SIMATIC NET
Industrial Remote Communication
TeleService
TS Gateway
Operating Instructions
Version V3
09/2014
C79000
-G8976-C380-01
Preface
Application and properties
1
Installation, commissioning
and operation
2
Configuration
3
Examples of the
configuration data of SMS
gateway providers
A
Documentation references
B
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
C79000-G8976-C380-01
09/2014 Subject to change
Copyright © Siemens AG 2014.
All rights reserved
Preface
Purpose of the manual
This manual supports you during the configuration, installation, commissioning and operation
of the TS Gateway application.
Validity of this manual
This manual applies to the following software versions:
TS Gateway - Version V3.0
Abbreviations/acronyms
Mobile wireless CP
CPs to connect the S7-1200 to a mobile wireless network, for example CP 1242-7
TCSB
TeleControl Server Basic as of Version V3
CMT
Configuration and Monitoring Tool: Program user interface of TS Gateway
New in this release
First issue
TS Gateway (version V3) is the successor to TS Gateway (version V2).
TS Gateway V3 supports 2 connection resources to a TeleService server at the same time
per station. In an existing TeleService session, a second connection resource of the
engineering station is used to load the project data.
You will find detailed information about the functions in the section Application and properties
(Page 9).
Replaced documentation
None
Required experience
To be able to configure and operate the system described in this document, you require
experience of the following products, systems and technologies:
SIMATIC S7
SIMATIC NET / TeleControl
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 3
Preface
STEP 7 Basic / Professional
IP-based communication
You will find further reading in the References in this manual.
Further information on the Internet
You will find further information on the Siemens telecontrol products such as the latest
information, manuals, FAQs or software updates on the Internet on the pages of Siemens
Industry Online Support under the following entry ID:
89330723 (http://support.automation.siemens.com/WW/view/en/89330723)
There select the required information under "Entry type" (for example "Updates", "Manuals",
"FAQs" etc.)
TeleService example of an application on the Internet
An example of an application for TeleService access from an engineering station via the
Internet to an S7 station with a mobile wireless CP can be found on the Internet on the
pages of Siemens Automation Customer Support under the following entry ID:
56720905 (http://support.automation.siemens.com/WW/view/en/56720905)
License conditions
Note
Open source software
Read the license conditions for open source software carefully before using the product.
You will find license conditions in the following documents on the supplied data medium:
DOC_OSS-S7CMCP_74.pdf
DOC_OSS-TSGW-V3_76.pdf
SIMATIC NET glossary
Explanations of many of the specialist terms used in this documentation can be found in the
SIMATIC NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection or product DVD
The DVD ships with certain SIMATIC NET products.
On the Internet under the following entry ID:
50305045 (http://support.automation.siemens.com/WW/view/en/50305045)
TS Gateway
4 Operating Instructions, 09/2014, C79000-G8976-C380-01
Preface
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. For more information about industrial security, visit
http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. For more information, visit http://support.automation.siemens.com.
Training, Service & Support
You will find information on Training, Service & Support in the multi--language document
"DC_support_99.pdf" on the data medium supplied with the documentation.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 5
Preface
TS Gateway
6 Operating Instructions, 09/2014, C79000-G8976-C380-01
Table of contents
Preface ................................................................................................................................... 3
1 Application and properties .......................................................................................................... 9
1.1 Properties............................................................................................................................ 9
1.2 Subcomponents of TS Gateway ........................................................................................ 12
1.3 Configuration examples ..................................................................................................... 12
2 Installation, commissioning and operation ....................................................................................15
2.1 Compatible operating systems for the application .............................................................. 15
2.2 Installation of the software ................................................................................................. 15
2.3 Changing port and network settings ................................................................................... 18
2.4 Installation of two TeleService gateways ............................................................................ 19
2.5 Wake-up SMS for the CP 1242-7 (firmware V1.x) .............................................................. 19
2.6 Overview of the passwords ................................................................................................ 20
3 Configuration ..........................................................................................................................21
3.1 The Configuration and Monitoring Tool (CMT) ................................................................... 21
3.2 Windows and buttons of the CMT ...................................................................................... 22
3.2.1 Window layout and Editing................................................................................................. 22
3.2.2 The buttons of the CMT ..................................................................................................... 24
3.2.3 Menu bar ........................................................................................................................... 25
3.2.4 Individual adaptation of the window ................................................................................... 25
3.2.5 Online help ........................................................................................................................ 26
3.3 Starting CMT - changing passwords .................................................................................. 26
3.4 Creating and configuring projects ...................................................................................... 29
3.5 Setting up an administrator ................................................................................................ 32
3.6 TCSB system .................................................................................................................... 33
3.7 Changing port settings ....................................................................................................... 37
3.8 Configuring SMS gateway providers .................................................................................. 37
3.9 SMTP server ..................................................................................................................... 40
A Examples of the configuration data of SMS gateway providers ........................................................41
B Documentation references ........................................................................................................43
B.1 /1/...................................................................................................................................... 43
B.2 /2/...................................................................................................................................... 44
B.3 /3/...................................................................................................................................... 44
Index .....................................................................................................................................45
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 7
Table of contents
TS Gateway
8 Operating Instructions, 09/2014, C79000-G8976-C380-01
Application and properties
1
1.1
Properties
Use of TS Gateway
TS Gateway is an application used for TeleService connections via the mobile wireless
network with remote SIMATIC stations of the type S7-1200 with a mobile wireless CP.
