1
220V kW 9,5 9,5 12,2 12,2 19,0 24,7 30,4 41,9 45,7 49,5
230V kW 9,9 9,9 12,7 12,7 19,9 25,9 31,8 43,8 47,7 51,7
240V kW 10,4 10,4 13,3 13,3 20,8 27,0 33,2 45,7 49,8 54,0
380V kW 16,4 16,4 21,0 21,0 32,9 42,7 52,6 72,3 78,9 85,5
400V kW 17,3 17,3 22,1 22,1 34,6 45,0 55,4 76,1 83,0 90,0
415V kW 17,9 17,9 23,0 23,0 35,9 46,7 57,4 79,0 86,2 93,3
440V kW 19,0 19,0 24,4 24,4 38,1 49,5 60,9 83,7 91,3 99,0
500V kW 21,6 21,6 27,7 27,7 43,3 56,2 69,2 95,2 103,8 112,5
660V kW 28,5 28,5 36,5 36,5 57,1 74,2 91,3 125,6 137,0 148,4
690V kW 29,8 29,8 38,2 38,2 59,7 77,6 95,5 131,3 143,2 155,2
1000VkW----------
Rated operational current Ie (=Ithe) at 60°C, enclosed A 25 25 32 32 40 55 65 90 100 110
Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1
220V kW 9,5 9,5 12,2 12,2 15,2 20,9 24,7 34,3 38,1 41,9
230V kW 9,9 9,9 12,7 12,7 15,9 21,9 25,9 35,8 39,8 43,8
240V kW 10,4 10,4 13,3 13,3 16,6 22,8 27,0 37,4 41,5 45,7
380V kW 16,4 16,4 21,0 21,0 26,3 36,2 42,7 59,2 65,7 72,3
400V kW 17,3 17,3 22,1 22,1 27,7 38,1 45,0 62,3 69,2 76,1
415V kW 17,9 17,9 23,0 23,0 28,7 39,5 46,7 64,6 71,8 79,0
440V kW 19,0 19,0 24,4 24,4 30,4 41,9 49,5 68,5 76,1 83,7
500V kW 21,6 21,6 27,7 27,7 34,6 47,6 56,2 77,9 86,5 95,2
660V kW 28,5 28,5 36,5 36,5 45,7 62,8 74,2 102,8 114,2 125,6
690V kW 29,8 29,8 38,2 38,2 47,7 65,7 77,6 107,4 119,4 131,3
1000VkW----------
Minimum cross-section of conductor
at load with Ie (=Ith)
mm² 4 4 6 6 10 16 25 35 50 50
Utilization category AC2 and AC3
Switching of three-phase motors
Rated operational current Ie
open and enclosed
220VA121518222430405063 74
230V A 11,5 14,5 18 22 24 30 40 50 62 74
240VA11141822243240506274
380-400V A 10 14 18 22 24 32 40 50 62 74
415V A 9 14 18 22 23 30 40 50 62 74
440V A 9 14 18 22 23 30 40 50 62 74
500V A 7 9 9 9 17,5 21 21 33 42 42
660-690V A 6,5 8,5 8,5 8,5 17 20 20 31 40 40
1000VA--- ------
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 3 4 5 6 6 8,5 11 12,5 18,5 22
240V kW 3 4 5 7 7 9 11,5 13,5 19 23
380-400V kW 4 5,5 7,5 11 11 15 18,5 22 30 37
415VkW4,56 8,512121620243340
440VkW4,56 8,512121620243340
500V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 45
660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 45
1000VkW--- ------
Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie (=Ith)
open and enclosed
220V A121518182430405063 63
230V A 11,5 14,5 18 18 24 30 40 50 62 62
240V A11141818243240506262
380-400VA10141818243240506262
415V A 9 14 18 18 23 30 37 45 60 60
440V A 9 14 18 18 23 30 37 45 55 55
500V A 9 12 16 16 17,5 21 21 33 42 42
660V A7 9 9 9 172020314040
690V A6,58,58,58,5172020314040
1000VA--- ------
Motor Contactor J7KN H-41
LVSG
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 3 4 5 5 6 8,5 11 12,5 18,5 18,5
240VkW34557911,513,51919
380-400V kW 4 5,5 7,5 7,5 11 15 18,5 22 30 30
415V kW 4,5 6 8,5 8,5 12 16 20 24 33 33
440V kW 4,5 6 8,5 8,5 12 16 20 24 33 33
500V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 37
660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 37
1000VkW--- ------
Utilization category AC 5a
Switching of gas discharge lamps
Rated operational current Ie per pole at 220/230V
Fluorescent lamps,
uncompensated and serial compensated A 20 20 25 25 40 52 64 88 96 104
parallel compensated A 7 9 9 9 18 22 22 30 40 45
dual-connection A 22,5 22,5 28 28 45 58 72 98 108 117
Metal halide lamps*2,
uncompensated A12151919303948667278
parallel compensated A 7 9 9 9 18 22 22 30 40 45
Mercury-vapour lamps*3,
uncompensated A 22,5 25 28 28 45 58 72 99 108 117
parallel compensated A 7 9 9 9 18 22 22 30 40 45
Mixed light lamps*4 A202025254052648896104
Utilization category AC5b
Switching of incandescent lamps*5
Rated operational current Ie per pole at 220/230V A 12,5 12,5 12,5 12,5 25 31 31 43 56 56
Utilization category AC6a
Transformer primary switching
at inrush n30303030303030303030
Rated operational current Ie400V A 4,5 5,5 7,5 7,5 10,5 13,5 13,5 20 27 33
Rated operational power
dependent on inrush n
220-230V kVA 1,8 2,2 3 3 4,2 5,4 5,4 8 10,7 13
240V kVA 1,9 2,3 3,1 3,1 4,3 5,6 5,6 8,3 11,2 13,5
380-400V kVA 3,1 3,8 5,2 5,2 7,3 9,3 9,3 13,5 18,5 22,5
For different inrush-factors x
use the following formula:
Px=Pn*(n/x)
415-440V kVA 3,4 4,2 5,7 5,7 8 10,2 10,2 15 20,5 25
500V kVA 3,9 4,8 6,5 6,5 9 11,5 11,5 17 23 28
660-690V kVA 5,4 6,5 9 9 12,5 16 16 24 32 39
Utilization category AC6b
Switching of three-phase capacitor banks
Maximum inrush current (peak val-
ue) as multiple k of the capacitor
rated current
k35252020252525252520
Rated operational current Ie500V A 8 12 15,5 15,5 23 32 32 45 60 70
Rated operational power
(sinϕ→1)
220-230V kVAr 3 4,5 6 6 8,5 12 12 17 24 28
240V kVAr 3,5 5 6,5 6,5 9,5 13 13 18,5 25 29
380-400V kVAr 5 7,5 10 10 15 20 20 29 39 46
For different multiples x
use the following formula:
Px=Pk*(k/x)
415-440V kVAr 5,5 8 11 11 16 22 22 32 43 50
500V kVAr7 10131320262639 5058
660-690V kVAr 7 10 13 13 20 26 26 40 50 58
Switching of detuned capacitors
Rated operational current Ie690V A 8 13 18 20 28 36 42 48 72 105 1)
Rated operational power 220-230V kVAr 2,9 5 7 7,5 11 14 16 20 28 33
240V kVAr 3,1 5,4 7 8 11 14 17 20 28 36
380-400V kVAr 5 9 12,5 13 20 25 27,5 33,3 50 75 1)
415-440V kVAr 5,5 9,5 13 14 22 27 30 36 53 75 1)
500V kVAr6 111517253036406075
660-690V kVAr 8 15 20 22 33 41 48 55 82 100
Utilization category DC1
Switching of resistive load
Time constant L/R 1ms
Rated operational current Ie1 pole24V A 20 25 32 32 50 65 80 110 120 130
60V A 20 25 32 32 50 65 80 110 120 130
110V A 6 6 6 6 10 10 10 12 12 12
220V A 0,8 0,8 0,8 0,8 1,4 1,4 1,4 1,4 1,4 1,4
3 poles in series 24V A 20 25 32 32 50 65 80 110 120 130
60V A 20 25 32 32 50 65 80 110 120 130
110V A 20 25 32 32 50 65 80 110 120 130
220VA16202020303535638080
Main Contacts Type J7KN-10 J7KN-14 J7KN-18 J7KN-22 J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
H-42 Motor Contactor J7KN
Utilization category DC3 and DC5
Switching of shunt motors and series motors
Time constant L/R 15ms
Rated operational current Ie1 pole24V A 20 25 32 32 50 65 80 110 120 130
60V A 6 6 6 6 30 30 30 60 60 60
110V A 1,2 1,2 1,2 1,2 1,8 1,8 1,8 1,8 1,8 1,8
220V A 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,25 0,25 0,25
3 poles in series 24V A 20 25 32 32 50 65 80 110 120 130
60V A 20 25 32 32 40 40 40 80 80 80
110VA20202020404040808080
220V A 2,5 2,5 2,5 2,5 4 4 4 5 5 5
Maximum ambient temperature
Operation open °C -40 to +60 (+90)*6
enclosed °C -40 to +40
with thermal overload relay open °C -25 to +60
enclosed °C -25 to +40
Storage °C -50 to +90
Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without
hazard of persons
max. fuse size gL (gG) A 63 63 63 63 80 80 80 160 160 160
Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size gL (gG) A 25 35 35 35 50 50 50 100 125 125
Contact welding not accepted
max. fuse size gL (gG) A 16 16 16 16 25 35 35 50 63 63
For contactors with thermal overload relay the device with
the smaller admissible backup fuse (contactor or thermal
overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1 - 4 2,5 - 16 10 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
Cables per clamp 2 1 1
solid or stranded mm² 6+(1-6) / 4+(0,75-4) 16+(2,5-6) / 10+(4-10) 50+4 / 35+6 / 25+(6-16)
2,5+(0,75-2,5) / 1,5+(0,75-1,5) 6+(4-6) / 4+(2,5-4) 16+(6-16) / 10+(6-16)
flexible mm² 6+(1,5-6) / 4+(1-4) 16+(2,5-6) / 10+(4-10) 50+(4-10) / 35+(4-16)
2,5+(0,75-2,5) / 1,5+(0,75-1,5) 6+(4-6) / 4+(2,5-4) 25+(4-25) / 16+(4-16)
Cables per clamp 2 2 2
main connector solid AWG 18 - 10 16 - 10 12 - 10
flexible AWG 18 - 10 14 - 4 10 - 0
Cables per clamp 2 1 1
solid AWG 10+(16-10) / 12+(18-12) 10+(16-10) / 12+(18-12) 10+(12-10) / 12+12
14+(18-14) / 16+(18-16) 14+(18-14) / 16+(18-16)
flexible AWG 10+(14-10) / 12+(18-12) 4+(18-12) / 6+(18-8) 1+(12-10) / 2+(8-12)
14+(18-14) / 16+(18-16) 8+(18-8) / 10+(18-12) 3+(12-8) / 4+(10-6)
Cables per clamp 2 2 2
Frequency of operations z
Contactors without thermal overload relay
without load 1/h 10000 10000 10000 10000 7000 7000 7000 7000 7000 7000
AC3, Ie1/h 600 600 600 600 600 600 600 400 400 400
AC4, Ie1/h 120 120 120 120 120 120 120 120 120 120
DC3, Ie1/h 600 600 600 600 600 600 600 400 400 400
Mechanical life
AC operated S x 10610 10 10 10 10 10 10 10 10 10
DC operated S x 10610 10 10 10 10 10 10 10 10 10
Short time current 10s-current A 96 120 144 176 184 240 296 360 504 592
Power loss per pole at Ie/AC3 400V W 0,21 0,35 0,5 0,75 0,7 1,3 2 2,2 3,9 5,5
Resistance to shock acc. to IEC 68-2-27
Shock time 20ms sine-wave NO g 10 10 10 10 8 8 8 8 8 8
NCg6666- - - - - -
*1) Suitable at 690V for: earthed-neutral systems, overvoltage I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
*2) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
*3) High-pressure lamps
*4) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
*5) Current inrush approx. 16 x Ie
*6) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3
Main Contacts Type J7KN-10 J7KN-14 J7KN-18 J7KN-22 J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
Motor Contactor J7KN H-43
LVSG
Main Contacts Type J7KN-85 J7KN-110 J7KN-150 J7KN-175 J7KN-200
Rated insulation voltage Ui *1 V AC 750 750 690 690 690
Making capacity Ieff at Ue = 690V AC A 1100 1200 1500 1800 1700
Breaking capacity Ieff 400V AC A 950 1100 1200 1400 1600
J7KN-10 to J7KN-22 cosϕ = 0,65 500V AC A 850 1000 1200 1400 1600
J7KN-24 to J7KN-72 cosϕ = 0,35 690V AC A 600 600 700 800 1200
1000V AC A - - - - -
Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open A 150 170 200 250 350
Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1
220V kW 57 64 72 90 125
230V kW 59 67 72 90 125
240V kW 62 70 75 94 130
380V kW 98 111 125 156 218
400V kW 103 117 125 156 218
415V kW 107 122 130 160 225
440V kW 114 129 144 180 250
500V kW 130 147 164 205 285
660V kW 171 194 216 270 380
690V kW 179 203 216 270 380
1000V kW - - - - -
Rated operational current Ie (=Ithe) at 60°C, enclosed A 100 125 160 200 280
Rated operational power
of three-phase resistive loads
50-60Hz, cosϕ = 1
220V kW 38 47 60 76 106
230V kW 40 49 63 79 111
240V kW 41 52 66 83 116
380V kW 65 82 105 131 184
400V kW 69 86 110 138 193
415V kW 71 89 115 143 201
440V kW 71 95 121 152 213
500V kW 86 108 138 173 242
660V kW 114 142 182 228 320
690V kW 119 149 191 239 334
1000V kW - - - - -
Minimum cross-section of conductor
at load with Ie (=Ith)
mm² 50 70 95 120 185
Utilization category AC2 and AC3
Switching of three-phase motors
Rated operational current Ie
open and enclosed
220V A 85 110 150 175 210
230V A 85 110 150 175 210
240V A 85 110 150 175 210
380-400V A 85 110 150 175 210
415V A 85 110 150 175 210
440V A 85 110 - - -
500V A 60 60 - - -
660-690V A 57,5 57,5 - - -
1000V A - - - - -
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 25 33 40 50 60
240V kW 27 35 45 55 65
380-400V kW 45 55 75 90 110
415V kW 49 63 80 95 115
440V kW 49 63 85 100 125
500V kW 55 75 75 100 132
660-690V kW 55 55 75 110 132
1000V kW - - - - -
Utilization category AC4
Switching of squirrel cage motors, inching
Rated operational current Ie (=Ith)
open and enclosed
220V A 85 98 55 63 85
230V A 85 98 55 63 85
240V A 85 98 55 63 85
380-400V A 85 85 55 63 85
415V A 85 85 - - -
440V A 85 85 - - -
500V A 85 85 - - -
660V A 60 60 - - -
690V A 57,5 57,5 - - -
1000V A - - - - -
H-44 Motor Contactor J7KN
Rated operational power
of three-phase motors
50-60Hz
220-230V kW 25 30 15 18,5 25
240V kW 27 32 15,5 19 26
380-400V kW 45 45 25 30 45
415V kW 49 49 25 33 45
440V kW 49 49 30 34 48
500V kW 55 55 25 30 55
660-690V kW 55 55 25 30 55
1000VkW-----
Utilization category AC 5a
Switching of gas discharge lamps
Rated operational current Ie per pole at 220/230V
Fluorescent lamps,
uncompensated and serial compensated A 100 120 120 140 180
parallel compensated A 55 70 85 100 120
dual-connection A 112 144 120 140 180
Metal halide lamps*2,
uncompensated A 85 90 95 110 140
parallel compensated A 55 70 75 85 110
Mercury-vapour lamps*3,
uncompensated A 112 144 120 140 180
parallel compensated A 55 70 75 85 110
Mixed light lamps*4 A 100 120 100 120 160
Utilization category AC5b
Switching of incandescent lamps*5
Rated operational current Ie per pole at 220/230V A 69 75 100 120 160
Utilization category AC6a
Transformer primary switching
at inrush n3030303030
Rated operational current Ie400V A3850658090
Rated operational power
dependent on inrush n
220-230V kVA 15 20 25 30 34
240V kVA 15,5 20,5 27 33 37
380-400V kVA 26 34 45 55 60
For different inrush-factors x
use the following formula:
Px=Pn*(n/x)
415-440V kVA 29 38 46 57 63
500V kVA3343556975
660-690V 45 60 56 69 100
Utilization category AC6b
Switching of three-phase capacitor banks
Maximum inrush current (peak val-
ue) as multiple k of the capacitor
rated current
k2020202015
Rated operational current Ie500V A 87 100 120 155 195
Rated operational power
(sinϕ→1)
220-230V kVAr 33 38 45 60 75
240V kVAr 36 42 52 62 78
380-400V kVAr 57 65 80 100 130
For different multiples x
use the following formula:
Px=Pk*(k/x)
415-440V kVAr 60 70 95 110 135
500V kVAr 70 80 100 130 170
660-690V kVAr 70 80 100 130 170
Switching of detuned capacitors
Rated operational current Ie690V A 98 105 115 140 200
Rated operational power 220-230V kVAr 35 40 43 53 76
240V kVAr 39 43 45 55 80
380-400V kVAr 68 75 75 90 130
415-440V kVAr 71 77 80 100 140
500V kVAr 85 90 95 120 170
660-690V kVAr 110 120 125 150 200
Utilization category DC1
Switching of resistive load
Time constant L/R 1ms
Rated operational current Ie1 pole24V A 150 170 - - -
60V A 150 170 - - -
110V A 20 25 - - -
220V A 2 2,5 - - -
3 poles in series 24V A 150 170 200 250 350
60V A 150 170 200 250 350
110V A 150 170 150 170 250
220V A 100 160 80 100 150
Main Contacts Type J7KN-85 J7KN-110 J7KN-150 J7KN-175 J7KN-200
Motor Contactor J7KN H-45
LVSG
Utilization category DC3 and DC5
Switching of shunt motors and series motors
Time constant L/R 15ms
Rated operational current Ie1 pole24V A 150 170 - - -
60V A 85 110 - - -
110V A 2 2,5 - - -
220V A 0,5 0,5 - - -
3 poles in series 24V A 150 170 - - -
60V A 100 110 - - -
110V A 100 110 - - -
220V A 7 8 - - -
Maximum ambient temperature
Operation open °C -40 to +60 (+90)*6 -25 to +55 (+70)*7
enclosed °C -40 to +40 -25 to +40
with thermal overload relay open °C -25 to +60 -25 to +55
enclosed °C -25 to +40 -25 to +40
Storage °C -50 to +90 -55 to +80
Short circuit protection
for contactors without thermal overload relay
Coordination-type "1" according to IEC 947-4-1
Contact welding without hazard of persons
max. fuse size gL (gG) A 250 250 250 315 400
Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size gL (gG) A 160 200 200 250 315
Contact welding not accepted
max. fuse size gL (gG) A 100 125 160 200 250
For contactors with thermal overload relay the device with
the smaller admissible backup fuse (contactor or thermal
overload relay) determines the fuse size.
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 10 - 70*8 10 - 70*8 95 120 185
flexible mm² 6 - 50*8 16 - 50*8 screw screw screw
flexible with multicore cable end mm² 10 - 35 10 - 35 M8 M8 M8
Cables per clamp
solid or stranded mm²
flexible mm²
Cables per clamp
main connector solid AWG 10 10
flexible AWG 6 - 0 6 - 0
Cables per clamp 1 1
solid AWG
flexible AWG
Cables per clamp
Frequency of operations z
Contactors without thermal overload relay
without load 1/h 3000 3000 1200 1200 1200
AC3, Ie1/h 300 300 - - -
AC4, Ie1/h 120 120 - - -
DC3, Ie1/h 300 300 - - -
Mechanical life
AC operated S x 1065510108
DC operated S x 1065510108
Short time current 10s-current A 680 880 1200 1400 1800
Power loss per pole
at I
e
/AC3 400V
W 4,3 6,0 8 11 8
Resistance to shock acc. to IEC 68-2-27
Shock time 20ms sine-wave NO g 7 7 - - -
NC g 5 5 - - -
*1) Suitable at 690V for: earthed-neutral systems, overvoltage I to IV, pollution degree 3 (standard-industry):
Uimp = 8kV. Data for other conditions on request.
*2) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
*3) High-pressure lamps
*4) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb
(daylight lamps)
*5) Current inrush approx. 16 x Ie
*6) With reduced control voltage range 0,9 up to 1,0 x U
s
and with reduced rated current I
e
/AC1 according to I
e
/AC3
*7) With reduced control voltage range 1,0 x Us and with reduced rated current Ie/AC1 according to Ie/AC3
*8) Maximum cable cross-section with prepared conductor
Main Contacts Type J7KN-85 J7KN-110 J7KN-150 J7KN-175 J7KN-200
H-46 Motor Contactor J7KN
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts Ty p e J7KN-10 J7KN-14 J7KN-18 J7KN-22 J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
Rated insulation voltage Ui
*1
*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other con-
ditions on request
V~ 690 690 690 690 - - - - - -
Thermal rated current Ith to 690V
Ambient temperature 40°C A 16 16 16 16 - - - - - -
60°CA12121212- - - - - -
Utilization category AC15
Rated operational current Ie220-240V A 12 12 12 12 - - - - - -
380-415V A 4 4 4 4 - - - - - -
440V A 4 4 4 4 - - - - - -
500V A 3 3 3 3 - - - - - -
660-690V A 1 1 1 1 - - - - - -
Utilization category DC13
Rated operational current Ie60VA8888------
110V A 1 1 1 1 - - - - - -
220V A 0,1 0,1 0,1 0,1 - - - - - -
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 25 25 25 25 - - - - - -
For contactors with thermal overload relay the device with
the smaller admissible control fuse (contactor or thermal
overload relay) determines the fuse.
