MODEL NUMBERS HPF240D20 HPF240D30 HPF480D20 HPF480D30
OUTPUT SPECIFICATIONS 1
Operating Voltage (47-63 Hz) [Vrms] 12-280 12-280 48-660 48-660
Max. Load Current [Arms] 20 30 20 30
Min. Load Current, [mArms] 150 150 150 150
Transient Overvoltage [Vpk] 600 600 1200 1200
Max. Surge Current, (16.6ms) [Apk] 250 625 250 625
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.4 1.6 1.4
Maximum I 2 t for Fusing, (8.3 msec.) [I 2sec] 260 1620 260 1620
Max. Off-State Leakage Current @ Rated Voltage [mArms] 20.1 0.1 0.1 0.1
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 3500 500 500 500
Max. Turn-On Time 41/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Max. Turn-Off Time 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS 1DC CONTROL
(HPF240Dxx) (HPF480Dxx)
Control Voltage Range 4-32 Vdc 4.5-32 Vdc
Max. Turn-On Voltage 5.0 Vdc 5.0 Vdc
Min. Turn-Off Voltage 1.0 Vdc 1.0 Vdc
Nominal Input Impedance See Note 5See Note 5
Typical Input Current @ 5Vdc 5 mAdc 5 mAdc
Typical Input Current @ 20Vdc 20 mAdc 20 mAdc
GENERAL NOTES
1All parameters at 25ºC unless otherwise specified.
2Off-State leakage for snubbered version (S suffix) is 10 mArms
3Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
4Turn-on time for random turn-on version is 0.02 msec.
5Input circuitry incorporates active current limiter.
6Operating voltage range for snubbered version (S-suffix) is 48-530 Vrms.
• DIN Rail Mount
• Integral Heat sink
• LED Status Indicator
• SCR Output
• Zero Voltage and Random
Turn-On Switching
• Low Leakage
SERIES HPF.
Rev. 102607
PAGE 1 OF 3
2
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
The Series HPF Solid State Relays utilize
Crydom’s proprietary thermal man-
agement technology providing a com-
pact and efficient design. Built-in DIN
Rail attachment, easy-to-use cage type
terminals and integral heat sinking
complete the package. This compact
new design offers up to 30Arms in
ambient temperatures of 25°C.
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
© 2007 CRYDOM Inc., Specifications subject to change without notice.
Series HPF
20, 30Amp • 120/240/480 Vac - AC OUTPUT
66
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Inc., 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 606030 • FAX +44 (0)1202 606035 Crydom SSR Ltd., Arena Business Centre,
Holyrood Close, Poole, Dorset BH17 7FJ, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506