What is a TeleService gateway?
A TeleService gateway is a PC on which the "TS Gateway" software is installed.
The TeleService gateway is not configured in STEP 7.
What functions does the TeleService gateway provide?
The TeleService gateway has the following functions:
Switching station
The TeleService gateway is a PC in the network that serves as the intermediary between
the engineering station and remote S7 station.
Since a firewall is normally closed for connection requests from the outside, a switching
station between the remote station and the engineering station is required. This switching
station can be a telecontrol server or, if there is no telecontrol server in the configuration,
a TeleService gateway. The switching station directs the messages via a tunnel through
the firewall. This allows access by the engineering station connected to a LAN to the S7-
1200 via a router and via the APN of the network provider.
Configuration of the SMS gateway provider
With the help of TS Gateway, SMS gateway providers are configured that are necessary
for the sending of an SMS message to the remote S7 stations.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 9
Application and properties
1.1 Properties
Configuration with TeleService gateway
A TeleService gateway is intended for the following telecontrol systems in which TeleService
is used via a mobile wireless network:
Configurations without a telecontrol server
In configurations without a telecontrol server, a TeleService gateway is required for
TeleService via the mobile wireless network.
Configurations with telecontrol server
In configurations in which a second path needs to be established for TeleService via the
mobile wireless network alongside the telecontrol server, a TeleService gateway can be
used.
This can, for example, be the case when certain people, groups or companies should not
operate TeleService via the telecontrol server or when access to the stations for
TeleService needs to be set up independent of the telecontrol server.
Range of performance of a TS Gateway
Number of simultaneous TeleService connections in total: 1
Note
TS Gateway only for TeleService
TS
Gateway is used only for the "TeleService" function via the mobile wireless network.
No connections to the remote stations can be monitored and no process data can be
transferred.
First and second TeleService gateway
If the requirements for availability are higher, you can install TS Gateway on two
independent computers. If the connection cannot be established via the first gateway, you
can establish the TeleService connection via the second TeleService gateway. The two
systems are independent of each other and in terms of the range of functions identical.
TS Gateway
10 Operating Instructions, 09/2014, C79000-G8976-C380-01
Application and properties
1.1 Properties
Requirements for TeleService with the TeleService gateway
The following requirements must be met for TeleService via a TeleService gateway:
Engineering station connected to a LAN or with Internet access
TeleService using the mobile wireless network is possible on an engineering station with
the STEP 7 project that contains the remote station with the mobile wireless CP.
STEP 7 version required for TeleService via the mobile wireless network: V13.x
PC for the TeleService gateway with:
DVD drive
Connection to LAN or Internet access for connecting to the engineering station
Internet access for connecting to the remote S7 station
Installation of the "TS Gateway" application
The software ships with the mobile wireless CP (see product DVD).
TeleService for S7-1200 with mobile wireless CP
The TeleService functions for the mobile wireless CP are described in the manual of the CP,
refer to /2/ (Page 44), and in the online help of STEP 7.
TCSB or a TeleService gateway automatically makes 1 access point available for
TeleService per project. This means that up to 1 TeleService user can access the stations of
a project.
An engineering station is required for each TeleService connection.
Per station, 1 TeleService session is possible. In an existing TeleService session, a second
connection resource of the engineering station is used to load the project data.
Monitoring times when establishing TeleService connections
When a TeleService connection is established, the following monitoring times are used:
Establish TeleService connection but no online connection: An interrupted connection is
detected after 1 minute.
Disconnection of a TeleService connection:
Follow-up time of approx. 5 minutes
Within the follow-up time, the connection between the telecontrol server / TeleService
gateway and CP is maintained.
If a new TeleService connection is established during the follow-up time, no new
wake-up SMS is sent to the station.
If a TeleService connection aborts, a new TeleService connection is not established
automatically.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 11
Application and properties
1.2 Subcomponents of TS Gateway
1.2
Subcomponents of TS Gateway
Main components of the application
TS Gateway is made up of the following main components:
Telecontrol Manager (TCM)
The Telecontrol Manager manages the connections with communications partners. This
is the communications center of all connected software components in the PC side and
the process side. It controls the frames between the sender and destination address and
has the logical connection information and configuration information.
The Telecontrol Manager is not visible to the user. The configuration of the access data is
created using the CMT (see below).
Database
The database stores the configuration data and system messages. The database is not
visible to the user. The user interface to the database is CMT (see below).
The database has separate areas for the offline configuration data and for the online
configuration data of the runtime system. With the Enable function in CMT, the
configuration data is shifted from the offline to the online area of the runtime system.
Configuration and Monitoring Tool (CMT)
The CMT is the program user interface for setting up and configuring the system.
1.3
Configuration examples
With an S7-1200 with a mobile wireless CP, a TeleService connection runs via the Internet
and the mobile wireless network.
The following figures show the typical configurations for the use of the TeleService gateway.