Control Circuit
Power consumption of coils
AC operated inrush VA 33-45 90-115 140-165
sealed VA 7-10 9-13 13-18
W 2,6-3 2,7-4 5,4-7
DC operated inrush W 75 140 200
sealed W 2 2 6
Operation range of coils
in multiples of control voltage UsAC operated 0,85-1,1 0,85-1,1 0,85-1,1
DC operated 0,8-1,1 0,8-1,1 0,8-1,1
Switching time at control voltage Us ±10%*2,*3
*2) Total breaking time = release time + arc duration
*3) Values for delay of the release time of the making contact and the make time of the break contact will be increased, if magnet coils are
protected against voltage peaks (varistor, RC-unit, diode-unit)
AC operated make time ms 8-16 10-25 12-28
release time ms 5-13 8-15 8-15
arc duration ms 10-15 10-15 10-15
DC operated make time ms 8-12 10-20 12-23
release time ms 8-13 10-15 10-18
arc duration ms 10-15 10-15 10-15
Cable cross-section
Auxiliary connector solid mm² 0,75-6 - -
flexible mm² 1-4 - -
flexible with multicore cable end mm² 0,75-4 - -
Magnet coil solid mm² 0,75-2,5 0,75-2,5 0,75-2,5
flexible mm² 0,5-2,5 0,5-2,5 0,5-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,5-1,5
Clamps per pole 2 2 2
Auxiliary connector solid AWG 18 - 10 - -
flexible AWG 18 - 10 - -
Magnet coil solid AWG 14 - 12 14 - 12 14 - 12
flexible AWG 18 - 12 18 - 12 18 - 12
Clamps per pole 2 2 2
Motor Contactor J7KN H-47
LVSG
Auxiliary Contacts Ty p e J7KN-85 J7KN-110 J7KN-150 J7KN-175 J7KN-200
Rated insulation voltage Ui
*1
*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3
(standard-industry): Uimp = 8kV. Data for other conditions on request
V~ 690 690 690 690 690
Thermal rated current Ith to 690V
Ambient temperature 40°C A 16 16 10 10 10
60°C A 12 12 - - -
Utilization category AC15
Rated operational current Ie220-240V A 12 12 3 3 3
380-415V A 6 6 2 2 2
440V A 6 6 1,5 1,5 1,5
500V A 4 4 1,5 1,5 1,5
660-690V A 2 2 1 1 1
Utilization category DC13
Rated operational current Ie60V A 8 8 - - -
110V A 1 1 0,5 0,5 1
220V A 0,1 0,1 0,2 0,2 0,5
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 25 25 10 10 10
For contactors with thermal overload relay the device with
the smaller admissible control fuse (contactor or thermal
overload relay) determines the fuse.
Control Circuit
Power consumption of coils
AC operated inrush VA 280-350 350-420 550 550 1100
sealed VA 16 -23 23 -29 120 120 66
W 4-6 6-7,3 - - -
DC operated inrush W 170 320 160 160 530
sealedW245521
Operation range of coils
in multiples of control voltage UsAC operated 0,85-1,1 0,85-1,1 0,85-1,1 0,85-1,1
DC operated 0,8-1,1 0,85-1,1 0,85-1,1 0,85-1,1
Switching time at control voltage Us ±10%*2,*3
*2) Total breaking time = release time + arc duration
*3) Values for delay of the release time of the making contact and the make time of the
break contact will be increased, if magnet coils are protected against voltage peaks
(varistor, RC-unit, diode-unit)
AC operated make time ms 13-30 12-30 12-30 30-40
release time ms 8-15 15-40 15-40 15-45
arc duration ms 10-15 - -
DC operated make time ms 20-30 - - -
release time ms 10-18 - - -
arc duration ms 10-15 - - -
Cable cross-section
Auxiliary connector solid mm² 0,75-2,5 0,75-2,5
flexible mm² 0,75-2,5 0,75-2,5
flexible with multicore cable end mm² 0,5-1,5 -
Magnet coil solid mm² 0,75-2,5 1-2,5
flexible mm² 0,5-2,5 1-2,5
flexible with multicore cable end mm² 0,5-1,5 -
Clamps per pole 14 - 12 16 - 12
Auxiliary connector solid AWG 18 - 12 16 - 12
flexible AWG 14 - 12 16 - 12
Magnet coil solid AWG 18 - 12 16 - 12
flexible AWG 2 2
Clamps per pole 0,75-2,5 0,75-2,5
H-48 Motor Contactor J7KN
Contactors for North America
Data according to UL508
Main Contacts (cULus) Ty p e J7KN-10 J7KN-14 J7KN-18 J7KN-22 J7KN-24 J7KN-32 J7KN-40 J7KN-50 J7KN-62 J7KN-74
Rated operational current
"General Use"
A25253030506580110120130
Rated operational power 110-120V hp 2 2 3 5 5 10 10 10
of three-phase motors 200V hp 3 3 5 5 10 10 15 20 25
at 60Hz (3ph) 220-240V hp 3 3 10 10 15 20 25 30
277V hp 3 5 10 15 20 25 30
380-415V hp 5 5 10 10 10 15 20 25 30 40
440-480V hp 5 10 15 15 20 25 30 40 50
550-600V hp 10 15 20 20 25 30 40 50 50
Rated operational power 110-120V hp ½ ¾ 1 2 3 3 5
of AC motors 200V hp 1 1,5 2 3 3 5 7½ 10 15
at 60Hz (1ph) 220-240V hp 2 3 3 5 5 10 15 15
277V hp 2 3 3 5 5 10 10 15 15
380-415V hp 3 3 5 5 5 10 15 20 20
440-480V hp 3 5 5 10 15 20 25 25
550-600V hp 3 5 10 10 15 20 25 30 30
Rated operational power of 110-120V hp - - - - 2 3 - 3 5 -
three-phase motors at 60Hz (3ph) 200V hp - - - - 3 5 - 10 -
for elevators 220-240V hp - - - - 5 - 7½ 10 -
Demands according to ANSI A17.5
(500.000 operations) 440-480V hp - - - - 10 15 - 20 25 -
550-600V hp - - - - 10 20 - 25 30 -
Rated operationalcurrent 600V A - - - - 15 22 - 27 37 -
Fuses A 30 40 50 50 90 125 175 175 225 250
Suitable for use on a capability
of delivering not more than rms A 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000
V 600 600 600 600 600 600 600 600 600 600
Auxiliary Contacts (cULus) A600 A600 A600 A600 - - - - - -
Main Contacts (cULus) Ty p e J7KN-85 J7KN-110 J7KN-150 J7KN-175 J7KN-200
Rated operational current
"General Use"
A 125 125 - - -
Rated operational power 110-120V hp 15 - - - -
of three-phase motors 200V hp - 30 - - -
at 60Hz (3ph) 220-240V hp 35 40 - - -
277V hp - - - - -
380-415V hp - - - - -
440-480V hp 65 75 - - -
550-600V hp 85 100 - - -
Rated operational power 110-120V hp 8 10 - - -
of AC motors 200V hp - 20 - - -
at 60Hz (1ph) 220-240V hp 20 20 - - -
277V hp - - - - -
380-415V hp - - - - -
440-480V hp - 50 - - -
550-600V hp - 60 - - -
Rated operational power of 110-120V hp - - - - -
three-phase motors at 60Hz (3ph) 200V hp - - - - -
for elevators 220-240V hp - - - - -
Demands according to ANSI A17.5
(500.000 operations) 440-480V hp - - - - -
550-600V hp - - - - -
Rated operationalcurrent 600V A - 62 - - -
Fuses A-300---
Suitable for use on a capability
of delivering not more than rms A 10000 10000 - - -
V 600 600 - - -
Auxiliary Contacts (cULus) A600 A600 - - -
Motor Contactor J7KN H-49
LVSG
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Contact Life
For selection of the suitable contactor-type according to supply volt-
age, power rating and application (utilization category AC1, AC3 or
AC4) use contact life characteristic diagram.
For the most common supply voltages four scales of power ratings Pn
are provided for each utilization category.
Select contactor-type according to utilization category AC3 (breaking
current Ia = Ie) using the motor rating scales to the right, according
to utilization category AC4 (breaking current Ia = 6 x Ie) using the
motor rating scales to the left.*1
Select contactor-type according to utilization category AC1 (breaking
current Ia = Ie/AC1) using the breaking current scale.*1
For contactors frequently used under AC3/AC4-mixed service condi-
tions calculate contact life with the formula:
1. Pay attention to the approved rated values of the selected
contactor according to the national approvals
MAC3
1%AC4
100
-----------------x AC3
AC4
----------- 1


+
---------------------------------------------------------=
M = Contact life (switching cycles) for AC3/AC4-mixed operations
AC3 = Contact life (switching cycles) for AC3 operations (normal switching
conditions). Breaking current Ia = rated motor current In.
AC4 = Contact life (switching cycles) for AC4 operations (inching).
Breaking current Ia= multiples of rated motor current In.
%AC4 = Percents of AC4-operations related to the total cycles.
A
Motor Rating
Pn/AC4
Motor Rating
Pn/AC3
Breaking Current
Ia (=Ie/AC1)
J7KN-74
J7KN-24
J7KN-32
J7KN-40
J7KN-50
J7KN-62
J7KN-22
J7KN-18
J7KN-14
J7KN-12
J7KN-10
J7KN-09
millions of operations
H-50 Motor Contactor J7KN
A
Motor Rating
Pn/AC4
Motor Rating
Pn/AC3
Breaking Current
Ia (=Ie/AC1)
J7KN-200
J7KN-150
J7KN-175
J7KN-110
J7KN-85
millions of operations
Motor Contactor J7KN H-51
LVSG
Contactors
Utilization Categories
For easier choice of devices and in order to make the comparison of
different products simplier are utilization categories for contactors and
motor-starters according to IEC 947-4-1 and VDE 0660 Part 102 ,for
control circuit devices and switching elements according to IEC 947-5-
1 and VDE 0660 Part 200 determind. The table offers different utiliza-
tion categories, typical applications and assorted test conditions.
Ue Rated operational voltage, U Voltage before make, Ur Recovery voltage, Ie Rated operational current, I Current make, Ic Current broken
1) Test with incandescent lamps
2) Test conditions according to standard
Ty p e o f
current
Cate-
gory
Typical applications Rated operational
current
Test conditions for the number of
on-load operating cycles
Test conditions for
making and breaking capacities
Make Break Make Break
I/Ie U/Ue cosϕIc/Ie Ur/Ue cosϕI/Ie U/Ue cosϕIc/Ie Ur/Ue cosϕ
Alternating Current
AC1 Non-inductive or
slightly inductive loadsre-
sistance furnaces
all values 1 1 0.95 1 1 0.95 1.5 1.05 0.8 1.5 1.05 0.8
AC2 Slip-ring motors:
starting, switching off
all values 2.5 1 0.65 2.5 1 0.65 4 1.05 0.65 4 1.05 0.65
AC3 Squirrel-cage motors:
starting, switching off mo-
tors during running
17A< Ie17A 6 1 0.65 1 0.17 0.65 10 1.05 0.45 8 1.05 0.45
Ie100A 6 1 0.35 1 0.17 0.35 10 1.05 0.45 8 1.05 0.45
Ie> 100A 6 1 0.35 1 0.17 0.35 10 1.05 0.35 8 1.05 0.35
AC4 Squirrel-cage motors:
starting, plugging, inching
17A< Ie17A 6 1 0.65 6 1 0.65 12 1.05 0.45 10 1.05 0.45
Ie100A 6 1 0.35 6 1 0.35 12 1.05 0.45 10 1.05 0.45
Ie> 100A 6 1 0.35 6 1 0.35 12 1.05 0.35 10 1.05 0.35
AC5a Switching of electric dis-
charge lamp controls
all values - - - - - - 3 1.05 0.45 3 1.05 0.45
AC5b Switching of incandes-
cent lamps
all values ------1.51.05 1)41.05 1)
AC6a Switching of transformers Ie100A - - - - - - 4.5 1.05 0.45 3.6 1.05 0.45
Ie> 100A - - - - - - 4.5 1.05 0.35 3.6 1.05 0.35
AC6b Switching of capacitor
banks
- ------2) 2)
AC7a Slightly inductive loads in
household appliances
and similar applications
all values ------1.51.050.81.51.050.8
AC7b Motor loadsfor household
applications
Ie100A - - - - - - 8 1.05 0.45 6 1.05 0.45
Ie>100A------81.050.3561.050.35
AC8a Hermetic refrigerant com-
pressor motor control with
manualresetting of over-
load releases
Ie100A - - - - - - 6 1.05 0.45 6 1.05 0.45
Ie>100A------61.050.3561.050.35
AC8b Hermetic refrigerant com-
pressor motor control with
automatic resetting of
overload releases
Ie100A - - - - - - 6 1.05 0.45 6 1.05 0.45
Ie>100A------61.050.3561.050.35
AC12 Control of resistive loads
and solid state loads with
isolation by opto couplers
all values ------110.9110.9
AC13 Control of solid state
loads with transformer
isolation
all values - - - - - - 10 1.1 0.65 1.1 1.1 0.65
AC14 Control of small electro-
magnetic loads (<=72VA)
- ------61.10.761.10.7
AC15 Control of
electromagnetic load
(>72VA)
- 10 1 0.7 1 1 0.4 10 1.1 0.3 10 1.1 0.3
Make L/R Break L/R Make L/R Break L/R
I/Ie U/Ue [ms] Ic/Ie Ur/Ue [ms] I/Ie U/Ue [ms] Ic/Ie Ur/Ue [ms]
Direct Current
DC1 Non-inductive or
slightly inductive loads re-
sistance furnaces
all values 1111111.51.0511.51.051
DC3 Shunt-motors: starting,
plugging, inching dynamic
braking of d.c. motors
all values 2.5 1 2 2.5 1 2 4 1.05 2.5 4 1.05 2.5
DC5 Series-motors:
starting, plugging, inching
dynamic braking of d.c.
motors
all values 2.5 1 7.5 2.5 1 7.5 4 1.05 15 4 1.05 15
DC6 Switching of incandes-
cent lamps
all values ------1.51.05 1)41.05 1)
DC12 Control of resistive loads
and solid state loads with
isolation by opto couplers
all values ------111111
DC13 Control of electromagnets all values 1 1 300 1 1 300 1.1 1.1 300 1.1 1.1 300
DC14 Control of electromagnet-
ic loads having economy
resistors in circuit
all values ------101.115101.115
H-52 Motor Contactor J7KN
Accessories
Data according to IEC 947-5-1, EN 60947-5-1, VDE 0660
Data according to CSA, UL and CUL
Contactors and Accessories
Wiring diagrams
Auxiliary contact blocks Pneumatic timer
Auxiliary Contacts Ty p e J73KN-B J73KN-C J73KN-B-TP...
Rated insulation voltage Ui
*1
*1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pol-
lution degree 3 (standard-industry): Uimp = 8kV. Data for other condi-
tions on request
V~ 690 690 690
Thermal rated current Ith to 690V
Ambient temperature 40°C A 10 10 10
60°C A 6 6 -
Frequency of operations z 1/h 3000 3000 1200
Mechanical life S x
106
10 10 1
Power loss per pole at Ie/AC1 W 0,5 0,5 -
Utilization category AC15
Rated operational current Ie 220-240V A 3 3 4
380-400V A 2 2 3
440V A 1,6 1,6 2
500V A 1,2 1,2 2
660-690V A 0,6 0,6 2
Utilization category DC13
Rated operational current Ie60V A 2 2 2,5
110V A 0,4 0,4 1,5
220V A 0,1 0,1 0,2
Short circuit protection
short-circuit current 1kA, contact
welding not accepted max. fuse
size
gL (gG) A 20 20 10
For contactors with thermal overload relay or auxiliary con-
tacts the device with the smaller admissible control fuse
(contactor or thermal overload relay) determines the fuse
size.
Cable cross-sections
solid or stranded mm² 0,75-2,5 0,75-2,5 1-2,5
flexible mm² 0,75-2,5 0,75-2,5 0,75-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,75-2,5
Cables per clamp 2 2 2
Auxiliary Contacts Ty p e J73KN-B J73KN-C J73KN-B-TP...
Rated operational current
„General Use“
A10 10 10
Rated operational voltage max. V AC 600 600 600
Auxiliary Contacts A600 A600 A600
J73KN-B-10 J73KN-B-01 J73KN-C-11S*1
*1) Correct terminal marking is given by mounting
53 61
54 62
71 83
72 84
(left side) (right side)
on-delayed off-delayed
J74KN-B-TP...DA J74KN-B-TP...IA
Motor Contactor J7KN H-53
LVSG
Dimensions
AC operated DC operated
J7KN-10...
J7KN-10-4
J7KN-14...
J7KN-18...
J7KN-22...
J7KN-10...D
J7KN-14...D
J7KN-18...D
J7KN-22...D
J7KN-24...
J7KN-32...
J7KN-40...
J7KN-24...D
J7KN-32...D
J7KN-40...D
J7KN-50...
J7KN-62...
J7KN-74...
J7KN-50...D
J7KN-62...D
J7KN-74...D
H-54 Motor Contactor J7KN
AC operated
J7KN-85...
J7KN-110...
J7KN-200...
J7KN-150...
J7KN-175...
Auxiliary contact blocks
J73KN-B-01
J73KN-B-10
J73KN-C-11S
Motor Contactor J7KN H-55
LVSG
Pneumatic timer
J74KN-B-TP...
Auxiliary contact blocks
J74KN-A-VG J74KN-A-RC
J74KN-B-VG J74KN-B-RC
H-56 Motor Contactor J7KN
Position of Terminals
AC operated
J7KN-10-10
to
J7KN-22-10
J7KN-10-01
to
J7KN-22-01
J7KN-24
J7KN-32
J7KN-40
J7KN-50
J7KN-62
J7KN-74
J7KN-85-22
J7KN-110-22
J7KN-150-11
J7KN-175-11
J7KN-200-22
DC operated with double winding coil
J7KN-10-10...D
J7KN-14-10...D
J7KN-18-10...D
J7KN-22-10...D
J7KN-10-01...D
J7KN-14-01...D
J7KN-18-01...D
J7KN-22-01...D
J7KN-24...D
J7KN-32...D
J7KN-40...D
J7KN-50...D
J7KN-62...D
J7KN-74...D
J7KN-81-21...D
J7KN-110-21...D
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J505-E2-02
Thermal Overload Relay J7TKN H-57
LVSG
Thermal Overload Relay
J7TKN
Thermal Overload Relay
Direct and separate mounting
Single phasing sensivity according to IEC 947-4-1
Finger proof (VBG 4)
Accessories
Busbar sets
Set for single mounting
)
Approved Standards
Ordering Information
Model Number Legend
1. Thermal Overload Relay
1) Thermal Overload Relay
2) A: for mini motor contactor and motor contactor (4-11 kW)
B: for motor contactor (4-15 kW)
C: for motor contactor (18.5 kW)
D: for motor contactor (22-37 kW)
E: for motor contactor (45-55 kW)
F: for motor contactor (75-110 kW)
3) Setting range (examples)
E16: 0.12-0.16 A
E27: 0.18-0.27 A
...
2E7: 1.8-2.7 A
...
11: 8-11 A
2. Accessories for Thermal Overload Relay
1) Accessories for Thermal Overload Relay
2) SM: Single mounting for J7TKN-B Types (4-32 kW)
SU: Busbar sets
3) 175: for J7TKN-F Types (75-90 kW)
200: for J7TKN-F Types (110 kW)
Standard Guide No (US,C)
UL NKCR, NKCR7
ICE 947-4-1
VDE 0660
EN 60947-4-1
J7TKN-#-###
123
J74TK-##-###
123
H-58 Thermal Overload Relay J7TKN
System overview
Thermal Overload Relays for plug-in mounting
Setting Range Type Pack Weight
D.O.L. (A) Star Delta (A) pcs. kg/pc.
For contactors J7KNA-09..., J7KNA-12..., J7KN-10... to J7KN-22...
0.12 - 0.18 -
hand reset
J7TKN-A-E18 1 0.10
0.18 - 0.27 -J7TKN-A-E27 1 0.10
0.27 - 0.4 -J7TKN-A-E4 1 0.10
0.4 - 0.6 -J7TKN-A-E6 1 0.10
0.6 - 0.9 -J7TKN-A-E9 1 0.10
0.8 - 1.2 -J7TKN-A-1E2 1 0.10
1.2 - 1.8 -J7TKN-A-1E8 1 0.10
1.8 - 2.7 - J7TKN-A-2E7 1 0.10
2.7 - 4 - J7TKN-A-4 1 0.10
4-
67 - 10.5 J7TKN-A-6 10.10
6-
910.5 - 15.5 J7TKN-A-9 10.10
8-
11 14 - 19 J7TKN-A-11 10.10
10 - 14 18 - 24 J7TKN-A-14 10.10
13 - 18 23 - 31 J7TKN-A-18 10.10
17 - 23 30 - 40 J7TKN-A-23 10.10
22 - 30 38 - 52 J7TKN-A-30 10.10
For contactors J7KN-10... to J7KN-40...
0.12 - 0.18 -
hand- and auto reset
J7TKN-B-E18 1 0.14
0.18 - 0.27 -J7TKN-B-E27 1 0.14
0.27 - 0.4 -J7TKN-B-E4 1 0.14
0.4 - 0.6 -J7TKN-B-E6 1 0.14
0.6 - 0.9 -J7TKN-B-E9 1 0.14
0.8 - 1.2 -J7TKN-B-1E2 1 0.14
1.2 - 1.8 -J7TKN-B-1E8 1 0.14
1.8 - 2.7 - J7TKN-B-2E7 1 0.14
2.7 - 4 - J7TKN-B-4 1 0.14
4-
67 - 10.5 J7TKN-B-6 10.14
6-
910.5 - 15.5 J7TKN-B-9 10.14
8-
11 14 - 19 J7TKN-B-11 10.14
10 - 14 18 - 24 J7TKN-B-14 10.14
13 - 18 23 - 31 J7TKN-B-18 10.14
17 - 24 30 - 41 J7TKN-B-24 10.14
23 - 32 40 - 55 J7TKN-B-32 10.14
For contactors J7KN-24... to J7KN-40...
28 - 42 48 - 73 J7TKN-C-42 10.30
Thermal Overload Relay J7TKN H-59
LVSG
Thermal Overload relays for separate mounting
Accessories
For contactors J7KN-50...-J7KN-74...
40 - 52 70 - 90 J7TKN-D-52 10.40
52 - 65 90 - 112 J7TKN-D-65 10.40
60 - 74 104 - 128 J7TKN-D-74 1 0.40
Setting Range Type Pack Weight
D.O.L. (A) Star Delta (A) pcs. kg/pc.
For contactors J7KN-85... to J7KN-150...