TS Gateway
12 Operating Instructions, 09/2014, C79000-G8976-C380-01
Application and properties
1.3 Configuration examples
Installation of TS Gateway on the computer of the engineering station
Figure 1-1 Installation of TS Gateway on the computer of the engineering station
In this case, the "TS Gateway" application is installed on the engineering Station.
Installation of TS Gateway on a separate computer
Figure 1-2 Installation of TS Gateway on a separate computer
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 13
Application and properties
1.3 Configuration examples
In this case, the "TS Gateway" application is not installed on the engineering Station but on a
separate computer. The engineering station and TeleService gateway are connected via an
Intranet.
TeleService via a local or a remote engineering station
Figure 1-3 TeleService via a local or a remote engineering station
As an alternative, TeleService can be operated from two engineering stations:
A central engineering station connected to the TeleService gateway via an intranet.
The connection between the engineering station and S7 station is via the TeleService
gateway, the Internet and the mobile wireless network.
A remote engineering station connected to the TeleService gateway via the Internet.
The connection between the engineering station and S7 station is via the Internet to the
TeleService gateway and from there further via the Internet and the mobile wireless
network.
Simultaneous access by both engineering stations to the same mobile wireless CP is not
possible.
TS Gateway
14 Operating Instructions, 09/2014, C79000-G8976-C380-01
Installation, commissioning and operation
2
2.1
Compatible operating systems for the application
Compatible operating systems
the application can run on a PC with one of the following operating systems:
Single installation
Microsoft Windows 7 Professional 32/64-bit + Service Pack 1
Microsoft Windows 7 Enterprise 32/64-bit + Service Pack 1
Microsoft Windows Embedded 7 32-bit
Microsoft Windows Server 2008 32-bit + Service Pack 2
For this operating system, you require Windows PowerShell.
Microsoft Windows Server 2008 R2 64-bit + Service Pack 1
2.2
Installation of the software
Firewall settings (ports)
Just as with any computer connected to the Internet or to another IP network, the
TeleService gateway should be protected at least by the firewall of the operating system
and/or the connected router against attacks from the connected network.
Remember that during installation of the system, several ports need to be opened and other
changes need to be made in your system. These settings are displayed during installation.
You can print these settings during the installation or save them in a log file.
Note
Response to a deactivated firewall
If the firewall is deactivated during installation, the necessary incoming and outgoing rules
will not be created. In this case, no warning is output.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 15
Installation, commissioning and operation
2.2 Installation of the software
Commissioning the TeleService gateway
1. Set up the PC according to the documentation that ships with the PC.
2. Connect up the following connectors on the PC:
Monitor, keyboard, mouse
Power supply
Local area network if the engineering station is connected via a LAN.
Internet
Note the information from the network provider and the manufacturer of the router
3. Turn on the PC.
4. Set up the following access:
Local LAN connection
Internet access
5. Insert the product DVD that ships with the CP in the DVD drive.
6. In the file management of the PC, an open the DVD root directory > folder "TS Gateway".
7. Start the installation by double clicking on the "setup.exe" file.
The installation of the software begins automatically. A wizard guides you through the
remaining steps in installation.
Figure 2-1 Section of the window of the installation wizard of TS Gateway
8. Enable the two options "TeleService Gateway V3.x" and "SQL Server 2008 Express" and
click "Next".
During the installation, the "Database settings and certificates" dialog opens in which you
make the settings for the database, refer to the following section.
"Database settings and certificates" dialog
In this dialog, you configure the following:
Database password
Use of an existing database of TS Gateway V2 / TCSB V2 if available
If an older version V2 is installed on your computer, you have the option of using your
previous data.
TS Gateway
16 Operating Instructions, 09/2014, C79000-G8976-C380-01
Installation, commissioning and operation
2.2 Installation of the software
Figure 2-2 "Database settings and certificates" dialog
Database password
In the "Assign a password for your database:" box, Assign the database password for later
access to the database of TS Gateway to be installed.
Note
Note down the database password
You only require this password if you want to access the database using Microsoft tools. You
do not require the password for any activities in t
he system.
Import a TCSB V2 database
If there is already a version V2 of the gateway on your computer, you have the option of
continuing to use the data of your existing system. To do this, continue to use the database
of the TeleService gateway V2. You control this during the installation in the "Import a TCSB
database V2" box.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 17
Installation, commissioning and operation
2.3 Changing port and network settings
In the "Import a TCSB V2 database" box, specify the use of the database using the following
options:
Do not import database
When the option is selected, you install the new database of the TS Gateway V3 /
TCSB V3 system. By doing this you specify that a new empty system will be created.
Existing data of an older system can no longer be used.
Select the storage location of the file "Smsc.sqlite".
If the option is selected, you continue to use your previous SQLITE database of the V2
system.
The preset path of the database in the file directory is displayed in the input box. If you
have moved your database to another location, you will need to enter the correct path in
the input box.
When all the options in the dialog are correctly set, confirm the dialog with OK. The
installation is continued and completed.
2.3
Changing port and network settings
Network settings
To ensure that the system operates correctly, the following settings must be made:
1. Open the following dialog in the Control Panel of the TS Gateway computer:
"Network and Internet" > "Network and Sharing Center" > "Advanced sharing settings"
2. Turn on "Network discovery" for both networks "Home or Work" and "Public".
Opening changed ports
If you change port numbers, you will need to open the ports used in the router or using the
functions of the operating system.
Below you will find the ports of TS Gateway along with their significance and the default
numbers:
Listener port for stations of the type S7-1200 + mobile wireless CP
The port must be opened for communication with the engineering station and with remote
stations of the type S7-1200 with a mobile wireless CP.
Default port number: 55097
Port of the database server
Port of the database server for TCP connections with CMT client PCs
Default port number: 26865
You can change the default port numbers in the CMT, refer to section TCSB system
(Page 33) > "Listener ports".
TS Gateway
18 Operating Instructions, 09/2014, C79000-G8976-C380-01
Installation, commissioning and operation
2.4 Installation of two TeleService gateways
2.4
Installation of two TeleService gateways
Installation of two TeleService gateways
If you install TS Gateway on two computers, two parallel systems of TS Gateway are
installed that are independent of each other. In terms of the range of functions, both systems
are identical and do not monitor each other.
Configuration
Make sure that the configuration of both systems is consistent, especially the configuration of
the projects.
2.5
Wake-up SMS for the CP 1242-7 (firmware V1.x)
Wake-up SMS
Waking the station by a TeleService gateway is achieved by sending an e-mail. The e-mail is
sent to an SMS gateway via an SMTP server. The SMS gateway converts the e-mail into an
SMS message and transfers this to the station.
The SMS gateway is configured in the CMT of the TeleService gateway, refer to the section
Configuring SMS gateway providers (Page 37).
If the wake-up SMS message is sent from a phone, the number of the phone must be
authorized in the STEP 7 configuration of the receiving CP (refer to "Authorized phone
numbers"). The telephone must support the CLIP function (transfer of its own call number)
and the sending of SMS messages.
The wake-up SMS message is not send extra when a TeleService connection is established,
it is generated automatically by the TeleService gateway.
Depending on the switching TeleService gateway, the following text must be transferred in
the wake-up SMS:
Text for the wake-up SMS message for establishing a connection via the first TeleService
gateway (TeleService server):
TELESERVICE
or
TELESERVICE 1
Text for the wake-up SMS message for establishing a connection via the second
TeleService gateway (TeleService server) - if it exists:
TELESERVICE 2
You configure the TeleService server in STEP 7 in the "TeleService settings" parameter
group of the mobile wireless CP.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 19
Installation, commissioning and operation
2.6 Overview of the passwords
2.6
Overview of the passwords
Overview of the passwords used during operation
Below, you will find an overview of the passwords used on the TeleService gateway.
No.
Password
Password configuration in
...
Password entry in ...
Function
Administrator pass-
word
CMT of the TeleService
gateway
CMT (at startup) Protection of the TeleService
gateway from unauthorized
access
TeleService password CP (per station in STEP 7) STEP 7 (TeleService
startup)
Protection from access to the
CP in TeleService
Server password Per project in CMT (TCSB
only)
STEP 7 (TeleService
startup)
Protection from access to the
TeleService gateway in Tele-
Service
Figure 2-3 Overview of the passwords used. The numbers correspond to those in the table.
Other passwords required by the mobile wireless, SMTP server or SMS gateway providers
or when installing the database are not listed here.
TS Gateway
20 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3
3.1
The Configuration and Monitoring Tool (CMT)
The Configuration and Monitoring Tool (CMT)
The Configuration and Monitoring Tool (CMT) is the programm user interface of TS Gateway
and is used to configure the following parameters and settings:
System of the TeleService gateway
Address data of the gateway and port numbers
Authorized phone number for connections to the CPs
Projects (optional)
If you have configured different projects with different server passwords for the telecontrol
server, you must create projects with the same name in the CMT of the gateway.
SMS gateway provider
SMTP server
Functions not supported
The CMT of TS Gateway is a special form of the CMT of the "TeleControl Server Basic"
(TCSB) software. This contains several functions that are not supported by the CMT of the
TS Gateway application.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 21
Configuration
3.2 Windows and buttons of the CMT
3.2
Windows and buttons of the CMT
3.2.1
Window layout and Editing
Layout of the user interface
The program user interface of the CMT is divided into the following areas:
Figure 3-1 Window layout of the CMT
The subareas have the following functions:
No.
Area / subarea
Function
Title bar Display of the name of the program
Menu bar Contains the menus
System navigation Shows the structure of the parameter groups: Projects, users (admin-
istrator), system, SMS gateway provider, SMTP server
The individual objects of the selected parameter group are displayed
in the object area.
TS Gateway
22 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.2 Windows and buttons of the CMT
No.
Area / subarea
Function
Object area Depending on the entry selected in the system navigation, the follow-
ing content is displayed:
Projects and their parameters
Administrator
System parameters
SMS gateway provider, SMTP server
Command bar Contains buttons for functions in the context of the particular object
area
Parameter area Shows the parameters of the object selected in the object area.
Message window Displays the accumulated system messages. The window is opened
using the "View" > "Messages" menu and is closed again using the
'X' icon at the top right.
Status bar Shows the connection status of CMT and the logged in users.