60 - 90 104 - 156
hand reset
J7TKN-E-90 10.90
80 - 120 140 - 207 J7TKN-E-120 10.90
For contactors J7KN-175... to J7KN-200...
100 - 150 175 - 260
hand reset
J7TKN-F-150 11.5
140 - 220 240 - 380 J7TKN-F-210 11.5
busbar sets
see accessories
Type Pack Weight
for overload relays for contactors pcs. kg/pc.
Busbar Sets
J7TKN-F-175 J7KN-150, J7KN-175 J74TK-SU-175 10.6
J7TKN-F-210 J7KN-200 J74TK-SU-200 10.7
busbars must be installed by users
Setting Range Type Pack Weight
D.O.L. (A) Star Delta (A) pcs. kg/pc.
Cable Cross-section to clamp (mm²) Type Pack Weight
for overload relay solid or stranded flexible
flex. with multicore
cable end pcs. kg/pc.
Sets for single mounting
J7TKN-B 0.75-60.75-40.5-4
J74TK-SM 1 0.035
H-60 Thermal Overload Relay J7TKN
Specifications
Engineering data and Characteristics
Thermal Overload Relays, tripping times for selection to motors of protection degree EEx e
Relays With Standard Tripping Characteristic
When selecting a standard overload, refer to the tripping curve.
Determine the values of the starting current ratio IA/IN and the time tE
which is marked on the label of the motor. The overload must trip
within the tE time, which means that the tripping curve from cold con-
dition must be (20% due to tolerance) below the coordination point IA/
IN and the time tE.
IA= Starting current of motor
IN = Rated current of motor
tE = tE-time of motor
All tripping times of overload relays J7TKN-A are shorter than the
minimum values of the tE time for motors of protection degree EEx e
acc. to EN 50019 and therefore are suitable for all motors of protec-
tion degree EEx e. For these overload relays the selection on basis
of tripping curves is thereby not necessary.
Labels of tripping curves for each setting range, sized 148x105mm
(self-adhesive) are available on request.
Specify type and setting range.
Setting Range Tripping time depending on the multiple of the
current setting from cold condition (tolerance
±20% of the tripping time)
IA/INIA/INIA/INIA/INIA/INIA/IN
AA34567,28
J7TKN-A-... ssssss
0,12 - 0,18 18,5 10,4 7,2 5,5 4,3 3,6
0,18 - 0,27 16,7 9,8 6,5 5 4,1 3,5
0,27 - 0,4 19,4 12,1 8,2 5,9 4,9 4,2
0,4 - 0,6 18,7 11,2 8 6 4,9 4,1
0,6 - 0,9 19,7 11,6 8,1 6,1 4,9 4,2
0,8 - 1,2 22,9 13,6 10 7,3 6 5,2
1,2 - 1,8 22,2 13,2 9,2 7,6 5,8 5,3
1,8 - 2,7 23 13,7 9,3 7,6 5,7 5,1
2,7 - 424 14,4 9,9 7,8 5,9 5,1
4-
624,7 13,8 9,9 7,3 5,6 4,8
6-
922 13,4 8 5,7 4,1 3,5
8-
11 17,4 9,2 5,9 4,1 2,9 2,3
10 - 14 26,4 12,9 7,6 5,2 3,5 2,8
13 - 18 14,7 7,7 4,8 3,2 2,3 1,7
17 - 23 16,2 8,4 5 3,6 2,4 1,8
22 - 30 16,8 8,5 5 3,6 2,3 1,9
J7TKN-C-42 ssssss
28 - 42 25,2 13,3 8 5,5 4 3,1
J7TKN-D-... ssssss
40 - 52 18,3 9,2 5,6 3,9 2,8 2,2
52 - 65 17,8 8,7 5,2 3,4 2,5 1,9
60 - 74 19,5 13,5 11 10 9,5 8,5
J7TKN-E-... ssssss
60 - 90 19,5 13,5 11 10 9,5 8,5
80 - 120 18 11 10 9 8,5 8
J7TKN-F-... ssssss
100 - 150 34 26 24 20,5 19 18
140 - 210 30 24 21 18,5 17 16
Typical tripping
curve for overload
relay J7TKN-A
Minimum values of
tE time (motor)
acc. to EN50019
ratio IA/IN
Thermal Overload Relay J7TKN H-61
LVSG
Fuses for J7TKN-A; J7TKN-B; J7TKN-C; J7TKN-D; J7TKN-E; J7TKN-F
Type Setting Range Max. Fuse Size According to Coordination-type Fuse UL
"2"*1
*1) Coordination-type according to IEC 947-4-1:
„2“: Light contact welding accepted. Thermal overload relay must not be damaged.
„1“: Welding of contactor and damage of the thermal overload relay allowed.
"1"*1
DOL Star Delta quick slow,
gL(gG)
slow,
gL(gG)
aM
AAA AAA A
J7TKN-A
J7TKN-B
0.12 - 0.18 -0.5
*2
*2) Miniature fuse
0.5*2 25 - 15
0.18 - 0.27 -1.0
*2 1.0*2 25 - 15
0.27 - 0.4 -2225-15
0.4 - 0.6 -2225-15
0.6 - 0.9 -4425-15
0.8 - 1.2 -44252 15
1.2 - 1.8 -66252 15
1.8 - 2.7 -1010254 15
2.7 - 4-161025415
4-
67 - 10.5 20 16 25 6 15
6-
910.5 - 15.5 35 25 35 10 25
8-
11 14-193525351630
10 - 14 18-2450356316 40
13 - 18 23-3150356320 50
17 - (23)24 30 - (40)41 63 50 63 25 60
(22)23 - (30)32 (38)40 - (52)55 80 63 80 35 70
J7TKN-C 28 - 42 48 - 73 100 80 150 50 110
J7TKN-D 40 - 52 70 - 90 160 100 150 63 200
52 - 65 90 - 112 160 125 150 80 250
60 - 74 104 - 128 160 125 150 80 250
For short circuit protecting overload relays with
current transformer use fuse according to the
7contactor of the combination.
J7TKN-E 60 - 90 104 - 156 300
80 - 120 140 - 207 -
J7TKN-F all ranges -
H-62 Thermal Overload Relay J7TKN
Tripping Characteristics for J7TKN-A, J7TKN-B, J7TKN-C, J7TKN-D
Detailed tripping times for each range see table page 60
Tripping Characteristics for J7TKN-E
Detailed tripping times for each range see table page 60
with three-phase load with two-pole load
Tripping time
min. s
F.L.C. multiplication factor
Average value of
typical tolerance
curves from cold
condition
Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values
Tripping time
min. s
K
Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values
K= Imax/Ie
Imax = max. phase current
Ie= max. scale value
with three-phase load with two-pole load
Tripping time
min. s
F.L.C. multiplication factor
Average value of
typical tolerance
curves from cold
condition
Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values
Tripping time
min. s
K
Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values
K= Imax/Ie
Imax = max. phase current
Ie= max. scale value
Thermal Overload Relay J7TKN H-63
LVSG
Tripping Characteristics for J7TKN-F
Detailed tripping times for each range see table page 60
Position of Terminals
with three-phase load with two-pole load
J7TKN-A J7TKN-B J7TKN-C; J7TKN-D
Tripping time
min. s
F.L.C. multiplication factor
Average value of
typical tolerance
curves from cold
condition
Proceeding from
service conditions
the times decrease
to 20-30% of the
characteristic values
Tripping time
min. s
K
Typical tolerance
curve from cold
condition
Proceeding from
service conditions
the times decrease
to 70-80% of the
characteristic values
K= Imax/Ie
Imax = max. phase current
Ie= max. scale value
H-64 Thermal Overload Relay J7TKN
Thermal Overload Relays
Data according to IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
Type J7TKN-A J7TKN-B J7TKN-C J7TKN-D J7TKN-E J7TKN-F
Rated insulation voltage Ui*1
*1) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry: Uimp = 4kV (at 440V), 6kV (at 690V).
Data for other conditions on request.
V~ 690 690 690 690 750 690
Permissible ambient temperature
operation open °C -25 to +60
storage °C -50 to +70
Trip class according to IEC 947-4-1 10A 10A 10A 10A 20 20
Cable cross-section
main connector solid or stranded mm² 0.75-6 +
0.75-2.5*2
*2) Maximum cable cross-section with prepared conductor
0.75-6 0,75-10 4-35*2 *3
*3) Without terminals, suitable for bushing one connector 70mm² (stranded) per phase
*4
*4) Busbar sets see accessories page 59
flexible mm² 0.75-4 +
0.5-2.5*2
1-4 0,75-6 6-25*2
flexible with multicore cable end mm² 0.5-2.5 +
0.5-1.5
0.75-4 0.75-6 4-25
Cables per clamp number 1+1 2 2 1
auxiliary connector solid mm² 0.75-2.5*2
flexible mm² 0.5-2.5*2
flexible with multicore cable end mm² 0.5-1.5
Cables per clamp number 2
Auxiliary contacts
Rated insulation voltage Ui*1
same potential V~ 690 690 690 690
different potential V~ 440 440 250 440
Utilization category AC15
Rated operational current Ie24V A 5 3 4*5
*5) Switching capacity of the start contact: AC15 300VA, max. 1.5A, DC13 (max. 220V) 30W, max. 1.5A
5
230V A 3 2 2.5 3
400V A 2 1 1.5 2
690V A 0.6 0.5 0.6 0.6
Utilization category DC13
Rated operational current Ie24V A 1.2 1 1.2 1.2
110V A 0.15 0.15 0.15 0.15
220V A 0.1 0.1 0.1 0.1
Short circuit protection (without welding 1kA)
highest fuse rating gL (gG) A 6 4 6 6
Setting range A to 23 all 28-42 52-65 all -
Power loss per current path (max.)
minimum setting value W 1.1 1.1 1.3 2.9 1.1 -
maximum setting value W 2.3 2.3 3.3 4.5 2.5 -
Thermal Overload Relay J7TKN H-65
LVSG
Temperature Compensation
In case of higher ambient temperature use the following formula:
(Ambient temperature - 20) x 0.125 = correction factor in % of the
full load motor current
Example:
Ambient temperature 70°C, full load motor current 7A
(70 - 20) x 0.125 = 6.25%
Setting value: 7A + 6,25% = 7.44A
Data according to CULUS
Type J7TKN-A J7TKN-B J7TKN-C J7TKN-D J7TKN-E
Rated insulation voltage V~ 600 600 600 600 600
Rated current A2332427485
Auxiliary contacts
Rated voltage
same potential V AC 600 600 600 600 600
different potential V~ 150 150 150 150 150
Switching capacity AC VA 500 500 600 600 600
of aux. contacts A42444
H-66 Thermal Overload Relay J7TKN
Dimensions
J7KNA-09 + J7TKN-A
J7KNA-12
J7KN-10 + J7TKN-B
J7KN-14
J7KN-18
J7KN-22
J7KN-10 + J7TKN-A
J7KN-14
J7KN-18
J7KN-22
J7KN-24 + J7TKN-B
J7KN-32
J7KN-40
Thermal Overload Relay J7TKN H-67
LVSG
J7KN-24 + J7TKN-C
J7KN-32
J7KN-40
J7KN-50 + J7TKN-D
J7KN-62
J7KN-74
J7KN-85 + J7TKN-E
J7KN-110
J7KN-150 + J7TKN-F
J7KN-175
J7KN-200 + J7TKN-210
H-68 Thermal Overload Relay J7TKN
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J509-E2-02
Motor Protection Circuit Breaker (MPCB) J7MN H-69
LVSG
Motor Protection Circuit Breaker (MPCB)
J7MN
MPCB system (motor protection CLASS 10)
Rotary and switch types
Rated operational current = 12 A, 25 A, 50 A and 100 A
Switching capacity up to 12.5 A = 100 kA/400 V
Fixed short-circuit release = 13 x Iu
Overload release adjustable 0.7 - 1 x Iu
Single phasing sensivity
Auxiliary contact modules
ON/OFF indication for MPCB front mounting and side mounting
Trip indication for MPCB side mounting
Accessories
Undervoltage release
Shunt release
Three phase busbar system up to 5 MPCB
Moulded plastic enclosures (IP55)
Moulded plastic front plates (IP55)
Door coupling rotary mechanisms (black and red/yellow)
)
Approved Standards
Standard Guide No (US,C)
UL see page 95
ICE 947-5-1
VDE 0660
EN 60947-5-1
H-70 Motor Protection Circuit Breaker (MPCB) J7MN
Ordering Information
Model Number Legend
1. Motor Protection Circuit Breaker (MPCB)
1) Motor Protection Circuit Breaker (MPCB)
2) Type
12: Switch type (0.16 - 12 A)
25: Rotary type (0.16 - 25 A)
50: Rotary type (25 - 40 A)
100: Rotary type (45 - 100 A)
3) Setting range (examples)
E16: 0.11 - 0.16 A
E2: 0.14 - 0.2 A
16: 10 - 16 A
...
2. Aux. Contacts for MPCB
1) Aux. Contact for MPCB
2) 11: 1 NO 1 NC
3) S: side mounting
F: front mounting
1) Aux. Contact for MPCB
2) T: Trip indicating contact
3) 11: 1 NO 1 NC
4) S: side mounting
3. Accessories for MPCB
1) Accessories for MPCB
2) S: Shunt release
U: Under voltage release
3) N1: 230 V 50 Hz / 240 V 60 Hz
N2: 210 - 230 V 50/60 Hz
1) Accessories for MPCB
2) PF: Enclosure IP55
P: Module plastic front plate
PH: Holder for front plate
3) 12: Switch type
25: Rotary type
1) Accessories for MPCB
2) DC: Door coupling rotary mechanism
3) B: black / gray
RY: red / yellow
1) Accessories for MPCB
2) L3: 3-phase busbar system (45 mm modular spacing)
DS: Shroud for unused terminal
3) 1/2: for 2 circuit breakers
1/3: for 3 circuit breakers
1/4: for 4 circuit breakers
1/5: for 5 circuit breakers
1) Accessories for MPCB
2) TC: Line side terminal
3) 12: for switch type
25: for rotary type
1) Accessories for MPCB
2) TB: Terminal block for UL/cUL type E
3) 25: for rotary type up to 25A
100: for rotary type up to 100A
J7MN-##-###
123
J73MN-###
123
J73MN-#-## #
123
4
J74MN-#-##
123
J74MN-## ##
123
J74MN-##-##
123
J74MN-##-#/#
123
J74MN-## ##
123
J74MN-## ###
123
Motor Protection Circuit Breaker (MPCB) J7MN H-71
LVSG
System overview
Motor Protection Circuit Breaker (MPCB)
Rated
current
In
A
Suitable
for
motors*1
3~400V
kW
Current setting range Short-circuit
breaking
capacity
at 3~400V
kA
Type Pack
pcs.
Weight
approx.
kg/pcs.
Thermal
overload
release
A
Instantaneous
short-circuit
release
A
Circuit-Breakers J7MN-12
0.16 - 0.11 – 0.16 2.1 100 J7MN-12-E16 10.21
0.2 - 0.14 – 0.2 2.6 100 J7MN-12-E2 10.21
0.25 0.06 0.18 – 0.25 3.3 100 J7MN-12-E25 10.21
0.32 0.09 0.22 – 0.32 4.2 100 J7MN-12-E32 10.21
0.4 - 0.28 – 0.4 5.2 100 J7MN-12-E4 10.21
0.5 0.12 0.35 – 0.5 6.5 100 J7MN-12-E5 10.21
0.63 0.18 0.45 – 0.63 8.2 100 J7MN-12-E63 10.21
0.8 - 0.55 – 0.8 10 100 J7MN-12-E8 10.21
1 0.25 0.7 – 1 13 100 J7MN-12-1 10.21
1.25 0.37 0.9 – 1.25 16 100 J7MN-12-1E25 10.21
1.6 0.55 1.1 – 1.6 21 100 J7MN-12-1E6 10.21
2 0.75 1.4 – 2 26 100 J7MN-12-2 10.21
2.5 - 1.8 – 2.5 33 100 J7MN-12-2E5 10.21
3.2 1.1 2.2 – 3.2 42 100 J7MN-12-3E2 10.21
4 1.5 2.8 – 4 52 100 J7MN-12-4 10.21
5 - 3.5 – 5 65 100 J7MN-12-5 10.21
6.3 2.2 4.5 – 6.3 82 100 J7MN-12-6E3 10.21
8 3 5.5 – 8 104 50 J7MN-12-8 10.21
10 4 7 – 10 130 50 J7MN-12-10 10.21
12 5.5 9 – 12 156 50 J7MN-12-12 10.21
*1) Recommended values for standard motors
*2) max. motor current 95A
H-72 Motor Protection Circuit Breaker (MPCB) J7MN
Circuit-Breakers J7MN-25
0.16 - 0.11 – 0.16 2.1 100 J7MN-25-E16 1 0.32
0.2 - 0.14 – 0.2 2.6 100 J7MN-25-E2 1 0.32
0.25 0.06 0.18 – 0.25 3.3 100 J7MN-25-E25 1 0.32
0.32 0.09 0.22 – 0.32 4.2 100 J7MN-25-E32 1 0.32
0.4 - 0.28 – 0.4 5.2 100 J7MN-25-E4 1 0.32
0.5 0.12 0.35 – 0.5 6.5 100 J7MN-25-E5 1 0.32
0.63 0.18 0.45 – 0.63 8.2 100 J7MN-25-E63 1 0.32
0.8 - 0.55 – 0.8 10 100 J7MN-25-E8 1 0.32
1 0.25 0.7 – 1 13 100 J7MN-25-1 1 0.32
1.25 0.37 0.9 – 1.25 16 100 J7MN-25-1E25 1 0.32
1.6 0.55 1.1 – 1.6 21 100 J7MN-25-1E6 1 0.32
2 0.75 1.4 – 2 26 100 J7MN-25-2 1 0.32
2.5 - 1.8 – 2.5 33 100 J7MN-25-2E5 1 0.32
3.2 1.1 2.2 – 3.2 42 100 J7MN-25-3E2 1 0.32
4 1.5 2.8 – 4 52 100 J7MN-25-4 1 0.32
5 - 3.5 – 5 65 100 J7MN-25-5 1 0.32
6.3 2.2 4.5 – 6.3 82 100 J7MN-25-6E3 1 0.32
8 3 5.5 – 8 104 100 J7MN-25-8 1 0.32
10 4 7 – 10 130 100 J7MN-25-10 1 0.32
12.5 5.5 9 – 12.5 163 100 J7MN-25-12E5 1 0.32
16 7.5 11 – 16 208 50 J7MN-25-16 1 0.32
20 - 14 – 20 260 50 J7MN-25-20 1 0.32
22 - 17 – 22 286 50 J7MN-25-22 1 0.32
25 11 20 – 25 325 50 J7MN-25-25 1 0.32
Circuit-Breakers J7MN-50
25 11 18 – 25 325 50 J7MN-50-25 1 0.96
32 15 22 – 32 416 50 J7MN-50-32 1 0.96
40 18.5 28 – 40 520 50 J7MN-50-40 1 0.96
45 36 – 45 585 50 J7MN-50-45 1 0.96
50 22 40 – 50 650 50 J7MN-50-50 1 0.96
Circuit-Breakers J7MN-100
63 30 45 – 63 819 50 J7MN-100-63 12.1
75 37 57 – 75 975 50 J7MN-100-75 12.1
90 70 – 90 1170 50 J7MN-100-90 12.1
100 45 80 – 100*2 1235 50 J7MN-100-100 12.1
Rated
current
In
A
Suitable
for
motors*1
3~400V
kW
Current setting range Short-circuit
breaking
capacity
at 3~400V
kA
Type Pack
pcs.
Weight
approx.
kg/pcs.
Thermal
overload
release
A
Instantaneous
short-circuit
release
A
*1) Recommended values for standard motors
*2) max. motor current 95A
Motor Protection Circuit Breaker (MPCB) J7MN H-73
LVSG
Accessories
Enclosures and Front Plates
Description Version for circuit
breaker
Type Pack
pcs.
Weight
approx.
kg/pcs.
Transverse auxiliary contact block
Contact block 1NO + 1NC all J73MN-11F 10 0.02
Auxiliary contact block for left hand side mounting (max 1pc. per circuit breaker)
Contact block 1NO + 1NC 9 mm all J73MN-11S 10 0.03
Signalling switch for left hand side mounting (max 1pc. per circuit breaker)
Signalling switch 1NO + 1NC each
Individual tripped and
short-circuit signalling
J7MN-25
J7MN-50
J73MN-T-11S 1 0.07
Auxiliary releases for right hand side mounting (max 1pc. per circuit breaker)
Undervoltage release
Trips the circuit-breaker
when the voltage is
interrupted. Prevents the
motor from being
restarted accidentally
when the voltage is
restored, suitable for
EMERGENCY STOP
acc. to VDE 0113
AC 50 Hz
230 V
AC 60 Hz
240 V all J74MN-U-N1 1 0.12
Shunt release
Trips the circuit-breaker
when the release coil
energized.
50/60 Hz
100% ON
210-240 V
50/60 Hz, DC
5sec ON
190-330 V all J74MN-S-N2 1 0.11
Description Version for circuit
breaker
Type Pack
pcs.
Weight
approx.
kg/pcs.
Front Plates
Moulded plastic front
plate with actuator dia-
phragm and holder for
circuit breaker
for actuation of circuit-breakers
in any enclosure
protection degree IP55
J7MN-12 J74MN-P12 1 0.08
Moulded plastic front
plate with rotary operat-
ing mechanism
lockable
for actuation of circuit-breakers
in any enclosure
protection degree IP55
J7MN-25
J7MN-50
J74MN-P25 1 0.08
Holder for front plate
J74MN-P25
Holder is mounted on front
plate, circuit-breaker (with ac-
cessories) is snapped on
J7MN-25 J74MN-PH 1 0.12
Enclosures
Moulded plastic
enclose with actuator
diaphragm
knockouts for J7MN-25
sealable
protection degree IP55
with N- and PE- terminal
(+ aux. contact + release) J7MN-12 J74MN-PF12 1 0.27
H-74 Motor Protection Circuit Breaker (MPCB) J7MN
Busbars
Mounting Parts for Fuseless Load Feeders
Moulded plastic
enclose with rotary
operating mechanism
knockouts for J7MN-25
lockable
protection degree IP55
with N- and PE- terminal
(+ aux. contact + release) J7MN-25 J74MN-PF25 10.30
Door-coupling mechanisms
The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and a extension shaft
(5 mm x 5 mm). The door-coupling rotary operating mechanisms are designed for degree of protection IP 65.