Parameter area - Editing objects
The parameter area shows the parameters of the object selected in the object area. The
individual parameters are described in the sections that follow.
The following applies generally:
The displayed parameters depend on the object selected in the object area.
As default, all the parameter boxes are grayed out and cannot be edited.
To be able to edit permitted boxes, prior to editing, the "Edit" button (see below) must be
enabled.
The configuration must be consistent (for example the SMS number of a station must not
be assigned more than once).
If an input box is intended only for certain types of character, other types of character will
be rejected.
Example: Letters cannot be entered in input boxes for phone numbers.
While they are being entered and prior to being transferred to the runtime system,
parameters are checked for plausibility.
Invalid parameters
Incomplete input boxes and input boxes containing fobidden characters are declared
invalid during the plausibility check and shown on a red background (see figure).
Figure 3-2 Marking of input boxes with forbidden content
Objects with bad parameters are given the configuration status "invalid".
Figure 3-3 Marking of objects with invalid parameters
Invalid parameters are not stored in the database.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 23
Configuration
3.2 Windows and buttons of the CMT
Editing objects
Before boxes can be edited, an object must first be enabled using the "Edit" button.
After editing has been enabled, the editing icon () appears in the left-hand column in the
object area.
After saving, edited boxes are grayed out again and the editing icon () disappears.
3.2.2
The buttons of the CMT
The most important buttons in the CMT
After starting the CMT, all the input boxes in the program user interface are locked.
Configuration is only possible and other buttons can only be selected after clicking the "Edit"
button. The buttons described below can be found in most views of the CMT.
Edit
Enables the objects or parameters displayed in the object or parameter area for
configuration.
Add
Generates a new object in the particular view.
Delete
Deletes the selected object
Discard
Discards all the changes made in the current view and restores the status as it was after
the last save.
Save
To avoid changed data being lost when you exit a view, you need to save any changes
you have made.
In some views, you can only "Save & activate"; this means that the changed data is
transferred to the runtime system when you save.
Save & activate
Relevant for connection and project data
Before the configured data of connections takes effect in the runtime system, the relevant
project must be activated. The configured data can only be transferred to the runtime
system for entire projects.
If you have not yet saved the configuration data, the configuration data is saved first in
the database prior to activation.
TS Gateway
24 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.2 Windows and buttons of the CMT
3.2.3
Menu bar
The menu bar contains the following menus:
"File" menu
Menu command
Function
Exit
Closes the CMT.
"View" menu
Menu command
Function
Messages
Shows the messages of the system below the parameter area.
"Options" menu
Menu command
Function
Language
Opens a drop-down list for setting the language used by the CMT.
"Help" menu
Menu command
Function
Help
Opens the online help of the CMT.
About
Shows version information of the program.
3.2.4
Individual adaptation of the window
Adapting the view
The following options are available for adapting the program user interface:
Changing the size of areas
By moving the dividing line between the individual areas, you can change the size of the
areas in the window.
Changing the column width in the object area *)
By moving the dividing lines in the table header with the mouse, you can change the
width of the columns in the object area.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 25
Configuration
3.3 Starting CMT - changing passwords
Sorting entries in the object area
If you click on a column header, you can sort the entries in the table in ascending or
descending order according to this column.
Changing the column order
By selecting a column header and moving it while holding down the mouse button, you
can move the column to the right or left.
*) This also applies the system variables in the parameter area.
3.2.5
Online help
Opening online help
You open the online help of CMT with the menu "Help" > "Online help".
3.3
Starting CMT - changing passwords
Starting the CMT
To start the CMT, select the following program:
Windows Start menu > Siemens Automation > SIMATIC > TCS Basic > Config and
Monitoring Tool
Logging on
After the program has started, the logon window of the CMT is displayed.
Figure 3-4 Logon window of the CMT
TS Gateway
26 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.3 Starting CMT - changing passwords
1. Enter a configured user name or leave the default user name.
You will find information on the first login in the next section.
2. Enter the corresponding password.
You will find information on the first login in the next section.
3. Click the "Logon" button.
When you log on for the first time, you need to change the password immediately. Make
sure you read the notes below.
During all subsequent logons, the same window of the CMT opens.
Initial logon: User name and password
The following user data is set in the factory:
User data
Default values set in the factory
User name
administrator
Password
0000
Entering the wrong user name or password
If you enter a user name that is not configured, an error message is displayed regardless of
the password entered. One or a variety of incorrect user names can be entered any number
of times without the system being locked.
Note
Loss of the administrator password
Note down a newly assigned or modified administrator password and keep this in a safe
place.
If only one administrator is set up, the loss of the administrator password means that no
more administrator tasks can be performed.
There is no way in which the system can be reset to the factory-set administrator password.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 27
Configuration
3.3 Starting CMT - changing passwords
Note
Incorrect entry of the password
When entering the default user name:
If you enter an incorrect password with the default user name (see above) an error
message is displayed. You can attempt to enter the factory-set password any number of
times to log on with the system.
If you enter an incorrect password, a lock out time begins that is extended with each
attempt to logon with an incorrect password.
When entering a configured user name:
If you enter an incorrect password along with a configured user name, an error message
is displayed.
If you enter an incorrect password, a lock out time begins that is extended with each
attempt to logon with an incorrect password.
Formats and lengths for user names and passwords
User names
Length (characters): Minimum 1, maximum 32
The following ASCII characters are permitted (digits, lowercase letters, uppercase letters,
many special characters):
0x20 ... 0x7e
0x80 ... 0xff
Passwords
Length (characters): Minimum 8, maximum 32
The following ASCII characters are permitted (digits, lowercase letters, uppercase letters,
many special characters):
0x20 ... 0x7e
0x80 ... 0xff
TS Gateway
28 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.4 Creating and configuring projects
3.4
Creating and configuring projects
View when the "Projects" entry is selected in the navigation area
With this selection, the CMT displays the following screen:
Figure 3-5 Object area when the "Projects" entry is selected in the navigation area
The "Projects" tab displays the configuration data of the individual projects in the form of a
table.
Purpose of creating projects
To use the functions of the TeleService gateway, it is not absolutely essential to create
projects. If you do not create a project, the provider listed first in the drop-down list will be
used as the SMS gateway provider".
In larger systems, in which all stations are not accessed via the same SMS gateway
provider, you can create various projects that are then assigned to a specific SMS gateway
provider. The stations to be accessed via a specific SMS gateway provider are grouped
together in a project. This means that you do not need to change the provider data each
time.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 29
Configuration
3.4 Creating and configuring projects
A unique project number must be assigned to each CMT project that matches the project
number of the CPs in the STEP 7 project.
Note
Consistency with the STEP 7 project
Make sure that the project number in the CMT is consistent with the project number of the
mobile wireless CP in the STEP 7 project.
The SMS gateway provider is assigned to the project in the parameter area (see below).
Parameters of projects
The mandatory parameters "Project name" and "Project number" of the project must be
completed by the administrator.
Project name
Assign a project name.
The mandatory parameter is checked for consistency when it is entered.
If the entry is inconsistent, the input box is shown with a red frame.
Project number
Assign the project number.
The mandatory parameter is checked for consistency when it is entered.
If the entry is inconsistent, the input box is shown with a red frame.
As long as no project number has been entered, the input box has a red frame and the
configuration cannot be saved.
Note
Consistency with the STEP 7 project
The project number assigned here must be identical to the project number of the mobile
wireless
CP in STEP 7 because it forms part of the address of the connections.
Check and agree the project number with the configuration engineer of the STEP 7
project.
TS Gateway
30 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.4 Creating and configuring projects
SMS gateway provider
From the drop-down list, select the SMS gateway provider via which you want to send a
wake-up SMS message to the remote stations.
Comment
Optional: If necessary, enter a comment (max. 200 characters).
Note
Saving configuration data
Following configurat
ion, save the project otherwise the configuration data is lost.
When you save, the configuration data is saved in the database but is not transferred to
the runtime system.
Creating projects
Create new projects as follows:
1. Select the "Projects" entry in the navigation panel.
2. Click the "Add" button.
The new project appears in the navigation area and in the object area.
3. Click the "Create" button.
Activating projects
Once you have completed the configuration in the CMT, you need to transfer the modified
data to the runtime system using the "Save & activate" button so that the configuration data
becomes effective for the connection establishment. Configuration data can only be
transferred for entire projects not for individual stations.
Deleting projects
Deleting inactive projects
If the project to be deleted contains no or only new data records (the project has not yet
been activated), it is deleted immediately.
Deleting projects that have already been activated
If the project to be deleted already contains activated data records, deleting initially
changes it to the "To delete" status. To delete the configuration data from the runtime
system, it must then be activated. Only then is the entire delete procedure completed.
To delete a project, follow the steps outlined below:
1. Select the "Projects" entry.
2. Select the project in the object area.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 31
Configuration
3.5 Setting up an administrator
3. Click the "Delete" button.
The project disappears if it contains no or only new data records.
In this case, deleting is completed.
The project changes to the "To delete" status if it was previously activated
(configuration data in the runtime system).
4. Activate the project that has the "To delete" status.
The project is finally deleted.
3.5
Setting up an administrator
Configuration of the administrator
With the "Users" entry in the navigation area, you can edit the user properties of the
administrator:
"General" parameter group
The following data must be entered when they are created.
User name
User name of the administrator, is used to log in to CMT.
Password
Password of the administrator, is used to log in to CMT.
Note
Loss of the administrator password
Note down a newly assigned or modified administrator password and keep this in a
safe place.
Once the administrator has been set up, the loss of the administrator password means
that the system can no longer be configured or operated.
There is no
way in which the system can be reset to the factory-set administrator
password.
First and last name of the administrator are optional.
"Contact information" parameter group
All contact information is optional and can be entered and modified by the administrator.
E-mail address
Call number
Mobile phone number
Address
TS Gateway
32 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.6 TCSB system
3.6
TCSB system
Selection of the navigation entry "TCSB system"
Under this entry, you will find the parameters to make settings for the following system
components:
TCM
Database
Only administrators can make the settings for the system.
If you expand the "TCSB system"entry, the following further entries will be visible and these
are described in the following sections:
SMTP gateway provider
SMTP server
TCSB system, "TCM" tab
"General" box
Here, you configure the address data of the TeleService gateway and, if it exists, the second
gateway.