The door locking device prevents accidental opening of the cubicle door in the ON position of the circuit-breaker.
The OFF position can be locked with up to 3 padlocks.
Door-coupling rotary
mechanism black
extension shaft 330 mm
with supporting bracket
J7MN-25 to
J7MN-50
J74MN-DC-B 10.3
Emergency-Stop
Door-coupling rotary
mechanism red/yellow
extension shaft 330 mm
with supporting bracket
J7MN-25 to
J7MN-50
J74MN-DC-RY 10.3
Description Version for circuit
breaker
Type Pack
pcs.
Weight
approx.
kg/pcs.
Insulated 3-phase busbar systems
For feeding several modular circuit-breakers on standard mounting rails, insulated, shock-protected.
Rated operational voltage max. 690 V
3-phase busbars
modular spacing 45 mm
for 2 circuit-breakers
for 3 circuit-breakers
for 4 circuit-breakers
for 5 circuit-breakers
J7MN-12
J7MN-25
J74MN-L3-1/2
J74MN-L3-1/3
J74MN-L3-1/4
J74MN-L3-1/5
1
1
1
1
0.03
0.05
0.07
0.10
For connecting the 3-phase busbars from circuit-breakers different sizes. Clamping together J7MN-12 and J7MN-25
circuit-breakers is not possible due to the different modular spacings and the different heights of the terminals.
Line side terminal
3-pole, connection
from top
Conductor cross-section
solid or stranded 6- 25 mm²
with ferrule 4-16 mm²
J7MN-12
J7MN-25
J74MN-TC12
J74MN-TC25
1
1
0.04
0.04
Shroud for unused terminals J7MN-12
J7MN-25
J74MN-DS 20 -
Description Version for circuit
breaker
Type Pack
pcs.
Weight
approx.
kg/pcs.
DIN-rail adapters
Adapter
for mechanical fixing of
circuit-breaker and
contactor
35 mm-DIN-rail
(DIN EN50022)
or screw mounting
J7MN... J74MN-HU 10 0.05
Link modules
for electrical connection between circuit-breaker and contactor
Link module up to 20 A
up to 32 A
J7MN... J74MN-VD-12
J74MN-VD-25
10
10
-
-
Terminal block
with increased creepage distances and clearances acc. to cULus Type „E“
Terminal block up to 600 V acc. to UL 489
not for transverse aux. contact
block
J7MN-25
J7MN-100
J74MN-TB25
J74MN-TB100
1
1
0.12
0.15
Description Version for circuit
breaker
Type Pack
pcs.
Weight
approx.
kg/pcs.
Motor Protection Circuit Breaker (MPCB) J7MN H-75
LVSG
Specifications
Engineering data and Characteristics
Components for Fuseless Load Feeders, DIN-Rail Mounting
Type of coordination „1“ 3 x 415 V 10 kA (other conditions on request)
Motor
3~400V
kW
Setting range
A
Circuit-breaker
page 72
Ty p e
Contactor
220-230V 50Hz
Ty p e
Link
module
Type
DIN-rail
adapter
Type
- 0.11– 0.16 J7MN-25-E16 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.14– 0.2 J7MN-25-E2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.06 0.18– 0.25 J7MN-25-E25 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.09 0.22– 0.32 J7MN-25-E32 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.28– 0.4 J7MN-25-E4 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.12 0.35– 0.5 J7MN-25-E5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.18 0.45– 0.63 J7MN-25-E63 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 0.55– 0.8 J7MN-25-E8 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.25 0.7– 1 J7MN-25-1 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.37 0.9– 1.25 J7MN-25-1E25 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.55 1.1– 1.6 J7MN-25-1E6 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
0.75 1.4– 2 J7MN-25-2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 1.8– 2.5 J7MN-25-2E5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
1.1 2.2– 3.2 J7MN-25-3E2 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
1.5 2.8– 4 J7MN-25-4 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
- 3.5– 5 J7MN-25-5 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
2.2 4.5– 6.3 J7MN-25-6E3 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
3 5.5– 8 J7MN-25-8 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
4 7– 10 J7MN-25-10 J7KN-10-10 230 J74MN-VD-12 J74MN-HU
5.5 9– 12.5 J7MN-25-12E5 J7KN-14-10 230 J74MN-VD-12 J74MN-HU
7.5 11– 16 J7MN-25-16 J7KN-18-10 230 J74MN-VD-12 J74MN-HU
- 14– 20 J7MN-25-20 J7KN-22-10 230 J74MN-VD-25 J74MN-HU
- 17– 22 J7MN-25-22 J7KN-22-10 230 J74MN-VD-25 J74MN-HU
11 20– 25 J7MN-25-25 J7KN-22-10 230 J74MN-VD-25 J74MN-HU
H-76 Motor Protection Circuit Breaker (MPCB) J7MN
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
This table shows the rated ultimate short-circuit breaking capacity Icu
and the rated service short-circuit breaking capacity Ics of the J7MN
circuit-breakers with different operational voltages as a function of
the rated current In of the circuit-breakers.
The circuit-breakers can be fed at the top or bottom supply terminals
without any reduction of the rated data.
If the short-circuit current exceeds the rated short-circuit breaking
capacity of the circuit-breaker specified in the tables at the
installation point, a back-up fuse is to be used.
The maximum rated current for the back-up fuse is specified in the
tables. These fuses are only suitable for the short-circuit-currents as
indicated on the fuses.
Circuit-
breaker
Rated
current In
up to AC 240V*1)
*1) 10% overvoltage
up to AC 400V*1)
up to AC 415V*2)
*2) 5% overvoltage
up to AC 440V*1)
up to AC 460V*2)
up to AC 500V*1)
up to AC 525V*2)
up to AC 690V*1)
Type AI
cu
kA
Ics
kA
max.
fuse
(gL/gG)
A
Icu
kA
Ics
kA
max.
fuse
(gL/gG)
A
Icu
kA
Ics
kA
max.
fuse
(gL/gG)
A
Icu
kA
Ics
kA
max.
fuse
(gL/gG)
A
Icu
kA
Ics
kA
max.
fuse
(gL/gG)
A
J7MN-12 0.16 to 0.8 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
1 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
1.25 100 100 -- 100 100 -- 100 100 -- 100 100 -- 2 2 20
1.6 100 100 -- 100 100 -- 100 100 -- 100 100 -- 2 2 20
2 100 100 -- 100 100 -- 100 100 -- 10 10 35 2 2 35
2.5 100 100 -- 100 100 -- 100 100 -- 10 10 35 2 2 35
3.2 100 100 -- 100 100 -- 10 10 40 3 3 40 2 2 40
4 100 100 -- 100 100 -- 10 10 40 3 3 40 2 2 40
5 100 100 -- 100 100 -- 10 10 50 3 3 50 2 2 50
6.3 100 100 -- 100 100 -- 10 10 50 3 3 50 2 2 50
8 100 100 -- 50 12.5 80*3)
*3) Back-up fuse required if short-circuit current at installation point > 50 kA
-- No back-up fuse required.
10 10 63 3 3 63 2 2 63
10 100 100 -- 50 12.5 80*3) 10 10 63 3 3 63 2 2 63
12 100 100 -- 50 12.5 80*3) 10 10 80 3 3 80 2 2 80
J7MN-25 0.16 to 1.25 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
1.6 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
2 100 100 -- 100 100 -- 100 100 -- 100 100 -- 8 8 25
2.5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 8 8 25
3.2 100 100 -- 100 100 -- 100 100 -- 100 100 -- 8 8 32
4 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 3 32
5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 3 32
6.3 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 3 50
8 100 100 -- 100 100 -- 50 25 63*3 42 21 63 6 3 50
10 100 100 -- 100 100 -- 50 25 80*3 42 21 63 6 3 50
12.5 100 100 -- 100 100 -- 50 25 80*3 42 21 80 6 3 63
16 100 100 -- 50 25 100*3) 20 10 80 10 5 80 4 2 63
20 100 100 -- 50 25 125*3) 20 10 80 10 5 80 4 2 63
22 100 100 -- 50 25 125*3) 20 10 100 10 5 80 4 2 63
25 100 100 -- 50 25 125*3) 20 10 100 10 5 80 4 2 63
J7MN-50 25 100 100 -- 50 25 125*3) 30 15 100 12 6 80 5 3 63
32 100 100 -- 50 25 125*3) 30 15 125 10 5 100 4 2 63
40 100 100 -- 50 25 160*3) 30 15 125 10 5 100 4 2 63
45 100 100 -- 50 25 160*3) 30 15 125 10 5 100 4 2 63
50 100 100 -- 50 25 160*3) 30 15 125 10 5 100 4 2 80
J7MN-100
63 100 100 -- 50 25 160*3) 40 20 160 12 6 125 6 3 80
75 100 100 -- 50 25 160*3) 40 20 160 8 4 125 5 3 100
90 100 100 -- 50 25 160*3) 40 20 160 8 4 125 5 3 125
100 100 100 -- 50 25 160*3) 40 20 160 8 4 125 5 3 125
Motor Protection Circuit Breaker (MPCB) J7MN H-77
LVSG
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Main Circuit
Type J7MN-12 J7MN-25 J7MN-50 J7MN-100
Number of poles 3333
Max. rated current Inmax (=max. rated operational current Ie) A122550100
Permissible ambient temperature
Storage/transport °C -50 to +80
Operation °C -20 to +70*1)
*1) Over +60°C current reduction
Permissible rated current at temperature inside cubicle of: +60 °C % 100
+70 °C % 87
Circuit-breaker inside enclosure
Permissible rated current at temperature inside enclosure of: +60 °C % 100
+70 °C % 87
Rated operational voltage Ue V 690*2)
*2) 500 V with moulded-plastic enclosure
Rated frequency Hz 50/60
Rated insulation voltage Ui V 690
Rated impulse withstand voltage Uimp kV 6
Utilization category
IEC 60 947-2 (circuit-breaker) A
IEC 60 947-4-1 (motor starter) AC-3
Class acc. to IEC 60 947-4-1 10
DC short-circuit breaking capacity (time constant t = 5 ms)
1 conducting path DC 150 V kA 10
2 conducting paths in series DC 300 V kA 10
3 conducting paths in series DC 450 V kA 10
Power loss Pv per circuit-breaker
dependent on rated current In
(upper setting range)
In -> to 1.25 A W 5 - - -
In -> 1.6 to 6.3 A W 6 - - -
In -> 8 to 12 A W 7 - - -
R per conducting path = P/(I² × 3) In -> 1 to 6.3 A W - 6 - -
In -> 8 to 16 A W - 7 - -
In -> 20 to 25 A W - 8 - -
In -> to 25 A W - - 12 -
In -> 32 A W - - 15 -
In -> 40 to 50 A W - - 20 -
In -> to 63 A W---20
In -> 75 to 90 AW---30
In -> to 100 A W ---38
Shock resistance acc. to IEC 68 Part 2-27 g 25 25 25 25
Degree of protection acc. to IEC 60 529 IP 20 IP 20 IP 20*3)
*3) Terminal compartment IP00
IP 20*3)
Shock hazard protection acc. to DIN VDE 0106 Part 100 safe against finger touch
Temperature compensation acc. to IEC 60 947-4-1 °C -20 to +60
Phase failure sensitivity acc. to IEC 60 947-4-1 yes
Explosion protection acc. to EC Directive 94191 EC yes*4)
*4) KEMA-test certification on request
Isolator characteristics acc. to IEC 60 947-3 yes
Main and EM. STOP switch characteristics acc. to IEC 60 204-1 (VDE 0113) yes*5)
*5) With appropriate accessories
Safe isolation between main and auxiliary
circuits
acc. to DIN VDE 0106 Part 101
up to 400 V + 10 % yes
up to 415 V+ 5 % yes
Mechanical endurance operating cycles 100 000 100 000 50 000 50 000
Electrical endurance 100 000 100 000 25 000 25 000
Max. operating frequency per hour (motor starts) 1/h 15 15 15 15
Permissible mounting position any. acc. to IEC 60 447 start command “I” right-hand side or top
H-78 Motor Protection Circuit Breaker (MPCB) J7MN
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Technical Data according to IEC/EN 60947-1, 60947-2, 60947-4-1 and VDE 0660
Conductor cross-sections for main Circuit
Type J7MN-12 J7MN-25 J7MN-50 J7MN-100
Terminal type Screw-type Screw-type Box terminal Box terminal
Terminal screw Pozidriv size 2 Pozidriv size 2 Pozidriv size 2 Allen screw 4 mm
Tightening torque Nm 0.8 to 1.2 2 to 2.5 3 to 4.5 4 to 6
Conductor cross-sections
solid mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 16)
mm² 2 x (0.75 to 2.5) 2 x (2.5 to 6)
mm² 1 x (0.5 to 4)
finely stranded with end ferrule mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 16) 2 x (2.5 to 35)
mm² 2 x (0.75 to 2.5) 2 x (2.5 to 6) 1 x (0.75 to 25) 1 x (2.5 to 50)
mm² 1 x (1 to 10)
stranded mm² 2 x (0.5 to 1.5) 2 x (1 to 2.5) 2 x (0.75 to 25) 2 x (10 to 50)
mm² 2 x (0.75 to 2.5) 2 x (2.5 to 6) 1 x (0.75 to 35) 1 x (10 to 70)
mm² 1 x (0.5 to 4) 1 x (1 to 10)
AWG-wires, solid or stranded AWG 2 x (18 to 14) 2 x (14 to 10) 2 x (18 to 3) 2 x (10 to 1/0)
AWG 1 x (18 to 2) 1 x (10 to 2/0)
conductor bar (number x width x thick) mm 2 x (6 x 9 x 0.8) 2 x (6 x 9 x 0.8)
mm 18 x 10
mm² up to 2 x 70
Auxiliary switches
Switching capacity Control voltage
Front transverse auxiliary switch with 1 NO + 1 NC
Rated operational voltage Ue AC V 24 230
Rated operational current Ie/AC-15 A 2 0.5
Rated operational current Ie/AC-12 Ith A 2.5 2.5
Rated operational voltage Ue DC L/R 200 ms V 24 48 60
Rated operational current Ie/DC-13 A 1 0.3 0.15
Lateral auxiliary switch and signalling switch
Rated operational voltage Ue AC V 24 230 400 690
Rated operational current Ie/AC-15 A 6 6 3 1
Rated operational current Ie/AC-12 Ith A 10 10 10 10
Rated operational voltage Ue DC L/R 200 ms V 24 110 220 440
Rated operational current Ie/DC-13 A 2 0.5 0.25 0.1
Undervoltage release Power consumption during pick-up VA/W 20.2/13
uninterrupted duty VA/W 7.2/2.4
Response voltage trip V 0.7 to 0.35 × Us
pick-up V 0.85 to 1.1 × Us
Max. opening time ms 20
Shunt release Power consumption during pick-up AC VA/W 20.2/13
DC W 13 to 80
Response voltage acc. to IEC 60 947-1, trip V 0.7 to 1.1 × Us
Max. opening time ms 20
Short-circuit protection for auxiliary and control circuits
Fuse gL/gG A 10
Miniature circuit breaker C-characteristic A 6*1)
*1) Prospective short-circuit current < 0.4 kA.
Conductor cross-sections for auxiliary and control circuits Screw-type Pozidriv size 2
solid mm² 2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)
finely stranded with ferrule mm² 2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)
stranded mm² 2 x (0.5 to 1.5) / 2 x (0.75 to 2.5)
AWG-wires, solid or stranded AWG 2 x (18 to 14)
Motor Protection Circuit Breaker (MPCB) J7MN H-79
LVSG
Description
J7MN circuit-breakers are compact, current-limiting circuit-breakers
which are optimised for load feeders. The circuit-breakers are used
for switching and protecting three-phase induction motors of up to
18,5 kW at AC 400 V and for loads with rated currents of up to 40 A.
Construction
The circuit-breakers are available in three sizes:
J7MN-12 overall width 45 mm. Max. rated current 12 A. Suitable for
3-phase induction motors of up to 5.5 kW at voltages of 400 V AC.
J7MN-25 overall width 45 mm. Max. rated current 25 A. Suitable for
3-phase induction motors of up to 11 kW at voltages of 400 V AC.
J7MN-50 overall width 55 mm. Max. rated current 40 A. Suitable for
3-phase induction motors of up to 18,5 kW at voltages of 400 V AC.
Releases
Circuit-breakers J7MN are equipped with bimetallic-based, inverse-
time delayed overload releases and with instantaneous overcurrent
releases (electromagnetic short-circuit releases).
The overload releases can be set in accordance with the load cur-
rent. The overcurrent releases are permanently set to a value 13
times the rated current and thus enable trouble-free start-up of
motors.
The scale cover can be sealed to prevent unauthorized adjustments
to the set current.
Operating mechanisms
circuit-breakers J7MN-12 are actuated via a switch operating mecha-
nism and circuit-breakers J7MN-25 and J7MN-50 via a rotary operat-
ing mechanism. If the circuit-breaker trips, the rotary operating
mechanism switches to the tripped position to indicate this. Before
the circuit-breaker is reclosed, the rotary operating mechanism must
be reset to the 0 position by hand, in order to prevent the former from
closing by mistake before the fault has been cleared.
In the case of circuit-breakers with rotary operating mechanisms,
there is an electrical signal via a signalling switch to indicate that the
circuit-breaker has tripped.
All operating mechanisms can be locked in the 0 position with a pad-
lock (shackle diameter 3.5 to 4.5 mm).
The J7MN circuit-breakers fulfil the isolation characteristics specified
in IEC 60 947-2.
Operating conditions
Circuit-breakers J7MN are suitable for use in any climate. They are
designed for operation in enclosed rooms under normal conditions
(e. g. no dust, corrosive vapours or harmful gases). Suitable enclo-
sures must be provided for installation in dusty or damp rooms.
Circuit-breakers J7MN can also be fed from below. The standards in
accordance with which the circuit-breakers are constructed, the per-
missible ambient temperatures, the maximum making and breaking
capacities, the tripping currents and other boundary conditions can
be found in the technical data and tripping characteristics.
Since the operational currents, starting currents and current peaks
vary as a result of the inrush current, even in the case of motors with
identical output ratings, the values specified for these output ratings
in the selection tables are intended as a guide only. The specific
rated and start-up data of the motor to be protected is always para-
mount to the choice of the most suitable circuit-breaker.
In order to prevent premature tripping due to phase failure sensitivity,
the circuit-breakers should always be connected in such a way that
current flows through all three main conducting paths.
Short-circuit protection
The short-circuit releases of J7MN circuit-breakers disconnect the
faulty load feeder from the system in the event of a short circuit and
thus prevent any further damage.
Circuit-breakers with a short-circuit breaking capacity of 50 kA or
100 kA at a voltage of 400 V AC are practically short-circuit-proof at
this voltage, as higher short-circuit currents are not usually encoun-
tered at the installation point.
Back-up fuses are only necessary if the short-circuit current at the
installation point exceeds the rated ultimate short-circuit breaking
capacity of the circuit-breakers.
Motor protection
The tripping characteristics of J7MN circuit-breakers are designed
mainly to protect three-phase induction motors. The circuit-breakers
are therefore also referred to as motor circuit-breakers. The current
of the motor to be protected is set with the aid of the scale.
Circuit-breakers with thermal overload releases are normally
designed in accordance with release Class 10.
Line protection
J7MN circuit-breakers for motor protection are also suitable for line
protection. In order to prevent premature tripping due to phase failure
sensitivity, the three conducting paths must always be uniformly
loaded. The conducting paths must be connected in series in the
case of single-phase loads.
The J7MN circuit-breakers meet the isolation conditions of
IEC 60 947-3 as well as the additional test conditions for circuit-
breakers with isolation characteristics specified in IEC 60 947-2. Tak-
ing IEC 60 204-1 into consideration, they can thus be implemented
as main and EMERGENCY STOP switches.
Door-coupling rotary operating mechanism do not fulfil the isolation
characteristics specified in IEC 60 947-2. Door-coupling rotary oper-
ating mechanism according isolation characteristics specified in
IEC 60 947-2 on request.
H-80 Motor Protection Circuit Breaker (MPCB) J7MN
Characteristics
The time/current characteristic, the current limiting characteristics
and the I²t characteristics were determined in accordance with
DIN VDE 0660 and IEC 60 947.
The tripping characteristic of the inverse-time delayed overload
releases (thermal overload releases or ’a’ releases) for DC and AC
with a frequency of 0 to 400 Hz also apply to the time/current charac-
teristic.
The characteristics apply to the cold state. At operating temperature,
the tripping times of the thermal releases are reduced to approxi-
mately 25 %.
Under normal operating conditions, all three poles of the device must
be loaded. The three main conducting paths must be connected in
series in order to protect single-phase or DC loads.
With 3-pole loading, the maximum deviation in the tripping time for 3
times the setting current and upwards is ± 20 % and thus in accor-
dance with DIN VDE 0165.
The tripping characteristics for the instantaneous, electromagnetic
overcurrent releases (short-circuit releases or ’n’ releases) are based
on the rated current In, which is also the maximum value of the set-
ting range for circuit-breakers with adjustable overload releases. If
the current is set to a lower value, the tripping current of the ’n’
release is increased by a corresponding factor.
The characteristics of the electromagnetic overcurrent releases
apply to frequencies of 50/60 Hz. Appropriate correction factors must
be used for lower frequencies up to 16 2/3 Hz, for higher frequencies
up to 400 Hz and for DC.
The characteristic shown here is a schematic representation of cir-
cuit-breakers for all ranges.
Time/current characteristics, current limiting characteristics and I²t
characteristics are available on request.