Figure 3-6 The "TCSB system" > "TCM" dialog
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 33
Configuration
3.6 TCSB system
Here, the IP address and the ports of the TeleService gateway are configured.
Note
Consistency with the STEP 7 project or block configuration
The address data to be configured here is also configured in the STEP 7 project of the
mobile wireless CP.
The configuration of an IPv4 address is mandatory. IPv4 addresses are given preference by
the gateway. The configuration of an IPv6 address is necessary if stations that use the IPv6
standard are connected to the gateway.
As default the computer name of the relevant PC is entered in the input box of the IPv6
address of TCM 1.
The relevant port numbers are preassigned. If necessary you can change these.
The following applies to all ports: The port number must be between 1 025 and 65 535.
Address TCM 1 or TCM 2
IP address of the TeleService gateway
Select one of the following entries:
The valid IP address of the computer
"localhost" entry
Entry "127.0.0.1" for the first gateway
Entry "127.0.0.2" for the second gateway
In addition to the addresses in IPv4 format, you can also specify the addresses in IPv6
format.
"Listener ports" box
If necessary, you can change the default numbers of listener ports of the system here.
Note
Port numbers used
If you change port numbers, note the information in the section
Changing port settings
(Page
37).
MSC listener port
Not relevant for TeleService gateway
Default port number: 26862
ITP listener port
Listener port for stations of the type S7-1200
The port must be opened for communication with the engineering station and with remote
stations of the type S7-1200 with a mobile wireless CP.
Default port number: 55097
TS Gateway
34 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.6 TCSB system
Control port
Not relevant for TeleService gateway
Default port number: 26861
Data port
Not relevant for TeleService gateway
Default port number: 26860
TCSB port
The port must be opened for the TCM to communicate with the CMT.
Default port number: 26864
Note
After changing and saving the port numbers, a restart is necessary for the changes to take
effect.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 35
Configuration
3.6 TCSB system
TCSB system, "Database" tab
Authorized phone number
Here, enter the string of numbers of the phone number that authorizes the TeleService
gateway to establish a connection with the mobile wireless CP.
This number configured for the CP is transferred to the CP with the SMS message.
The phone number entered here must be configured in the STEP 7 project of the CPs in
the list of phone numbers under the "Authorized phone number" parameter.
Note
Permitted character set
Keep to the permitted ASCII character set for the parameter: 0x20...0x7e and 0x80...0xff.
The hash '#' (0x23) must not be used.
Regular backup
For archiving purposes or if you want to transfer the configuration to another computer,
you can use this function to make regular copies of the entire database.
So as not to reduce the storage capacity of your hard disk too much, if you have short
backup intervals, you should delete older backup copies from time to time or move them
to a different data storage medium.
Select the interval at which backup copies of the database will be created.
The backup copies are saved as *.bak files in the following directory:
<Drive>:\Microsoft SQL Server\MSSQL10_50.TCSB\MSSQL\Backup
Backup copies are always created at 00:00h.
Restart:
When TS Gateway is restarted, the counter for the time of creation of the backup copies
is reset and the period is counted starting from the time of the restart. This changes the
time at which the backup copies are made. If you have configured the creation of backup
copies and restart the gateway computer, the backup copies will be created at the
configured intervals again starting from the day of the restart.
TS Gateway
36 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.7 Changing port settings
3.7
Changing port settings
Changing and opening ports
Changing port numbers
If you change port numbers, select ports only from the number range 1024 ... 65535. Select
free ports that are not otherwise being used.
Ports 0 ... 1023 are standardized (well known ports). Of the registered ports as of 1024, no.
1024 is reserved.
Opening a port automatically
Port 587 used for the SSL authentication of TS Gateway with the SMTP server or SMS
gateway provider is opened by TS Gateway during installation.
Preset numbers of the listener ports of the Telecontrol Manager (TCM)
For the internal communication of the components of TS Gateway and TCM with the
stations, various ports are used whose numbers are preset by the system.
You can change the default port numbers in the CMT. The function of the ports and the
presettings are described in the following section: TCSB system (Page 33), "TCM" tab
3.8
Configuring SMS gateway providers
Only an administrator can setup and configure SMS gateway providers.
Function
The SMS gateway provider forwards an SMS message to the remote stations. The
sequence of transmission is as follows:
1. The TeleService gateway sends an e-mail.
2. The e-mail is sent to an SMS gateway via an SMTP server.
3. The SMS gateway converts the e-mail into an SMS message and transfers this to the
station.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 37
Configuration
3.8 Configuring SMS gateway providers
View
Select the "SMS gateway provider" entry in the navigation area.
Figure 3-7 Dialog box for configuring an SMS gateway provider
The name and e-mail address of the SMS gateway providers that have already been created
are displayed in the object area.
The data of the provider selected above is configured in the parameter area.
Identification: Authorized phone number
To allow the mobile wireless CP to identify the TeleService gateway as the sender of an
SMS message, a computer ID is transferred in the e-mail. This ID must be configured in the
system settings as an "authorized phone number" before the sender of the SMS will be
accepted by the CP. The "authorized phone number" is configured in the system settings,
refer to the section TCSB system (Page 33).