Wiring diagrams
Opening Time
Current
2-pole
load
Class 10
3-pole
load
Class 10
Circuit-breaker Transverse auxiliary contact block Lateral auxiliary contact block
J7MN J73MN-11F J73MN-11S
Signalling switch Undervoltage release Shunt release
J73MN-T-11S J74MN-U J74MN-S
Motor Protection Circuit Breaker (MPCB) J7MN H-81
LVSG
Dimensions
Circuit-breaker J7MN-12 Circuit-breaker J7MN-25
Circuit-breaker J7MN-50
1) Lateral aux. contact
2) Signalling contact
3) Auxiliary release
4) Transverse aux. contact
7) Mounting holes
8) 35mm DIN-rail
9) 35mm DIN-rail 15mm high or
75mm DIN-rail
10) 4mm hexagon socket screw
11) Lockable in 0-position
with shackle diameter max.5mm
Circuit-breaker J7MN-100
1) Lateral aux. contact
2) Signalling contact
3) Auxiliary release
4) Transverse aux. contact
7) Mounting holes
8) 35mm DIN-rail
9) 35mm DIN-rail 15mm high or
75mm DIN-rail
10) 4mm hexagon socket screw
11) Lockable in 0-position
with shackle diameter max.5mm
H-82 Motor Protection Circuit Breaker (MPCB) J7MN
Moulded plastic front plate J74MN-P12 Moulded plastic front plate J74MN-P25
Moulded plastic enclosure J74MN-PF12
Door-coupling rotary operating mechanism J74MN-DC
1) Max. for shackle diameter for
padlock 8 mm
3-phase busbar J74MN-L3-#/#
for J7MN-12 and J7MN-25, modular spacing 45 mm
3-phase line-side terminal J74MN-TC12 and J74MN-TC25
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J508-E2-02
Appendix H-83
LVSG
Appendix
Precautions
Notice
Use under rated condition, otherwise contactors will not only cause
malfunction, but also cause a fire or damage the contactor.
Life period of contactor depends on the operating application. Please
check the electrical life under real application in advance.
If you continue to use malfunctioning contactor, a fire or breakdown
may occur.
Do not miss-wire or miss-charge the power supply, otherwise the
contactor does not work correctly.
Do not operate in places with explosive or flammable gas, otherwise
a fire or explosion may occur by arc or heating from contactor.
Make sure to use the circuit well considered about safety, in case
there is any possibility to cause secondary disaster by contact trou-
ble (welding, faulty contact).
Do not supply short-circuit current to electromagnetic switch (contac-
tor with thermal relay). Doing so may result failure in heater of ther-
mal relay. Please use short-circuit protection like fuse or protective
circuit breaker.
Do not use a contactor or thermal relay which has been dropped or
dismantled. Doing so may cause malfunction or a fire.
Make sure to shut off power supply to contactors before wiring or
replacing.
Do not operate the actuator of a contactor manually. Doing so may
cause contact welding by chattering or burn out by arc.
Correct use
General use
Unexpected malfunction may occur in real application. Please carry
out as many tests as possible.
Ratings in this catalogue measured under the condition according to
IEC unless otherwise specified. In cases of check by real application,
please carry out the test under the same condition as expected in the
actual application.
Selection
Coil specification
Please select suitable coil to circuit design, otherwise malfunction
may occur or coil may have a burn out by overvoltage etc.
Type
Please check contact ratings, switching capacity, thermal character-
istics etc. when selecting product type.
Thermal relay
Motor current differs by supplier, type, number of poles, frequency.
Please confirm operational current level.
Coil surge suppressor
Coil surge suppressor type should be selected by contactor type,
auxiliary relay type and applied voltage. Make sure to use defined
each contactor.
In case of installing coil surge suppressor, please check the actual
circuit because the release time will be delayed.
Electrical life expectancy
Electrical life expectancy tests in this catalogue are based on IEC.
Circuit design
Supplied voltage waveform for input
Make sure to apply and remove the voltage instantly. Do not use
under the condition that the coil voltage waveform increases or
decreases gradually.
In case of DC contactor use (input voltage
ripple)
Please use DC contactor input voltage with a ripple ratio less than
5%. Excessive ripple (pulsating current) may cause contact welding.
Fluctuation of input voltage
Make sure to supply sufficient voltage to actuate contactors properly.
Continuous supply of insufficient voltage results in excessive heating
and may cause burn out of coil.
Maximum applied voltage
Do not supply the voltage over the maximum rated voltage, otherwise
burn out or insulation failure may occur.
The temperature inside control panel has much influence to the coil
temperature, so make sure not to exceed the specified value in the
catalogue.
Basically rated voltage should be supplied to coil. To supply higher
voltage than rated would result in shorter electrical life, even if it is
lower than the maximum rated voltage.
Reverse
Make sure to use reversible contactors for reverse operation.
Make sure to use interlock device in reverse operation by two contac-
tors, otherwise short circuit current may burn out or give damage to
contactors and motors.
Unless otherwise stated in the catalogue,
modifications, especially those of stated values,
sizes and weights are subject to alternation.
Diagrams and tables are subject to alternation and
not to be regarded as binding drawings.
H-84 Appendix
Installation
Mounting
Make sure to use specified wire size, mounting screw size, mounting
screw number, and DIN rail size.
Tightening Screw
Tighten each screw securely by specified tightening torque. Loose
tightening may cause a fire by excessive heating.
Combination
Please use only OMRON product combinations in case of thermal
relay, timer block and auxiliary contact block etc.
Wrong-combinations may result in damage to contactors.
Mounting direction
Some products have a defined specific mounting direction. Please
refer to datasheet before use.
Operation ambience
Dust
Dust on the surface of the contacts could result in contact malfunc-
tioning. Take countermeasure in excessive dusty surrounding.
Temperature, humidity
Use contactors within the temperature and humidity conditions spec-
ified in datasheet. To use or store contactor in excessive temperature
or humidity may result in malfunction of contact by organic film com-
posed by sulfication and oxidation on the surface of the contacts.
Use contactors within the temperature and humidity conditions spec-
ified in the datasheet, to prevent contactors from insulation resis-
tance failure by condensation or insulation resistance deterioration
by tracking.
Gas
NH3, H2S, SO2, CI2, Si and NO2 have bad effects on a contactor.
With these gases, a corrosive metal film ist generated on the surface
of the contacts and could result in contact malfunctioning. Use a con-
tactor in low humidity and no corrosive gas surroundings.
Oil
Do not use a contactor in places where oil is sprayed onto the con-
tactor. It will cause cracks on polymer parts.
Shock and vibration
Do not use a contactor in places where there is excessive shock or
vibration. It may cause malfunctioning.
Storage
Store contactors in a place with no direct sunshine or ultraviolet rays.
It will cause crack on polymer parts.
When contactors are to be stored for a long time, they must be stored
with care. Though it generally depends where contactors are stored,
deterioration of contacts may occur after long storage. Please check
the characteristics before use after long time storage.
Appendix H-85
LVSG
European Standards
IEC 947, EN 60947
European Standards for Low-Voltage Switchgear
For Europe and most other industrial countries of the world, the new
IEC 947 and EN 60 947 specifications for low-voltage switchgear
have unified the regulations which previously varied from nation to
nation.
This required the introduction of new terms, and new test methods
and utilization categories. The new specifications are aimed
primarily at manufacturers. However, the user also will come across
new technical terms and data in the manufacturers’ catalogues
and on the devices themselves which are important for the selection
and application of the devices. The present paper deals with the cur-
rently published specifications. Further specifications and
supplements are in preparation.
Since 1993, all low-voltage switchgear purchased in Europe had to
satisfy the EN 60 947 European Standard. Installations in existence
prior to 1993 are not affected by the standard and need not to be
refitted with new devices. Devices constructed and tested to the IEC
standards and EN standards can be used worldwide, with the excep-
tion of the USA and Canada. In these countries UL and CSA specifi-
cations continue to apply. Switchgear which conforms to IEC 947
and EN 60 947 and which has, in addition, UL- and CSA approvals,
in the meantime has entered the market. Such ‘world market’ devices
offer the advantage that they can be used throughout the world,
including the USA and Canada.
Conditions for compliance with
Type 1 coordination
(Extract from IEC 947-4-1)
- The contactor or the starter must not endanger
personnel or equipment in the event of a short
circuit
- The contactor or the starter does not need to be
suitable for continued operation without repair and
replacement of parts
- Damage to the contactor and the overload relay is
permissible
Conditions for compliance with
Type 2 coordination
(Extract from IEC 947-4-1)
- The contactor or the starter must not endanger
personnel or equipment in the event of a short
circuit
- The contactor or the starter must be suitable for
further use
- No damage may occur to the overload relay or
other parts, with the exception of welding of the
contactor or starter contacts, provided they can
be separated easily without any significant
deformation (e.g. using a screwdriver)
Rated conditional
short-circuit current lq
- The rated conditional short-circuit
current lq indicates the max. short-
circuit breaking capacity of the starter
Rated operation current le
- The rated operational current le for
the starter is the current when the
starter is in the On position
Rated uninterrupted current lu
(to IEC 947-1)
- The rated uninterrupted current lu of
a unit is a current, specified by the
manufacturer, which the unit can
carry without interruption
IEC 947
IEC 947-1 General rules
IEC 947-2 Circuit-breakers
IEC 947-3 Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 947-4-1 Connectors and motor-starters
IEC 947-5-1 Control circuit devices and switching elements
IEC 947-6-1 Multiple function equipment, Automatic transfer switching equipment
IEC 947-6-2 Multiple function equipment, Control and protective switching devices (or equipment)
(CPS)
IEC 947-7-1 Ancillary equipment
H-86 Appendix
Overview
The following table shows in summarized form both the previous and the new IEC, EN and DIN VDE standards.
Switches, disconnectors, switch-disconnectors and fuse combination units
(IEC 947-3, EN 60947-3)
These devices must now be labelled with the product function designated by the manufacturer. This means placing clearly visible symbols on the
device itself.
Devices with an isolating function are subject to special safety requirements. They must for example have greater creepage distances and clear-
ances across the opened contacts than is necessary for other devices.
Device functions and corresponding symbols
OMRON equipment is designed for the world’s markets
It is manufactured and tested in accordance with national and international specifications, the most important of which are listed below:
IEC 947-..., EN 60947: Low-voltage switch gear and control gear
IEC 664: Insulation co-ordination including clearances and creepage distances for equipment
IEC364: Electrical installations of buildings
IEC 204-..., EN 60204-...: Electrical equipment of industrial machines
DIN VDE 0105: Operation of electrical power installations
IEC 536: Protection against electric shock
Previous specification New specification
Content
IEC DIN VDE IEC EN 60947
DIN VDE
- - 947-1 60947-1
0660, Part 100
Low-voltage switchgear,
General rules
157 0660, Part 101 947-2 60947-2
0660, Part 101
Low-voltage switchgear,
Circuit-breakers
406 0660, Part 107 947-3 60947-3
0660, Part 107
Low-voltage switchgear,
Switches,
Disconnectors,
Switch-disconnectors,
Fuse-combination units
158
292-1
292-2
292-3
0660, Part 102
0660, Part 104
0660, Part 106
0660, Part 301
947-4-1 60947-4-1
0660, Part 102
Low-voltage switchgear,
Control circuit devices and switching elements
337 0660 Part 200 to Part 205 947-5-1 60947-5-1
0660, Part 200
Low-voltage switchgear,
Multiple-function equipment,
Automatic transfer switching equipment
- - 947-6-1 60947-6-1
0660, Part 114
Low-voltage switchgear,
Multiple-function equipment,
Control and protective switching devices (CPS)
- 0611 Part 1 and 2 947-7-1 60947-7-1
0611, Part 1
Low-voltage switchgear,
Ancillary equipment (e.g. terminal blocks)
Making/breaking Isolating Making/breaking
+ isolating
Switch Disconnector Switch-disconnector
Switch-fuse Disconnector-fuse Switch-disconnector-fuse
Fuse-switch Fuse-disconnector Fuse switch-disconnector
Appendix H-87
LVSG
Note 1: cos ϕ = 0.45 for Ie 100 A; cos ϕ = 0.35 for Ie > 100 A.
2: The tests are to be carried out with an incandescent light load.
3: The test data are to be derived from the test values for AC-3 or AC-4 according to
Table VIIb, EN 60947-4-1.
4: AC-3 category may be used for occasional inching (jogging) or plugging for limited
time periods such as machine set-up; during such limited time periods the number
of such operations should not exceed five per minute or more than ten in a ten
minute period.
5: A hermetic refrigerant compressor motor is a combination consisting of a compres-
sor and a motor, both of which are enclosed in the same housing, with no external
shaft or shaft seals, the motor operating in the refrigerant.
Note 1: The value “6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, viz 6 x P = 300 ms. Loads having power
consumption greater than 50 W are assumed to consist of smaller loads in parallel. Therefore, 300 ms is to be an upper limit, irrespective of the power consumption value.
Utilization categories for contactors to IEC 947-4-1 and EN 60947
Type of
current
Utilization
category
Typical examples of application
I = current made, Ic = current broken
Ie = rated operational current
U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage
Verification of electrical endurance Verification of rated making and breaking capacities
Make Break Make Break
Ie
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕIe
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕ
AC
AC-1 Non-inductive or slightly inductive loads, resistance
furnaces All values 1 1 0.95 1 1 0.95 All values 1.5 1.05 0.8 1.5 1.05 0.8
AC-2 Slip-ring motors: starting, switching off All values 2.5 1 0.65 2.5 1 0.65 All values 4 1.05 0.65 4 1.05 0.65
AC-3 Squirrel-cage motors: starting, switching off motors
during running4
Ie 17
Ie > 17
6
6
1
1
0.65
0.35
1
1
0.17
0.17
0.65
0.35
Ie 100
Ie > 100
10
10
1.05
1.05
0.45
0.35
8
8
1.05
1.05
0.45
0.35
AC-4 Squirrel-cage motors: starting, plugging, inching Ie 17
Ie > 17
6
6
1
1
0.65
0.35
6
6
1
1
0.65
0.35
Ie 100
Ie > 100
12
12
1.05
1.05
0.45
0.35
10
10
1.05
1.05
0.45
0.35
AC-5A Switching of electric discharge lamp controls - - - - - - - - 3.0 1.05 0.45 3.0 1.05 0.45
AC-5B Switching of incandescent lamps - - - - - - - - 1.521.05 2)1.5
21.05 2)
AC-6A3 Switching of transformers As given by the manufacturer - - - - - - -
AC-6B3Switching of capacitor banks As given by the manufacturer - - - - - - -
AC-7A Slightly inductive loads in household appliances and
similar applications As given by the manufacturer - 1.5 1.05 0.8 1.5 1.05 0.8
AC-7B Motor-loads for household applications As given by the manufacturer - 8.0 1.05 1)8.01.05
1)
AC-8A Hermetic refrigerant compressor motor control with
manual resetting of overload releases5As given by the manufacturer - 6.0 1.05 1)6.01.05
1)
AC-8B Hermetic refrigerant compressor motor control with
automatic resetting of overload releases5As given by the manufacturer - 6.0 1.05 1)6.01.05
1)
Ie
A
I
-
Ie
U
-
Ue
L/R
ms
Ic
-
Ie
Ur
-
Ue
L/R
ms
Ie
A
I
-
Ie
U
-
Ue
L/R
ms
Ic
-
Ie
Ur
-
Ue
L/R
ms
DC
DC-1 Non-inductive or slightly inductive loads, resistance
furnaces All values 1 1 1 1 1 1 All values 1.5 1.05 1 1.5 1.05 1
DC-3 Shunt motors: starting, plugging, inching, dynamic
braking All values 2.5 1 2 2.5 1 2 All values 4 1.05 2.5 4 1.05 2.5
DC-5 Series motors: starting, plugging, inching, dynamic
braking All values 2.5 1 7.5 2.5 1 7.5 All values 4 1.05 15 4 1.05 15
DC-6 Switching of incandescent lamps - - - - - - - - 1.5
2)1.05 2)1.5
2)1.05 2)
Utilization categories for control switches to IEC 947-5-1 and EN 60947
Type of
current
Utilization
category
Typical examples of application
I = current made, Ic = current broken
Ie = rated operational current
Ue = rated operational voltage
Ur = recovery voltage
U = voltage before make
t0.95 = time in ms to reach 95 % of the steady-state
current
P = Ue x Ie = rated power consumption in watts
Normal conditions of use Abormal conditions of use
Make Break Make Break
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕI
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕ
AC AC-12 Control of resistive and solid state loads as in opto-
coupler input circuits 110.9110.9 ------
AC-13 Control of solid state loads with transformer isolation 2 1 0.65 1 1 0.65 10 1.1 0.65 1.1 1.1 0.65
AC-14 Control of small electromagnetic loads ( 72 VA) 6 1 0.3 1 1 0.3 6 1.1 0.7 6 1.1 0.7
AC-15 Control of electromagnetic loads (> 72 VA) 10 1 0.3 1 1 0.3 10 1.1 0.3 10 1.1 0.3
I
-
Ie
U
-
Ue
t0.95
Ic
-
Ie
Ur
-
Ue
t0.95
I
-
Ie
U
-
Ue
t0.95
Ic
-
Ie
Ur
-
Ue
t0.95
DC DC-12 Control of resistive and solid state loads as in opto-
coupler input circuits 111 ms111 ms ------
DC-13 Control of electromagnets 1 1 6xP1)1 1 6xP
1)1.11.16xP
1)1.1 1.1 6xP
1)
DC-14 Control of electromagnetic loads having economy
resistors in circuits 10 1 15 ms 1 1 15 ms 10 1.1 15 ms 10 1.1 15 ms
Utilization categories for switches, disconnectors, switch-disconnectors, and fuse combination units to IEC 947-3 and EN 60947
Type of
current
Utilization
category
Typical applications
I = current made, Ic = current broken
Ie = rated operational current
U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage
Verification of electrical endurance Verification of switching capacity
Make Break Make Break
Ie
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕIe
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕ
AC AC-20
A(B)2
Connecting and disconnecting under no-load condi-
tions All values 1)1)1)1)1)1) All values 1)1.05
1)1)1.05
1)
AC-21
A(B)2
Switching of resistive loads, including moderate
overloads All values 1 1 0.95 1 1 0.95 All values 1.5 1.05 0.95 1.5 1.05 0.95
AC-22
A(B)2
Switching of mixed resistive and inductive loads, in-
cluding moderate overloads All values 1 1 0.8 1 1 0.8 All values 3 1.05 0.65 3 1.05 0.65
H-88 Appendix
Note 1: If the switching device has a making and/or breaking capacity, the figures for the current and the power factor (time constants) must be stated by the manufacturer.
2: A: frequent operation, B: infrequent operation.
Protection against electrical shock, to IEC 536
IEC 536 covers the setting up of electrical apparatus, and its
arrangement in electrical installations with rated voltages up to 1000
VAC and 1500 VDC, with regard to protection against direct contact
where operating elements such as push-buttons and switches are
located in the vicinity of live parts.
“Finger-proofing” relates only to the operating device, and only in the
normal direction of operation. A clearance of at least 30 mm radius
from the centre point of the device to any live parts, must be ensured.
The IP 20 degree of protection is superior to “finger-proofing” in that
it embodies protection against contact with electrical apparatus in
any direction. Devices which are “finger-proof” and of IP 00 degree of
protection can be provided with further protection against contact in
the form of shrouding, if so desired.
Damp heat, constant, to IEC 68 Part 2-3
In this test, the effects of a constant high level of humidity
(93 +2/-3%) and a constant temperature (40 ±2)°C over a prescribed
duration, are observed.
Damp heat, cyclic, to IEC 68 Part 2 - 30, Test Db
This test is used to assess the suitability of electrical products for
operation and storage at high relative humidity levels, in conjunction
with cyclic temperature fluctuation. A test cycle consists of 12 hours
at 40 ±2°C, with relative humidity of 93 ±3%, and 12 hours at
25 ±3°C, with the relative humidity of at least 95%.
Ambient temperature
Ambient temperature is the temperature of the room (e.g. factory bay
or switchgear room), in which the open or enclosed device is
installed, a prerequisite being that this temperature is not significantly
influenced by the heat losses from the device.
AC-23
A(B)2
Switching of motor loads or other highly inductive
loads All values110.65110.65
Ie 100
Ie > 100
10
10
1.05
1.05
0.45
0.35
8
8
1.05
1.05
0.45
0.35
Ie
A
I
-
Ie
U
-
Ue
L/R
ms
Ic
-
Ie
Ur
-
Ue
L/R
ms
Ie
A
I
-
Ie
U
-
Ue
L/R
ms
Ic
-
Ie
Ur
-
Ue
L/R
ms
DC DC-20
A(B)2
Connecting and disconnecting under no-load condi-
tions All values 1)1)1)1)1)1)All values
1)1.05
1)1)1.05
1)
DC-21
A(B)2
Switching of resistive loads, including moderate
overloads All values111111All values1.51.0511.51.051
DC-22
A(B)2
Switching of mixed resistive and inductive loads, in-
cluding moderate overloads (e.g. shunt motors) All values112112All values41.052.541.052.5
DC-23
A(B)2
Switching of highly inductive loads (e.g. series mo-
tors) All values 1 1 7.5 1 1 7.5 All values 4 1.05 15 4 1.05 15
Utilization categories for switches, disconnectors, switch-disconnectors, and fuse combination units to IEC 947-3 and EN 60947
Type of
current
Utilization
category
Typical applications
I = current made, Ic = current broken
Ie = rated operational current
U = voltage before make
Ue = rated operational voltage
Ur = recovery voltage
Verification of electrical endurance Verification of switching capacity
Make Break Make Break
Ie
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕIe
A
I
-
Ie
U
-
Ue
cos ϕIc
-
Ie
Ur
-
Ue
cos ϕ
Appendix H-89
LVSG
Glossary of standard terms
This Glossary offers brief expIanations of some of the standard
terms used in this catalogue. However, it must not be regarded as a
substitute for the actual text of the standard, especially where the
new terms used in IEC 947 are concerned.
Reference is therefore made aIongside each such term to the reIev-
ant section of the standard, e.g. IEC 947-1 in addition, IEV numbers
are given to enable you to find foreign language equivalents in the
International EIectrotechnicaI Vocabulary
(IEG 50), if required.
Rated conditional short-circuit current Iq
(IEC 947-1; 2.5.29/IEV 441-17-20)
The prospective current which a switching device, e.g. a circuit-
breaker, protected by a short-circuit protective device such as a
motor-protective circuit-breaker, can carry for the duration of the pro-
tective device tripping time.
Mininum command time
Minimum duration for a trip-initiating factor (controI puIse, short cir-
cuit) to effect the corresponding reaction, e.g. the short-circuit dura-
tion necessary to initiate tripping.
Rated breaking capacity
(IEC 947-1; 4.3.5.3)
The r.m.s. value of current which a switching device is capable of
breaking according to its utiIization category. The rated breaking
capacity is stated by reference to the rated operational voltage and
the rated operational current.
The equipment must be capable of breaking any value of current up
to and incIuding its rated breaking capacity stated.
Rated actuating voltage Uc
(rated control circuit voltage)
(IEC 947-1; 4.5.1)
The voltage which is applied to the actuating make contact in a con-
trol circuit. Due to the presence in the controI circuit of transformers
or resistors, this voltage may differ from the rated control supply volt-
age.
Rated service short-circuit breaking capacity Ics
(IEC 947-2; 4.3.5.2.2)
The prospective short-circuit current which, depending on the rated
operationaI voltage, a circuit-breaker is capable of breaking repeat-
edly (test cycle: O - CO - CO; previousIy P-2). After interrupting this
current vaIue, the circuit-breaker must be capable, despite its own
thermal level having increased, of continuing to carry and disconnect
in the event of overIoading, the rated uninterrupted current.
Rating or rated power
(IEC 947-1; 4.3.2.3)
The rated operational power which an equipment is capable of
switching at the associated rated operational voItage in accordance
with the utilization category.
For example:
motor contactor utilization category AC-3: 37 kW at 400 V.
Rated operational voltage Ue
(IEC 947-1; 4.3.1.1)
The voItage to which the characteristics of an equipment are
referred. The rated operational current must not in any case exceed
the rated insulation voltage.
Rated operational current Ie
(IEC 947-1; 4.3.2.3)
The current which an equipment is capabIe of carrying taking into
account the rated operational current, duration of operation, utiliza-
tion category and ambient temperature.
Rated uninterrupted current Iu
(IEC 947-1; 4.3.2.4)
The vaIue of current which an equipment can carry in uninterrupted
duty (i.e. for weeks, months or years).
Rated making capacity
(IEC 947-1; 4.3.5.2)
The vaIue of current which an equipment is capabIe of switching On
in accordance with the utilization category and at the rated opera-
tional voltage.
Rated frequency
(IEC 847-1; 4,3.3)
The frequency for which an equipment is designed and to which the
other characteristic vaIues are referred.
Rated ultimate short-circuit breaking
capacity Icu
(IEC 947-2; 4.3.5.2.1)
The maximum prospective fault current which a circuit-breaker is
capable of interrupting
(test cycIe: O - CO; previously P-1)
Rated insulation voltage Ui
(IEG 947-1; 4.3.1 .2)
The voltage to which insulation tests and creepage distances of an
equipment are referred. The maximum operationaI voltage must not
in any case exceed the rated insulation voltage.
Rated short-circuit breaking capacity Icn
(IEC 947-1; 4.3.6.3)
The maximum value of current which an equipment is capable of
switching Off at rated operational voItage and rated frequency, and
without sustaining damage. It is expressed as r.m.s. value.
Motor rating
(IEC 947-1; 4.3.2.3)
Power output of a motor at the associated operational voltage.
Rated control supply voltage Us
(IEC 947-1; 4.5.1)
The voltage applied to the input terminals of the control circuit of an
equipment. Due to the presence of transformers or resistors in the
control circuit, this may differ from the rated actuating (control circuit)
voltage.
H-90 Appendix
Rated impulse withstand voltage Uimp
(IEC 947-1; 4.3.1 .3)
Measures the stability of the internal clearances of an equipment
against overvoltage peaks. The utilization of suitable switchgear can
ensure that overvoltages are prevented from transferring from the
mains to deenergized system sections within it.
Rated current In
(of a circuit-breaker)
(IEC 947-2; 4.3.2.3)
For circuit-breakers, this current value is equal to the uninterrupted
current and the conventional free air thermaI current.
Protection against direct contact
Design measures incorporated into equipment in order to prevent
direct contact, i.e. without tools, with live parts of a system (finger
proof, back-of-hand proof).
Control circuit reliability
Measures the probability of switching states arising during the
lifespan of a contact, which would be interpreted as faults by down-
stream electronic controllers (PLCs). Control circuit reliability is
expressed in values based on tests using standard limit values for
signal inputs.
Damp heat, constant
This test subjects the equipment to an ambient temperature of 40°C
at a constant humidity of 93%. At set intervals during the test, the
electrical and mechanical function of the equipment are examined.
Damp heat, cyclic
This test subjects the equipment to cyclically changing climatic con-
ditions: a cycle applies 40°C ambient temperature at 93% relative
humidity for 12 hours, followed by 12 hours of 25°C at 95% relative
humidity. At set intervals during the test, the electrical and mechani-
cal function of the equipment are examined.
Finger proof
An equipment whose live parts cannot be touched by the operator
during actuation is termed finger proof. This also affects operator
activity on neighbouring switching devices. The finger proof area of a
push-actuated operating medium is a circular area of at least 30 mm
radius around the actuating element, and vertical to the direction of
actuation.
Within this circular area, touch-critical parts must be located at not
less than 80 mm depth under the actuating level.
Utilization category
(IEC 947-1; 2.1 .18/IEV 441-17-19)
A combination of specified requirements relating to the condition in
which the switching device or the fuse fulfills its purpose, selected to
represent a characteristic group of practical applications. The speci-
fied requirements may concern, e.g. the values of making capacities,
breaking capacities and other characteristic values, data concerning
associated circuits, and the relevant conditions of use and behaviour.
(IEC 947-2; 4.4)
For circuit-breakers, the utilization category denotes whether the
equipment is designed for selectivity using time delay (category B) or
not (category A).
Back-of-hand proof
An equipment whose live parts cannot be touched by a sphere of
50 mm diameter, is regarded as back-of-hand proof.
Altitude
The density of air decreases with increasing altitude, and this
reduces its insulating capacity as well as its heat transfer capability.
The rated operational voltage and current of switching devices, con-
ductors and motors as well as the tripping behaviour of thermal over-
load relays are affected by this.
Upon request, OMRON ELECTRONICS will supply information as to
the suitability or otherwise of switchgear for operation at altitudes
above the 2000 m limit specified by the standard.
Conventional free air thermal current
(IEC 947-1; 4.3.2.1)
The maximum value of current which an equipment is capable of car-
rying for a minimum of eight hours without thermal overloading. As a
rule, it corresponds to the maximum operational current.
Creepage path
(IEC 947-1; 2.5.51/IEV 151-03-37)
The shortest distance along the surface of the insulating material
between two conductive parts. The creepage distance is determined
by the rated insulation voltage, the pollution degree and the creep-
age current resistance of the material used.
Clearance
(IEC 947-1; 2.5.46/IEV 441-17-31)
The distance between two conductive parts along a string stretched
the shortest way between these conductive parts. The clearance in
air is determined by the rated impulse withstand voltage, overvoltage
category and pollution degree.
Appendix H-91
LVSG
Emergency-stop switching device
Switching device within an emergency-stop circuit which is intended
to prevent danger to persons, damage to machinery or working
materials.
Opening delay
(IEV 441-17-36)
The interval of time between the specified instant of initiation of the
opening operation and the instant when the arcing contacts have
separated in all poles. The opening time is the sum of the tripping
time and the inherent delay of the contacts.
Closing delay
The interval of time between the instant of command and the first
make operation of the contacts of the first pole to close. The closing
delay is made up of the response delay and the closing time.
Shock resistance
The capacity of an equipment to withstand pulse-like motions without
changing its operating status or sustaining damage. No contact lifting
must take place on devices in the On position, the main contacts
must not knock against each other in the Off position. A safety switch
must not trip, and control circuit switches must not change their
switching status.
Safe isolation
(IEC 536, DIN VDE 0106 Part 101)
Isolation of circuits not carrying dangerous voltages (e.g. protective
extra-low voltage) from circuits in which dangerous voltages flow.
Such isolation is achieved by means of reinforced or double insula-
tion which reliably prevents voltage transfer from one circuit to
another. This might otherwise take place between main circuits and
control circuits in switching devices or between transformer primary
and secondary. ”Safe isolation” is a priority requirement for safety cir-
cuits and functional low-voltage circuits.
Isolating function
(IEC 947-1; 2.1.19)
Equipments are deemed to possess this isolating function provided
their switching contacts when in the open position, achieve the sepa-
ration distance prescribed for the isolation of electrical circuits, and
their creepage paths and clearance distances are of the required
size. The power supply to the entire installation or a section of the
installation can thus be cut off for safety reasons, e.g. during mainte-
nance.
Tamper proof
An emergency-stop switching device is regarded as tamper proof
provided it cannot be reset without tools or via a prescribed proce-
dure, after tripping has taken place. The device latches in the tripped
position. Accidental or deliberate manipulation (inching) is thus ruled
out.
Overvoltage category
(IEC 947-1; 2.5.60)
Conventional number for prospective overvoltages at the point of
installation, as might be caused for example by the effect of lightning
or switching processes. The overvoltage category applicable to
industrial switchgear is III. The applicability of switchgear according
to the overvoltage categories is defined as follows:
Overvoltage category IV:
Use allowed directly at the termination point of the installation
(directly affected by any lightning), e.g. at an overhead line connec-
tion point.
Overvoltage category III:
Operating media with special requirements as to the serviceability for
connection in fixed installations, which are protected by overvoltage
diversion measures, e.g. circuit-breakers in low-voltage distribution
systems or in control systems for industrial use.
Overvoltage category II:
Power consumers for connection to fixed installations, e. g. house-
hold appliances, electrical tools.
Overvoltage category I:
Operating media for connection to circuits containing overvoltage
protection schemes, e.g. electronic devices.
Ambient temperature, open
(IEV 441-11-13)
Room temperature for example of the workshop or switch room in
which the switching device is located.
Ambient temperature, enclosed
(IEV 441-11-13)
Temperature at which the switching device is capable of being oper-
ated within a closed housing. For this purpose, it must be taken into
account that the heat losses of the device will add to the internal tem-
perature rise within the enclosure.
Losses
(IEV 151-03-18)
The difference between the input power and the output power of a
device. The main type of loss in electrical power distribution switch-
gear and operating media is current heat loss.
Pollution degree
(IEC 947-1; 6./1.3.2)
Conventional number for the prospective quantities of conductive
dust and humidity which can lead to a reduction in the control circuit
reliability of a device. The pollution degree is described by the follow-
ing influencing factors:
Pollution degree 1:
No pollution or only dry, non-conductive pollution occurs. The pollu-
tion does not affect the control circuit reliability.
Pollution degree 2:
Usually, only non-conductive pollution. However, transient conductiv-
ity through condensation is to be expected.
Pollution degree 3: (switchgear for industrial use)
Conductive pollution or dry, non-conductive pollution which is ren-
dered conductive through condensation.
Pollution degree 4:
The pollution leads to long-term conductivity, e.g. pollution by con-
ductive dust, rain or snow.
H-92 Appendix
Coordination type
Status of a switchgear combination (motor starter) during and after
testing at rated conditional current:
Coordination Type “1“:
- No risk to persons or installations
- No requirement for immediate readiness for renewed operation
- Damage to the starter is permissible
Coordination type “2“:
- No risk to persons or installations
- Starter is capable of renewed operation
- No damage to the starter with the exception of a slight welding of
the contacts, provided they can be separated without significant
deformation.
Positive opening operation
(IEC 947-1; 2.4.11/IEV 441-16-12)
This opening operation is designed to ensure that auxiliary contacts
of a switching device are always in the respective positions corre-
sponding to the open or closed position of the main contacts. The
contacts of a contactor are interlocked opposing contacts, pro-
vided they are mechanically linked in such a way as to ensure that
normally open and normally closed contacts can never be closed
simultaneously.
This arrangement must also ensure that minimum contact separation
of 0.5 mm is maintained over the entire lifespan of the device, even
during a fault, e.g. the welding of one contact.
The relevant German Trade Association requires the use of contac-
tors with interlocked opposing contacts for control systems on power
presses in the metal processing industry.
Positive/enforced
operation/actuation
This describes an arrangement where a link between the actuator
and the switching element ensures that the force exerted on the actu-
ator is transferred directly, i.e. without the intervention of sprung
parts, onto the switching element.
Positive opening
(IEC 947-1; 2.4.10/IEV 441-16-11)
An opening operation which ensures that the main contacts of a
mechanical switching device have attained the open position when
the actuator is in the Off-position.
Symbols used in Technical Data and Formulae
DF Duty factor
Icn Rated short-circuit breaking capacity
Ics Rated service short-circuit breaking capacity
Icu Rated ultimate short-circuit breaking capacity
IeRated operational current
I”sc Transformer initial short-circuit current AC
InRated current
INT Rated transformer current
IqRated conditional short-circuit current
IrSet value of overcurrent release
Irm Response value of non-delayed short-circuit release
Ith Conventional free air thermal current
Ithe Conventional thermal current of enclosed devices
IuRated uninterrupted current
SNT Transformer rating
UcRated actuating voltage
UeRated operational voltage
UiRated insulation voltage
Uimp Rated impulse withstand voltage
ukTransformer short-circuit voltage
UsRated control voltage
Appendix H-93
LVSG
Additional ordering information for contactors
CE-Marking
The manufacturer has to sign his products with the CE-Marking. With
the CE-Marking the manufacturer confirms the accordance with the
different EEC Directives. The CE-Marking is absolutely necessary to
sell the products in the EEC.
Attached you find the EEC Directives concerning our products.
Low Voltage Directive (73/23/EEC)
EMC Directive (89/336/EEC)
Declarations of Conformity art. no. D586.. on request.
Test Authorities, Registration Mark, Approvals
OMRON Low voltage switchgear is built and tested to national and
international specifications. All devices suit all important specifica-
tions without any test obligation, like VDE, BS and also relative to
IEC Recommendations and to European Standards like IEC 947 and
EN 60947.
It is for this reason OMRON Low voltage switchgear is used all over
the world. In order to provide special versions, limitations to the max.
voltages, currents and power ratings or special markings are some-
times necessary.
OMRON Low voltage switchgear is also suitable for applications in
marine environments.
They are classified in "Lloyd`s Register of Shipping" and in the "Mari-
time Register of Shipping" (GUS). The "American Bureau of Ship-
ping" does not claim a general approval for single components, the
complete electrical equipment on board has to be approved. The
devices should have UL- and CSA-approvals. Further information for
Guide-No. and File-No. (CSA, UL) you will find on page 95.
For approved values see technical data of the devices.State deputy
Explanations for choice and supply of low voltage switchgears in Canada and USA
Marking of auxiliary contacts
At several devices in UL-data are two voltages for auxiliary contacts
mentioned (e. g.: 600 volts at same potential, 150 volts at different
potentials). That means, if the voltage is higher than 150 volts, the con-
trol voltage applied to input terminals must be at the same potential
Low voltage switchgear for auxiliary circuits (e. g. contactor relays,
control units, auxiliary contacts in general) usually approved for
"Heavy Duty" or "Standard Duty" UL and besides these marked with
the admissible max. voltage or with short codes (see table).
Country Canada USA Switzer-
land
Den-
mark
Norway Sweden Finland Poland Slowa-
kia
Czech Hun-
garia
State deputy or private
examination
(state admitted)
CSA UL UL SEV DEMKO NEMKO SEMKO SETI SEP SKTC EZU MEEI
Label marking of ex-
amination boards
*1
Duty of approvals All switchgear
or R
Approval of
switchgear
commendable
No approval since 1.1.1994
Our devices are according to the harmonised
European Standards e.g. EN 60947 (IEC 947,
VDE 0660) and can be used generally
Specification UL is authorised for approvals
acc. to Canadian Standards
Marking with approbation label is no longer
necessary
*1) CSA-approvals are replaced by UL-approvals valid for USA and Canada. From 1. 1. 2000 switchgear will be marked with the combined
approval. UL-mark or only.
Marking of
auxiliary
contacts
according to
CSA and UL
Max. rated values per pole Contact
Rating
Code
Designa-
tion
Voltage
V
Current Cont.
Current
A
Make
A
Break
A
Heavy Duty
(HD or HVY DTY)
AC 120 60 6 10 A150
AC 240 30 3 10 A300
AC 480 15 1,5 10 A600
AC 600 12 1,2 10 A600
DC 125 2,2 2,2 10 N150
DC 250 1,1 1,1 10 N300
DC 600 0,4 0,4 10 N600
Standard Duty
(SD or STD DTY)
AC 120 30 3 5 B150
AC 240 15 1,5 5 B300
AC 480 7,5 0,75 5 B600
AC 600 6 0,6 5 B600
DC 125 1,1 1,1 5 P150
DC 250 0,55 0,55 5 P300
DC 600 0,2 0,2 5 P600
- AC 120 15 1,5 2,5 C150
AC 240 7,5 0,75 2,5 C300
AC 480 3,75 0,375 2,5 C600
AC 600 3 0,3 2,5 C600
DC 125 0,55 0,55 2,5 Q150
DC 250 0,27 0,27 2,5 Q300
DC 600 0,1 0,1 2,5 Q600
- AC 120 3,6 0,6 1 D150
AC 240 1,8 0,3 1 D300
DC 125 0,22 0,22 1 R150
DC 250 0,11 0,11 1 R300
- AC 120 1,8 0,3 0,5 E150
Marking of
auxiliary
contacts
according to
CSA and UL
Max. rated values per pole Contact
Rating
Code
Designa-
tion
Voltage
V
Current Cont.
Current
A
Make
A
Break
A
H-94 Appendix
Discernment at UL-Standards
Are devices approved as "Listed Equipment" the approval is also valid for using as "Recognized Component" R.
Approvals
Recognized Component Industrial Control Equipment Listed Industrial Control Equipment
UL issues yellow "Guide cards" with Guide- and File-No. UL issues white "Guide cards" with Guide- and File-No.
Devices have permission to be marked with on the label Devices have to be marked with the "UL-Listing Mark"
Devices as components approved for "factory wiring":
devices for employment in control panels, when they are selected,
mounted and wired according to the charging conditions by skilled work-
er.
Devices approved for "field wiring",
a) devices for employment in control panels, when they are mounted
and wired by skilled worker.
b) devices for retail in USA
Valid UL-Standards:
UL 508„Standard for Industrial Control Equipment“
(partly limited)
Valid UL-Standards:
UL 508„Standard for Industrial Control Equipment“
(unlimited)
UL 486"Standard for Wire Connectors and Soldering Lugs"
Country
Type
USA, Canada Switzerland Europe Register of Shipping CENELEC
CB-Certificates
UL SEV
Great Britain
LRS
GUS
MRS
Italy
RINA
Mini Contactors J7KNA and Accessories
J7KNA-AR..(D) o--o---o
J7KNA-09..(D) o--o---o
J7KNA-12..(D) o--o----
J73KN-A..., J73KN-AM o--o---o
Contactors Series J7KN
J7KN-10...(D) o--o---o
J7KN-14...(D) o--o---o
J7KN-18...(D) o--o---o
J7KN-22...(D) o--o---o
J7KN-24...(D) o--o---o
J7KN-32...(D) o--o---o
J7KN-40...(D) o--o---o
J7KN-50...(D) o--o---o
J7KN-62...(D) o--o---o
J7KN-74...(D) o--o---o
J7KN-85...(D) o--o---o
J7KN-110...(D) o--o---o
J7KN-150... ---o----
J7KN-175... ---o----
J7KN-200... ---o----
Accessories
J73N-KB... o--o---o
J73N-KC-115 o--o---x
J74KN-B-PT... o--o----
J74KN-A-VG... o--o----
J74KN-B-VG ---o----
Thermal Overload Relays
J7TKN-B o--o---x
J7TKN-C o--o---x
J7TKN-D o--o---x
J7TKN-A o--o---o
J7TKN-E o--o---o
J7TKN-F ---o----
o In Standard version approved x In Test - Not provided for test until now
Appendix H-95
LVSG
and R-Guide- and File-No.
These data are important for UL-inspecting
Devices Guide-No.
Kanada USA Kanada USA
Contactors NLDX7 NLDX NLDX8 NLDX2
Accessories NKCR7 NKCR NKCR8 NKCR2
Thermal Overload Relays NKCR7 NKCR - -
Circuit Breakers J7MN
as Manual Motor Controller NLRV7 NLRV - -
Circuit Breakers J7MN
as Combination Motor Controller NKJH7 NKJH - -
J7MN Bus Bar Assemblies NLRV7 NLRV - -
J7MN Accessories NKCR7 NKCR - -
H-96 Appendix
Technical information
Degree of protection acc. to EN60947
Protection ratings are prefixed by the internationally agreed letters IP
followed by two digits.
1st digit: Pertains to solid objects
2nd digit: Pertains to water.
Terminal markings acc. to EN50011
Auxiliary contacts of AC contactors and contacts of contactor relays
and thermal overload relays are particularly marked. The terminal
markings of normally-open contacts are printed as positive figures,
they of normally-closed contacts as negative figures.
This gives a clear indication of the function of the contacts.
The figure below illustrates the determination of terminal markings
for contactors with auxiliary contact blocks.
Resistance to climatic conditions acc. to IEC 68
Open-type devices are climate-resistant in the constant climate
according to IEC 68-2-3 (this is a climate with an ambient tempera-
ture of 40°C and an atmospheric humidity of 90 to 95%).
Enclosed devices are climate-resistant in an alternating climate
according to IEC 68-2-30 (this is a moist alternating climate with a
24-hour cycle between climates with an ambient temperature of
25°C, and an atmospheric humidity of 95 to 100% and an ambient
temperature of 40°C, and an atmospheric humidity of 90 to 96% in
the presence of condensation during rises in temperature).
Data are valid up to an altitude of 2000m above sea level.
Short circuit protection
Back up fuses should be used to protect contactors and starters
against short circuits. For starters the device with the smaller admis-
sible fuse at the main and at the control circuit (contactor or thermal
overload) determines the fuse size.
After a short circuit devices have to be checked for correct operation.
Disconnect power before proceeding with any work on the equipment!
1st
digit
Short description Definition
1 Protected against
solid objects great-
er than 50 mm
Excludes solid objects exceeding
50 mm in diameter and protects against
contact with live and moving parts by a
large body surface such as a hand (but
not against deliberate access).
2L Protected against
solid objects great-
er than 12,5 mm
and against contact
by standard test
finger
Excludes solid objects exceeding
12,5 mm in diameter and protects
against contact with live and moving
parts by a standard test finger or similar
objects not exceeding 80 mm in length.
3 Protected against
solid objects great-
er than 2,5 mm
Excludes solid objects exceeding
2,5 mm in diameter or thickness.
4 Protected against
solid objects great-
er than 1 mm
Excludes solid objects exceeding 1 mm
in diameter or thickness.
5 Dust protected Prevents ingress of dust in quantities
and locations that would interfere with
the intended operation of the equip-
ment.
6 Dust tight Prevents ingress of dust.
2nd
digit
Short description Definition
1 Protected against-
dripping water
Dripping water (vertically falling drops)
shall have no harmful effect.
2 Protected against
dripping water
when tilted up to
15°
Vertically dripping water shall have no
harmful effect when the enclosure is tilt-
ed at any angle up to 15° from its nor-
mal position.
3 Protected against
spraying water
Water falling as a spray at an angle up
to 60° from the vertical shall have no
harmful effect.
4 Protected against
splashing water
Water splashed against the enclosure
from any direction shall have no harm-
ful effect.
5 Protected against
water jets
Water protected by a nozzle against the
enclosure from any direction shall have
no harmful effect.
6 Protected against
heavy seas
Water from heavy seas or water pro-
jected in powerful jets shall not enter
the enclosure in harmful quanties.
7 Protected against
the effects of im-
mersion
Ingress of water in a harmful quantity
shall not be possible when the enclo-
sure is immersed in water under stan-
dard conditions of pressure and time.
8 Protected against
submersion
No ingress of water.
The complete terminal marking according
to EN 50011 and EN 50012 results from the
sequence numbers on the contactor relay
or ac contactor (2., 3.) and the function
numbers on the auxiliary contact blocks
(e. g. .1, .2, or .3, .4).
Sequence number
Function number
Appendix H-97
LVSG
Mounting positions of contactors
Terminal screws
Terminal screws in relation to screwdriver sizes and tightening torques
J7KNA-AR... and J7KNA-12... J7KN-10 to J7KN-74, J7KN-85 to J7KN-110 J7KN-150... to J7KN-200
Devices Kind of connection
Type Screw with
washer
Screw with
clamp box
Mini Contactors
All conductors
J7KN-AR...; J7KNA-09...;
J7KNA-12... M3,5 -
Contactors
Main conductor
J7KN-10... to J7KN-22... M3,5 -
J7KN-24... to J7KN-40... - M5
J7KN-50... to J7KN-74... - M6
J7KN-85..., J7KN-110... - M8
Auxiliary conductor
J7KN-10... to J7KN-22... M3,5 -
J7KN-85... to J7KN-110 M3,5 -
Coil conductor
J7KN-10... to J7KN-110... M3,5 -
Accessories
J73KNA(M)... M3,5 -
J73KN-B, J73KN-C M3,5 -
Thermal Overload Relays
Main conductor
J7TKN-A M4 -
J7TKN-B M3,5 -
J7TKN-C M5 -
J7TKN-D - M6
Auxiliary conductor
All devices M3,5 -
Devices Kind of connection
Type Screw with
washer
Screw with
clamp box
Terminal screws Pozidriv Screw driver Tightening torque
Version Size Nm lb. inch
Screw with Pozidriv and slot M3 Pz 1 Size 1 0,6 - 1,2 5 - 11
M3,5 Pz 2 Size 2, 3 0,8 - 1,4 7 - 12
M4 Pz 2 Size 3, 4 1,2 - 1,8 11 - 16
M5 Pz 2 Size 3, 4, 5 2,5 - 3 22 - 26
M6 Pz 3 Size 4, 5 3,5 - 4,5 31 - 40
Screw or
nut with hexagonal-head
M8 - - 6 - 10 53 - 88
H-98 Appendix
General technical information
Current carrying capacities of PVC insulated 600/1000 Volt cables
with copper or aluminium conductors.
In accordance with the 16th edition of the “Wiring Regulations for Electrical Installations“.
Basic assumptions: Ambient temperature of 30°C.
Circuit of protected by a OMRON circuit-breaker to IEC 947-2, or a fuse to BS 88 or BS 1361.
Figures must be adjusted by the correction factors for ambient temperature and/or cable grouping as detailed in the IEE regs.
Conductor
size In conduit or trunking (enclosed)
Clipped to surface or cable tray,
bunched, embedded in plaster
(unenclosed)
Fixed to vertical surface of wall or open
cable trench with 20 mm separation
between cables and wall
mm² Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase
Cu [A] Al [A] Cu [A] Al [A] Cu [A] Al [A] Cu [A] Al [A] Cu [A] Al [A] Cu [A] Al [A]
Single core, PVC insulated cable non-armoured, copper or aluminium conductors.
1.0 13.5 - 12.0 - 15.5 - 14.0 - ----
1.5 17.5 - 15.5 - 20.0 - 18.0 - ----
2.5 24.0 - 21.0 - 27.0 - 25.0 - ----
4.0 32.0 - 28.0 - 37.0 - 33.0 - ----
6.0 41.0 - 36.0 - 47.0 - 43.0 - ----
10.0 57.0 - 50.0 - 65.0 - 59.0 - ----
16.0 76.0 - 68.0 - 87.0 - 79.0 - ----
25.0 101.0 - 89.0 - 114.0 - 104.0 - 126.0 - 112.0 -
35.0 125.0 - 110.0 - 141.0 - 129.0 - 156.0 - 141.0 -
50.0 151.0 118.0 134.0 104.0 182.0 134.0 167.0 123.0 191.0 144.0 172.0 132.0
70.0 192.0 150.0 171.0 133.0 234.0 172.0 214.0 156.0 246.0 185.0 223.0 169.0
95.0 232.0 181.0 207.0 161.0 284.0 210.0 261.0 194.0 300.0 225.0 273.0 206.0
120.0 296.0 210.0 239.0 186.0 330.0 245.0 303.0 226.0 349.0 261.0 318.0 240.0
150.0 300.0 234.0 262.0 204.0 381.0 283.0 349.0 261.0 404.0 301.0 369.0 277.0
185.0 341.0 266.0 296.0 230.0 436.0 324.0 400.0 299.0 463.0 344.0 424.0 317.0
240.0 400.0 312.0 346.0 269.0 515.0 384.0 472.0 354.0 549.0 407.0 504.0 375.0
300.0 458.0 358.0 394.0 306.0 594.0 444.0 545.0 410.0 635.0 469.0 584.0 435.0
400.0 546.0 - 467.0 - 694.0 - 634.0 - 732.0 - 679.0 -
500.0 626.0 - 533.0 - 792.0 - 723.0 - 835.0 - 778.0 -
630.0 720.0 - 611.0 - 904.0 - 826.0 - 953.0 - 892.0 -
Twin and multi-core PVC insulated cable, non-armoured, copper or aluminium conductors.
1.0 11.0 - 11.5 - 15.0 - 13.5 - 17.0 - 14.5 -
1.5 14.0 - 15.0 - 19.5 - 17.5 - 22.0 - 18.5 -
2.5 18.5 - 20.0 - 27.0 - 24.0 - 30.0 - 25.0 -
4.0 25.0 - 27.0 - 36.0 - 32.0 - 40.0 - 34.0 -
6.0 32.0 - 34.0 - 46.0 - 41.0 - 51.0 - 43.0 -
10.0 43.0 - 46.0 - 63.0 - 57.0 - 70.0 - 60.0 -
16.0 57.0 54.0 62.0 48.0 85.0 66.0 76.0 59.0 94.0 73.0 80.0 61.0
25.0 75.0 71.0 80.0 62.0 112.0 83.0 96.0 73.0 119.0 89.0 101.0 78.0
35.0 92.0 86.0 99.0 77.0 138.0 103.0 119.0 90.0 148.0 111.0 126.0 96.0
50.0 110.0 104.0 118.0 92.0 168.0 125.0 144.0 110.0 180.0 135.0 153.0 117.0
70.0 139.0 131.0 149.0 116.0 213.0 160.0 184.0 140.0 232.0 173.0 196.0 150.0
95.0 167.0 157.0 179.0 139.0 258.0 195.0 261.0 170.0 282.0 210.0 238.0 183.0
120.0 192.0 - 206.0 160.0 299.0 245.0 259.0 197.0 328.0 - 276.0 212.0
150.0 219.0 - 225.0 184.0 344.0 283.0 299.0 227.0 379.0 - 319.0 245.0
185.0 248.0 - 255.0 210.0 392.0 324.0 341.0 259.0 434.0 - 364.0 280.0
240.0 291.0 - 297.0 248.0 461.0 384.0 403.0 305.0 514.0 - 430.0 330.0
300.0 334.0 - 339.0 258.0 530.0 444.0 464.0 351.0 593.0 - 497.0 381.0
400.0 --402.0 - 634.0 - 557.0 - 715.0 - 597.0 -
Appendix H-99
LVSG
Overall diameter of cables (Copper)
The dimensions are based on BS specification or the average values as given by the manufacturers.
The overall diameters given are for cables of 600/1000 V grade.
Number and nominal
area of cables (mm2)
Approx. overall diameter in mm Number and nominal
area of cables (mm2)
Approx. overall diameter in mm
PVC/SWA PVC PVC/SWA PVC
1 x 1.0 - 4.5 2 x 1.0 - -
1 x 1.5 - 4.9 2 x 1.5 11.7 7.2
1 x 2.5 - 5.8 2 x 2.5 13.1 8.6
1 x 4.0 - 6.8 2 x 4.0 15.1 10.7
1 x 6.0 - 7.4 2 x 6.0 16.5 12.0
1 x 10.0 - 8.8 2 x 10.0 20.1 14.9
1 x 16.0 - 10.5 2 x 16.0 21.9 17.2
1 x 25.0 - 12.5 2 x 25.0 23.0 18.4
1 x 35.0 - 13.5 2 x 35.0 24.9 20.1
1 x 50.0 19.1 15.1 2 x 50.0 27.8 22.8
1 x 70.0 21.1 16.9 2 x 70.0 30.4 25.5
1 x 95.0 23.4 19.4 2 x 95.0 35.5 29.3
1 x 120.0 26.3 21.0 2 x 120.0 38.0 31.8
1 x 150.0 28.3 23.2 2 x 150.0 41.3 35.1
1 x 185.0 30.8 25.8 2 x 185.0 46.4 39.1
1 x 240.0 34.1 29.0 2 x 240.0 51.2 43.9
1 x 300.0 37.0 32.1 2 x 300.0 56.4 48.7
1 x 400.0 42.0 35.8 2 x 400.0 61.9 54.2
1 x 500.0 45.6 39.6 ---
1 x 630.0 49.7 43.8 ---
Number and nominal
area of cables (mm2)
Approx. overall diameter in mm Number and nominal
area of cables (mm2)
Approx. overall diameter in mm
PVC/SWA PVC PVC/SWA PVC
3 x 1.0 - - 4 x 1.0 - -
3 x 1.5 12.3 7.6 4 x 1.5 13.0 8.3
3 x 2.5 13.6 9.1 4 x 2.5 14.5 10.0
3 x 4.0 15.8 11.5 4 x 4.0 17.8 12.6
3 x 6.0 18.0 12.8 4 x 6.0 19.2 14.2
3 x 10.0 21.2 15.8 4 x 10.0 22.8 17.7
3 x 16.0 23.1 19.7 4 x 16.0 26.3 20.6
3 x 25.0 25.0 20.4 4 x 25.0 27.8 22.9
3 x 35.0 27.3 22.4 4 x 35.0 30.5 25.4
3 x 50.0 30.5 25.5 4 x 50.0 35.4 29.2
3 x 70.0 35.0 28.7 4 x 70.0 39.2 33.0
3 x 95.0 39.3 33.3 4 x 95.0 44.3 38.3
3 x 120.0 42.2 36.3 4 x 120.0 49.3 41.8
3 x 150.0 47.5 40.0 4 x 150.0 53.6 46.3
3 x 185.0 51.9 44.6 4 x 185.0 59.0 61.3
3 x 240.0 57.8 50.1 4 x 240.0 65.7 58.0
3 x 300.0 63.2 55.6 4 x 300.0 72.0 64.6
3 x 400.0 69.6 62.2 4 x 400.0 81.3 72.0
H-100 Appendix
Conversion table
Conversion table for mm²/AWG cable sizes
To convert Multiply by
Inches to millimeters (mm) 25.4
Millimeters to inches (In.) 0.03937
Feet to meters (m) 0.3048
meters to feet (ft) 3.2808
Yards to meters (m) 0.9144
meters to yards (yd) 1.0936
Miles to kilometers (km) 1.6093
Kilometers to miles (mil.) 0.6214
Square inches to square millimeters (mm2)645.16
Square millimeters to square inches (inch2)0.00155
Square yards to square meters (m2)0.8361
Square meters to square yards (yd2)1.196
Cubic inches to cubic centimeters (cm3)16.387
Cubic centimeters to cubic inches (inch3)0.06102
Pounds to kilogrammes (kg) 0.4536
Kilogrammes to pounds (lb) 2.2046
Tons (2,240 lb) to kilogrammes (kg) 1,016.05
Kilogrammes to tons (240 lb) 0.0009842
Ounces (avoirdpois) to grammes (g) 28.3495
Grammes to ounces 0.0353
Gallons to litres (l) 4.561
Litres to gallons 0.220
Force N (newtons) to lbft
1 N = 1 kg (mass) accelerated at 1 metre/sec. 0.225
1 Nm = 1 J (joule) to calorie 0.239
Horse-power to kilowatts (kW) 0.7458
Kilowatts to horse-power (h.p.)
1 W (watt) = 1J/s 1.3408
Atmospheres to lb per square inch (lb/inch2)
1 bar = 1 kg/cm2 = 735.6 mm Hg = 14.2 lb/inch214.68
200
CF
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
BP-212
10
0
10
20
30
40
50
60
70
80
90
100
FP-
mm2AWG
0.75 18
1.0 17
1.5 16
2.5 13
4.0 12
6.0 10
10.0 8
Appendix H-101
LVSG
Rated currents of 3-phase motors (approx. figures for squirrel-cage motors)
Minimum fuse size for protection of 3-phase motors
The maximum size is determined by the requirements of the switchgear or overload relay.
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting: Maximum starting current 6 x rated motor current. Maximum starting time 5 s.
Y/D starting: Maximum starting current 2 x rated motor current. Maximum starting time 15 s.
Set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring motors.
For higher rated currents, starting currents and/or longer starting times, larger fuses are required.
Table is valid for “slow” and/or “gL” fuses (DIN VDE 0636).
For NH fuses with aM characteristics, fuses = rated current is selected.
Motor rating
230 V400 V415 V
Rated
motor
current
Fuse
starting
D.O.L.
Y/Rated
motor
current
Fuse
starting
D.O.L.
Y/Rated
motor
current
Fuse
starting
D.O.L.
Y/
kW cos ϕη %AAAAAAAA, BSA, BS
0.06 0.7 58 0.37 2.0 - 0.21 2.0 - 0.21 2.0 2
0.09 0.7 60 0.54 2.0 - 0.31 2.0 - 0.30 2.0 2
0.12 0.7 60 0.72 4.0 2 0.41 2.0 - 0.40 2.0 2
0.18 0.7 62 1.04 4.0 2 0.6 2.0 - 0.58 2.0 2
0.25 0.7 62 1.4 4.0 2 0.8 4.0 2 0.8 4.0 2
0.37 0.72 66 2.0 6.0 4 1.1 4.0 2 1.1 4.0 2
0.55 0.75 69 2.7 10.0 4 1.5 4.0 2 1.5 6.0 4
0.75 0.79 74 3.2 10.0 4 1.9 6.0 4 1.8 6.0 4
1.1 0.81 74 4.6 10.0 6 2.6 6.0 4 2.6 10.0 6
1.5 0.81 74 6.3 16.0 10 3.6 6.0 4 3.5 16.0 10
2.2 0.81 78 8.7 20.0 10 5.0 10.0 6 4.8 16.0 10
3.0 0.82 80 11.5 25.0 16 6.6 16.0 10 6.4 20.0 16
4.0 0.82 83 14.8 32.0 16 8.5 20.0 10 8.2 20.0 16
5.5 0.82 86 19.6 32.0 25 11.3 25.0 16 10.9 25.0 20
7.5 0.82 87 26.4 50.0 32 15.2 32.0 16 14.6 35.0 25
11.0 0.84 87 38.0 80.0 40 21.7 40.0 25 20.9 50.0 32
15.0 0.84 88 51.0 100.0 63 29.3 63.0 32 28.2 80.0 40
18.5 0.84 88 63.0 125.0 80 36.0 63.0 40 35.0 80.0 50
22.0 0.84 92 71.0 125.0 80 41.0 80.0 50 40.0 80.0 50
30.0 0.85 92 96.0 200.0 100 55.0 100.0 63 53.0 100.0 80
37.0 0.86 92 117.0 200.0 125 68.0 125.0 80 65.0 125.0 80
45.0 0.86 93 141.0 250.0 160 81.0 160.0 100 78.0 125.0 80
55.0 0.86 93 173.0 250.0 200 99.0 200.0 125 96.0 160.0 100
75.0 0.86 94 233.0 315.0 250 134.0 200.0 160 129.0 250.0 160
90.0 0.86 94 279.0 400.0 315 161.0 250.0 200 155.0 250.0 160
110.0 0.86 94 342.0 500.0 400 196.0 315.0 200 189.0 315.0 200
132.0 0.87 95 401.0 630.0 500 231.0 400.0 250 222.0 355.0 250
160.0 0.87 95 486.0 630.0 630 279.0 400.0 315 269.0 355.0 315
200.0 0.87 95 607.0 800.0 630 349.0 500.0 400 337.0 450.0 355
250.0 0.87 95 ---437.0 630.0 500 421.0 500.0 450
315.0 0.87 96 ---544.0 800.0 630 525.0 630.0 560
400.0 0.88 96 ---683.0 1000.0 800 ---
450.0 0.88 96 ---769.0 1000.0 800 ---
500.0 0.88 97 ---------
560.0 0.88 97 ---------
630.0 0.88 97 ---------
H-102 Appendix
Minimum fuse size for protection of 3-phase motors
The maximum size is determined by the requirements of the switchgear or overload relay.
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting: Maximum starting current 6 x rated motor current. Maximum starting time 5 s.
Y/D starting: Maximum starting current 2 x rated motor current. Maximum starting time 15 s.
Set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring motors.
For higher rated currents, starting currents and/or longer starting times, larger fuses are required.
Table is valid for “slow” and/or “gL” fuses (DIN VDE 0636).
For NH fuses with aM characteristics, fuses = rated current is selected.
Motor rating
500 V 600 V
Rated
motor
current
Fuse
starting
D.O.L.
Y/Rated
motor
current
Fuse
starting
D.O.L.
Y/
kW cos ϕη %AAAAAA
0.06 0.7 58 0.17 2.0 - 0.12 2.0 -
0.09 0.7 60 0.25 2.0 - 0.18 2.0 -
0.12 0.7 60 0.33 2.0 - 0.24 2.0 -
0.18 0.7 62 0.48 2.0 - 0.35 2.0 -
0.25 0.7 62 0.70 2.0 - 0.50 2.0 -
0.37 0.72 66 0.90 2.0 2 0.70 2.0 -
0.55 0.75 69 1.20 4.0 2 0.90 4.0 2
0.75 0.79 74 1.50 4.0 2 1.10 4.0 2
1.1 0.81 74 2.1 6.0 4 1.5 4.0 2
1.5 0.81 74 2.9 6.0 4 2.1 6.0 4
2.2 0.81 78 4.0 10.0 4 2.9 10.0 4
3.0 0.82 80 5.3 16.0 6 3.8 10.0 4
4.0 0.82 83 6.8 16.0 10 4.9 16.0 6
5.5 0.82 86 9.0 20.0 16 6.5 16.0 10
7.5 0.82 87 12.1 25.0 16 8.8 20.0 10
11.0 0.84 87 17.4 32.0 20 12.6 25.0 16
15.0 0.84 88 23.4 50.0 25 17.0 32.0 20
18.5 0.84 88 28.9 50.0 32 20.9 32.0 25
22.0 0.84 92 33.0 63.0 32 23.8 50.0 25
30.0 0.85 92 44.0 80.0 50 32.0 63.0 32
37.0 0.86 92 54.0 100.0 63 39.0 80.0 50
45.0 0.86 93 65.0 125.0 80 47.0 80.0 63
55.0 0.86 93 79.0 160.0 80 58.0 100.0 63
75.0 0.86 94 107.0 200.0 125 78.0 160.0 100
90.0 0.86 94 129.0 200.0 160 93.0 160.0 100
110.0 0.86 94 157.0 250.0 160 114.0 200.0 125
132.0 0.87 95 184.0 250.0 200 134.0 250.0 160
160.0 0.87 95 224.0 315.0 250 162.0 250.0 200
200.0 0.87 95 279.0 400.0 315 202.0 315.0 250
250.0 0.87 95 349.0 500.0 400 253.0 400.0 315
315.0 0.87 96 436.0 630.0 500 316.0 500.0 400
400.0 0.88 96 547.0 800.0 630 396.0 630.0 400
450.0 0.88 96 615.0 800.0 630 446.0 630.0 630
500.0 0.88 97 ---491.0 630.0 630
560.0 0.88 97 ---550.0 800.0 630
630.0 0.88 97 ---618.0 800.0 630
&HUWDLQ7HUPVDQG&RQGLWLRQVRI6DOH
 2IIHU$FFHSWDQFH7KHVHWHUPVDQGFRQGLWLRQVWKHVH 7HUPVDUHGHHPHG
SDUWRIDOOFDWDORJVPDQXDOVRURWKHUGRFXPHQWVZKHWKHUHOHFWURQLFRULQZULW
LQJ UHODWLQJ WR WKH VDOH RI JRRGV RU VHUYLFHV FROOHFWLYHO\ WKH *RRGV E\
2PURQ(OHFWURQLFV//&DQGLWVVXEVLGLDU\FRPSDQLHV6HOOHU6HOOHUKHUHE\
REMHFWVWRDQ\WHUPVRUFRQGLWLRQVSURSRVHGLQ%X\HUVSXUFKDVHRUGHURURWKHU
GRFXPHQWVZKLFKDUHLQFRQVLVWHQWZLWKRULQDGGLWLRQWRWKHVH7HUPV3OHDVH
FRQWDFW\RXU 2PURQ UHSUHVHQWDWLYHWR FRQILUPDQ\ DGGLWLRQDOWHUPVIRU VDOHV
IURP\RXU2PURQFRPSDQ\
 3ULFHV $OO SULFHV VWDWHG DUH FXUUHQW VXEMHFW WR FKDQJH ZLWKRXW QRWLFH E\
6HOOHU%X\HUDJUHHVWRSD\WKHSULFHLQHIIHFWDWWLPHRIVKLSPHQW
 'LVFRXQWV &DVK GLVFRXQWV LI DQ\ ZLOO DSSO\ RQO\ RQ WKH QHW DPRXQW RI
LQYRLFHV VHQW WR %X\HU DIWHU GHGXFWLQJ WUDQVSRUWDWLRQ FKDUJHV WD[HV DQG
GXWLHVDQGZLOOEHDOORZHGRQO\LILWKHLQYRLFHLVSDLGDFFRUGLQJWR6HOOHUV
SD\PHQWWHUPVDQGLL%X\HUKDVQRSDVWGXHDPRXQWVRZLQJWR6HOOHU
 2UGHUV6HOOHUZLOODFFHSWQRRUGHUOHVVWKDQQHWELOOLQJ
 *RYHUQPHQWDO $SSURYDOV %X\HU VKDOO EH UHVSRQVLEOH IRU DQG VKDOO EHDU DOO
FRVWVLQYROYHGLQREWDLQLQJDQ\JRYHUQPHQWDSSURYDOVUHTXLUHGIRUWKHLPSRU
WDWLRQRUVDOHRIWKH*RRGV
 7D[HV$OOWD[HVGXWLHVDQGRWKHUJRYHUQPHQWDOFKDUJHVRWKHUWKDQJHQHUDO
UHDOSURSHUW\ DQGLQFRPH WD[HVLQFOXGLQJDQ\ LQWHUHVWRU SHQDOWLHVWKHUHRQ
LPSRVHGGLUHFWO\ RULQGLUHFWO\RQ 6HOOHURUUHTXLUHGWREHFROOHFWHG GLUHFWO\RU
LQGLUHFWO\E\6HOOHUIRUWKHPDQXIDFWXUHSURGXFWLRQVDOHGHOLYHU\LPSRUWDWLRQ
FRQVXPSWLRQ RU XVH RI WKH *RRGV VROG KHUHXQGHU LQFOXGLQJ FXVWRPV GXWLHV
DQGVDOHVH[FLVHXVHWXUQRYHUDQGOLFHQVHWD[HVVKDOO EH FKDUJHG WR DQG
UHPLWWHGE\%X\HUWR6HOOHU
 )LQDQFLDO,IWKHILQDQFLDOSRVLWLRQRI%X\HUDWDQ\WLPHEHFRPHVXQVDWLVIDFWRU\
WR 6HOOHU 6HOOHU UHVHUYHV WKH ULJKW WR VWRS VKLSPHQWV RU UHTXLUH VDWLVIDFWRU\
VHFXULW\RUSD\PHQWLQDGYDQFH,I%X\HUIDLOVWRPDNHSD\PHQWRURWKHUZLVH
FRPSO\ZLWKWKHVH7HUPVRUDQ\UHODWHGDJUHHPHQW6HOOHUPD\ZLWKRXWOLDELOLW\
DQGLQDGGLWLRQWRRWKHUUHPHGLHVFDQFHODQ\XQVKLSSHGSRUWLRQRI*RRGVVROG
KHUHXQGHUDQGVWRSDQ\*RRGVLQWUDQVLWXQWLO%X\HUSD\VDOODPRXQWVLQFOXG
LQJDPRXQWVSD\DEOHKHUHXQGHUZKHWKHURUQRWWKHQGXHZKLFKDUHRZLQJWRLW
E\%X\HU%X\HUVKDOOLQDQ\HYHQWUHPDLQOLDEOHIRUDOOXQSDLGDFFRXQWV
 &DQFHOODWLRQ (WF 2UGHUV DUH QRW VXEMHFW WR UHVFKHGXOLQJ RU FDQFHOODWLRQ
XQOHVV%X\HU LQGHPQLILHV6HOOHUIXOO\DJDLQVWDOOFRVWVRU H[SHQVHVDULVLQJLQ
FRQQHFWLRQWKHUHZLWK
 )RUFH0DMHXUH6HOOHU VKDOO QRW EH OLDEOH IRU DQ\ GHOD\ RUIDLOXUHLQ GHOLYHU\
UHVXOWLQJIURPFDXVHVEH\RQGLWVFRQWUROLQFOXGLQJHDUWKTXDNHVILUHVIORRGV
VWULNHV RU RWKHU ODERU GLVSXWHV VKRUWDJH RI ODERU RU PDWHULDOV DFFLGHQWV WR
PDFKLQHU\ DFWV RI VDERWDJH ULRWV GHOD\ LQ RU ODFN RI WUDQVSRUWDWLRQ RU WKH
UHTXLUHPHQWVRIDQ\JRYHUQPHQWDXWKRULW\
 6KLSSLQJ'HOLYHU\8QOHVVRWKHUZLVHH[SUHVVO\DJUHHGLQZULWLQJE\6HOOHU
D 6KLSPHQWVVKDOOEHE\DFDUULHUVHOHFWHGE\6HOOHU
E 6XFKFDUULHUVKDOODFWDVWKHDJHQWRI%X\HUDQGGHOLYHU\WRVXFKFDUULHU
VKDOOFRQVWLWXWHGHOLYHU\WR%X\HU
F $OOVDOHVDQGVKLSPHQWVRI*RRGVVKDOOEH)2%VKLSSLQJSRLQWXQOHVVRWK
HUZLVHVWDWHGLQZULWLQJE\6HOOHUDWZKLFKSRLQWWLWOHWRDQGDOOULVNRIORVVRI
WKH*RRGVVKDOOSDVVIURP6HOOHUWR%X\HUSURYLGHGWKDW6HOOHUVKDOOUHWDLQD
VHFXULW\LQWHUHVWLQWKH*RRGVXQWLOWKHIXOOSXUFKDVHSULFHLVSDLGE\%X\HU
G 'HOLYHU\DQGVKLSSLQJGDWHVDUHHVWLPDWHVRQO\
H 6HOOHUZLOOSDFNDJH*RRGVDVLWGHHPVSURSHUIRUSURWHFWLRQDJDLQVWQRUPDO
KDQGOLQJDQGH[WUDFKDUJHVDSSO\WRVSHFLDOFRQGLWLRQV
 &ODLPV $Q\ FODLP E\ %X\HU DJDLQVW 6HOOHU IRU VKRUWDJH RU GDPDJH WR WKH
*RRGVRFFXUULQJEHIRUHGHOLYHU\WRWKHFDUULHUPXVWEHSUHVHQWHGLQZULWLQJWR
6HOOHUZLWKLQGD\VRIUHFHLSWRIVKLSPHQWDQGLQFOXGHWKHRULJLQDOWUDQVSRUWD
WLRQELOOVLJQHGE\WKHFDUULHUQRWLQJWKDWWKHFDUULHUUHFHLYHGWKH*RRGVIURP
6HOOHULQWKHFRQGLWLRQFODLPHG
 :DUUDQWLHVD([FOXVLYH:DUUDQW\6HOOHUVH[FOXVLYHZDUUDQW\LVWKDWWKH
*RRGVZLOOEHIUHHIURPGHIHFWVLQPDWHULDOVDQGZRUNPDQVKLSIRUDSHULRGRI
WZHOYHPRQWKVIURPWKHGDWHRIVDOHE\6HOOHURUVXFKRWKHUSHULRGH[SUHVVHG
LQZULWLQJE\6HOOHU6HOOHUGLVFODLPVDOORWKHUZDUUDQWLHVH[SUHVVRULPSOLHG
E/LPLWDWLRQV6(//(50$.(612:$55$17<255(35(6(17$7,21
(;35(66 25 ,03/,(' $%287 121,1)5,1*(0(17 0(5&+$17$%,/
,7<25),71(66)25$3$57,&8/$5385326(2)7+(*22'6
%8<(5$&.12:/('*(67+$7,7$/21(+$6'(7(50,1('7+$77+(
*22'6 :,// 68,7$%/< 0((7 7+( 5(48,5(0(176 2) 7+(,5
,17(1'('86(6HOOHUIXUWKHUGLVFODLPVDOOZDUUDQWLHVDQGUHVSRQVLELOLW\RI
DQ\W\SHIRUFODLPVRUH[SHQVHVEDVHGRQLQIULQJHPHQWE\WKH*RRGVRURWKHU
ZLVHRIDQ\LQWHOOHFWXDOSURSHUW\ULJKWF%X\HU5HPHG\6HOOHUVVROHREOLJD
WLRQKHUHXQGHU VKDOOEHWR UHSODFH LQWKH IRUP RULJLQDOO\VKLSSHGZLWK %X\HU
UHVSRQVLEOH IRU ODERU FKDUJHV IRU UHPRYDO RU UHSODFHPHQW WKHUHRI WKH QRQ
FRPSO\LQJ *RRG RU DW 6HOOHUV HOHFWLRQ WR UHSD\ RU FUHGLW %X\HU DQ DPRXQW
HTXDOWRWKHSXUFKDVHSULFHRIWKH*RRGSURYLGHGWKDWLQQRHYHQWVKDOO6HOOHU
EHUHVSRQVLEOHIRUZDUUDQW\UHSDLULQGHPQLW\RUDQ\RWKHUFODLPVRUH[SHQVHV
UHJDUGLQJ WKH *RRGV XQOHVV 6HOOHUV DQDO\VLV FRQILUPV WKDW WKH *RRGV ZHUH
SURSHUO\KDQGOHGVWRUHGLQVWDOOHGDQGPDLQWDLQHGDQGQRWVXEMHFWWRFRQWDPL
QDWLRQDEXVHPLVXVHRULQDSSURSULDWHPRGLILFDWLRQ5HWXUQRIDQ\JRRGVE\
%X\HUPXVWEHDSSURYHGLQZULWLQJE\6HOOHUEHIRUHVKLSPHQW6HOOHUVKDOOQRW
EHOLDEOHIRUWKHVXLWDELOLW\RUXQVXLWDELOLW\RUWKHUHVXOWVIURPWKHXVHRI*RRGV
LQFRPELQDWLRQ ZLWKDQ\HOHFWULFDO RUHOHFWURQLF FRPSRQHQWV FLUFXLWVV\VWHP
DVVHPEOLHV RU DQ\ RWKHU PDWHULDOV RU VXEVWDQFHV RU HQYLURQPHQWV $Q\
DGYLFHUHFRPPHQGDWLRQVRULQIRUPDWLRQJLYHQRUDOO\RULQZULWLQJDUHQRWWREH
FRQVWUXHGDVDQDPHQGPHQWRUDGGLWLRQWRWKHDERYHZDUUDQW\
 'DPDJH/LPLWV(WF6(//(56+$//127%(/,$%/()2563(&,$/,1',
5(&7 25 &216(48(17,$/ '$0$*(6 /266 2) 352),76 25 352
'8&7,2125&200(5&,$//266,1$1<:$<&211(&7(':,7+7+(
*22'6:+(7+(568&+&/$,0,6%$6(',1&2175$&7:$55$17<
1(*/,*(1&(25 675,&7 /,$%,/,7< )XUWKHU LQ QR HYHQW VKDOO OLDELOLW\RI
6HOOHUH[FHHGWKHLQGLYLGXDOSULFHRIWKH*RRGRQZKLFKOLDELOLW\LVDVVHUWHG
 ,QGHPQLWLHV%X\HUVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHULWVDIILOLDWHVDQG
LWV HPSOR\HHV IURP DQG DJDLQVW DOO OLDELOLWLHV ORVVHV FODLPV FRVWV DQG
H[SHQVHVLQFOXGLQJDWWRUQH\VIHHVDQGH[SHQVHVUHODWHGWRDQ\FODLPLQYHV
WLJDWLRQOLWLJDWLRQRUSURFHHGLQJZKHWKHURUQRW6HOOHULVDSDUW\ZKLFKDULVHV
RULVDOOHJHGWRDULVHIURP%X\HUVDFWVRURPLVVLRQVXQGHUWKHVH7HUPVRULQ
DQ\ZD\ZLWKUHVSHFWWRWKH*RRGV:LWKRXWOLPLWLQJWKHIRUHJRLQJ%X\HUDW
LWVRZQH[SHQVHVKDOOLQGHPQLI\DQGKROGKDUPOHVV6HOOHUDQGGHIHQGRUVHWWOH
DQ\DFWLRQEURXJKWDJDLQVW6HOOHUWRWKHH[WHQWWKDWLWLVEDVHGRQDFODLPWKDW
DQ\*RRGPDGHWR%X\HUVSHFLILFDWLRQVLQIULQJHGLQWHOOHFWXDOSURSHUW\ULJKWVRI
DQRWKHUSDUW\
 3URSHUW\&RQILGHQWLDOLW\7KHLQWHOOHFWXDOSURSHUW\HPERGLHGLQWKH*RRGVLV
WKHH[FOXVLYHSURSHUW\RI6HOOHUDQGLWVDIILOLDWHVDQG%X\HUVKDOOQRWDWWHPSWWR
GXSOLFDWHLWLQDQ\ZD\ZLWKRXWWKHZULWWHQSHUPLVVLRQRI6HOOHU1RWZLWKVWDQG
LQJDQ\FKDUJHVWR%X\HUIRUHQJLQHHULQJRUWRROLQJDOOHQJLQHHULQJDQGWRROLQJ
VKDOO UHPDLQ WKH H[FOXVLYH SURSHUW\ RI 6HOOHU $OO LQIRUPDWLRQ DQG PDWHULDOV
VXSSOLHGE\6HOOHUWR%X\HUUHODWLQJWRWKH*RRGVDUHFRQILGHQWLDODQGSURSUL
HWDU\ DQG %X\HU VKDOO OLPLW GLVWULEXWLRQ WKHUHRI WR LWV WUXVWHG HPSOR\HHV DQG
VWULFWO\SUHYHQWGLVFORVXUHWRDQ\WKLUGSDUW\
0LVFHOODQHRXVD:DLYHU1RIDLOXUHRUGHOD\E\6HOOHULQH[HUFLVLQJDQ\ULJKW
DQGQRFRXUVHRIGHDOLQJEHWZHHQ%X\HUDQG6HOOHUVKDOORSHUDWHDVDZDLYHU
RIULJKWVE\6HOOHUE$VVLJQPHQW%X\HUPD\QRWDVVLJQLWVULJKWVKHUHXQGHU
ZLWKRXW6HOOHUVZULWWHQFRQVHQWF$PHQGPHQW7KHVH7HUPVFRQVWLWXWHWKH
HQWLUHDJUHHPHQWEHWZHHQ%X\HUDQG6HOOHUUHODWLQJWRWKH*RRGVDQGQRSUR
YLVLRQPD\EHFKDQJHGRUZDLYHGXQOHVVLQZULWLQJVLJQHGE\WKHSDUWLHV
G6HYHUDELOLW\,IDQ\SURYLVLRQKHUHRILVUHQGHUHGLQHIIHFWLYHRULQYDOLGVXFK
SURYLVLRQVKDOOQRWLQYDOLGDWHDQ\RWKHUSURYLVLRQH6HWRII%X\HUVKDOOKDYH
QR ULJKW WR VHW RII DQ\ DPRXQWV DJDLQVW WKH DPRXQW RZLQJ LQ UHVSHFW RI WKLV
LQYRLFHI$VXVHGKHUHLQLQFOXGLQJPHDQVLQFOXGLQJZLWKRXWOLPLWDWLRQ
&HUWDLQ3UHFDXWLRQVRQ6SHFLILFDWLRQVDQG8VH
 6XLWDELOLW\RI8VH6HOOHUVKDOOQRWEHUHVSRQVLEOHIRUFRQIRUPLW\ZLWKDQ\VWDQ
GDUGVFRGHVRUUHJXODWLRQVZKLFKDSSO\WRWKHFRPELQDWLRQRIWKH*RRGLQWKH
%X\HUVDSSOLFDWLRQRUXVHRIWKH*RRG$W%X\HUVUHTXHVW6HOOHUZLOOSURYLGH
DSSOLFDEOHWKLUGSDUW\FHUWLILFDWLRQGRFXPHQWVLGHQWLI\LQJUDWLQJVDQGOLPLWDWLRQV
RIXVHZKLFKDSSO\WRWKH*RRG7KLVLQIRUPDWLRQE\LWVHOILVQRWVXIILFLHQWIRUD
FRPSOHWHGHWHUPLQDWLRQRIWKH VXLWDELOLW\RI WKH*RRGLQ FRPELQDWLRQZLWK WKH
HQGSURGXFWPDFKLQHV\VWHPRURWKHUDSSOLFDWLRQRUXVH7KHIROORZLQJDUH
VRPH H[DPSOHV RI DSSOLFDWLRQV IRU ZKLFK SDUWLFXODU DWWHQWLRQ PXVW EH JLYHQ
7KLVLVQRWLQWHQGHGWREHDQH[KDXVWLYHOLVWRIDOOSRVVLEOHXVHVRIWKLV*RRG
QRULVLWLQWHQGHGWRLPSO\WKDWWKHXVHVOLVWHGPD\EHVXLWDEOHIRUWKLV*RRG
L 2XWGRRUXVHXVHVLQYROYLQJSRWHQWLDOFKHPLFDOFRQWDPLQDWLRQRUHOHFWULFDO
LQWHUIHUHQFHRUFRQGLWLRQVRUXVHVQRWGHVFULEHGLQWKLVGRFXPHQW
LL (QHUJ\FRQWUROV\VWHPVFRPEXVWLRQV\VWHPVUDLOURDGV\VWHPVDYLDWLRQ
V\VWHPVPHGLFDOHTXLSPHQWDPXVHPHQWPDFKLQHVYHKLFOHVVDIHW\
HTXLSPHQWDQGLQVWDOODWLRQVVXEMHFWWRVHSDUDWHLQGXVWU\RUJRYHUQPHQW
UHJXODWLRQV
LLL 6\VWHPVPDFKLQHVDQGHTXLSPHQWWKDWFRXOGSUHVHQWDULVNWROLIHRU
SURSHUW\3OHDVHNQRZDQGREVHUYHDOOSURKLELWLRQVRIXVHDSSOLFDEOHWR
WKLV*RRG
1(9(586(7+(352'8&7)25$1$33/,&$7,21,192/9,1*6(5,286
5,6.72/,)(253523(57<:,7+287(1685,1*7+$77+( 6<67(0
$6$:+2/(+$6%((1'(6,*1('72$''5(667+(5,6.6$1'7+$7
7+( 6(//(56 352'8&7 ,6 3523(5/< 5$7(' $1' ,167$//(' )25
7+(,17(1'('86(:,7+,17+(29(5$//(48,30(17256<67(0
 3URJUDPPDEOH 3URGXFWV 6HOOHU VKDOO QRW EH UHVSRQVLEOH IRU WKH XVHUV SUR
JUDPPLQJRIDSURJUDPPDEOH*RRGRUDQ\FRQVHTXHQFHWKHUHRI
 3HUIRUPDQFH'DWD3HUIRUPDQFH GDWD JLYHQLQWKLV FDWDORJ LV SURYLGHG DV D
JXLGHIRUWKHXVHULQGHWHUPLQLQJVXLWDELOLW\DQGGRHVQRWFRQVWLWXWHDZDUUDQW\
,WPD\UHSUHVHQWWKHUHVXOWRI6HOOHUVWHVWFRQGLWLRQVDQGWKHXVHUPXVWFRUUH
ODWHLWWRDFWXDODSSOLFDWLRQUHTXLUHPHQWV$FWXDOSHUIRUPDQFHLVVXEMHFWWRWKH
6HOOHUV:DUUDQW\DQG/LPLWDWLRQVRI/LDELOLW\
 &KDQJH LQ 6SHFLILFDWLRQV 3URGXFW VSHFLILFDWLRQV DQG DFFHVVRULHV PD\ EH
FKDQJHGDWDQ\WLPHEDVHGRQLPSURYHPHQWVDQGRWKHUUHDVRQV,WLVRXUSUDF
WLFHWRFKDQJHSDUWQXPEHUVZKHQSXEOLVKHGUDWLQJVRUIHDWXUHVDUHFKDQJHG
RUZKHQVLJQLILFDQWFRQVWUXFWLRQFKDQJHVDUHPDGH+RZHYHUVRPHVSHFLILFD
WLRQVRIWKH*RRGPD\EHFKDQJHGZLWKRXWDQ\QRWLFH:KHQLQGRXEWVSHFLDO
SDUWQXPEHUV PD\ EHDVVLJQHGWR IL[RU HVWDEOLVK NH\VSHFLILFDWLRQV IRU \RXU
DSSOLFDWLRQ 3OHDVH FRQVXOW ZLWK \RXU 6HOOHUV UHSUHVHQWDWLYH DW DQ\ WLPH WR
FRQILUPDFWXDOVSHFLILFDWLRQVRISXUFKDVHG*RRG
 (UURUV DQG 2PLVVLRQV 7KH LQIRUPDWLRQ LQ WKLV FDWDORJ KDV EHHQ FDUHIXOO\
FKHFNHGDQGLVEHOLHYHGWREHDFFXUDWHKRZHYHUQRUHVSRQVLELOLW\LVDVVXPHG
IRUFOHULFDOW\SRJUDSKLFDORUSURRIUHDGLQJHUURUVRURPLVVLRQV
2052121/,1(
*OREDOKWWSZZZRPURQFRP
86$KWWSZZZRPURQFRPRHL
&DQDGDKWWSZZZRPURQFD
Cat. No. J7cntctr 09/04 Specifications subject to change without notice Printed in USA
20521&$1$'$,1&
0LOQHU$YHQXH
7RURQWR2QWDULR0%9

20521(/(&7521,&6//&
2QH&RPPHUFH'ULYH
6FKDXPEXUJ,/

)RU86WHFKQLFDOVXSSRUWRURWKHULQTXLULHV

&RPSOHWH¦7HUPVDQG&RQGLWLRQVRI6DOH§IRUSURGXFWSXUFKDVHDQGXVHDUHRQ2PURQ©VZHEVLWH
DWZZZRPURQFRPRHL¤XQGHUWKH¦$ERXW8V§WDELQWKH/HJDO0DWWHUVVHFWLRQ
$//',0(16,2166+2:1$5(,10,//,0(7(56
7RFRQYHUWPLOOLPHWHUVLQWRLQFKHVPXOWLSO\E\7RFRQYHUWJUDPVLQWRRXQFHVPXOWLSO\E\