TS Gateway
38 Operating Instructions, 09/2014, C79000-G8976-C380-01
Configuration
3.8 Configuring SMS gateway providers
Configuring the parameters of the SMS gateway provider
Note
Parameters and placeholders
Remember that the SMS gateway providers have different requirements for the parameters
of the e
-mail. You will find examples in appendix Examples of the configuration data of SMS
gateway providers
(Page 41). There, you will also find the significance of the following
placeholders:
<SMS-NO>
Placeholder for the phone number of the mobile wireless CP
<MSG>
Placeholder for the content of "Re" and "Text" of the e-
mail that is automatically entered
in the e-mail by TS Gateway.
The data of the providers is entered in the parameter area:
Name
Here, enter the name of the SMS gateway provider (can be selected freely).
Address
E-mail address of the SMS gateway provider.
You will find the address in the agreement documents of your provider.
Re
Enter a suitable reference here.
With some providers, the text field contains the information indicating to the recipient
what needs to be done. The field can also include further job-specific information to allow
use of special services of a provider.
With some providers, the "authorized phone number" is entered here.
Ask your provider about the reference.
text
Enter a suitable text here.
Ask your provider about the text.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 39
Configuration
3.9 SMTP server
3.9
SMTP server
SMTP server
An SMS message of the TeleService gateway is sent as an e-mail. The SMTP server
forwards the e-mail to the SMS gateway.
In this dialog, you can configure up to two SMTP servers:
Server 1
Main server to which all e-mails are sent.
Server 2
Substitute server to which the e-mails are sent if the main server is not obtainable.
The following parameters must be configured:
Mail server
SMTP address of the SMTP server
Take the data from the agreement documents of your SMTP server provider.
Port number
Port number of the SMTP server
Take the data from the agreement documents of your SMTP server provider.
User name
Take the data from the agreement documents of your SMTP server provider.
Password
Take the data from the agreement documents of your SMTP server provider.
E-mail address
E-mail address of the TeleService gateway.
Take the data from the agreement documents of your SMTP server provider.
TS Gateway
40 Operating Instructions, 09/2014, C79000-G8976-C380-01
Examples of the configuration data of SMS gateway
providers
A
Examples of the configuration data of SMS gateway providers
The following table contains several examples of the configuration of the SMS gateway
providers on the CMT. See also section Configuring SMS gateway providers (Page 37).
You can find out from your SMS gateway provider how to configure the e-mail for the wake-
up SMS message.
Table A- 1 SMS gateway provider-related e-mail structures
SMS network provider
E-mail address of the SMS gateway provider *
Re **
Text **
E-Plus
<SMS-NO>@smsmail.eplus.de
<MSG> *
<MSG> *
O2 <SMS-NO>@o2online.de
***
<MSG>
*
<MSG>
*
Smstrade <SMS-NO>@email2sms.smstrade.de <MSG>
*
#Identifikationkey
#Sendroute
#Sender#
T-Mobile
<SMS-NO>@t-mobile-sms.de
<MSG> *
<MSG> *
Vodafone
<SMS-NO>@vodafone-sms.de
<MSG> *
<MSG> *
* <SMS
-
NO>
When configuring the e-mail address of the SMS gateway provider in the "Address" box,
enter the placeholder "<SMS-NO>". TCSB then automatically enters the call number of the
SIM card of the CP that originates from the CP configuration in STEP 7 and is transferred in
the frame of the engineering station.
** All cells of the table with the entry "<MSG>"
Enter the placeholder "<MSG>" in the "Re" or "Text" box. TCSB then automatically enters
the correct message that is stored in the system and understood by the CP 1242-7. (This is
the same text that is transferred in a wake-up SMS as the message text.) Wake-up SMS for
the CP 1242-7 (firmware V1.x) (Page 19)
***
The call number of the SIM card may only be entered in STEP 7 without the international
country dialing code.
Activating the e-mail address
To receive the e-mail, a personal mobile e-mail address needs to be activated with some
network providers. To do this, send an activation SMS with a short number to your SMS
network provider that you will find in the table below "Activation and deactivation SMS". You
will receive a personal e-mail address via SMS that is normally made up of the phone
number and the gateway name.
To activate your personal mobile e-mail address, send the special activation text to a short
number of your SMS network provider.
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 41
Examples of the configuration data of SMS gateway providers
You will receive a reply SMS with your personal mobile e-mail address that is made up of
your phone number and the gateway name of your SMS network provider, for example:
0123412345678@providersms.com
You will find examples of activation texts and short numbers of SMS network providers in the
following table.
Note
Check with your network provider whether or not it is necessary to send activation and
deactivation SMS messages. Your network provider will inform you of the texts and short
number.
Table A- 2 Activation and deactivation SMS (examples)
E-Plus
O2 Germany
T-Mobile
Vodafone
Gateway name
smsmail.eplus.de
o2online.de
t-mobile-sms.de
vodafone-sms.de
Enabling
Send SMS with text to
short number
Text: START
Short number:
7676245
Text: OPEN
Short number:
6245
Text: OPEN
Short number: 8000
Text: OPEN
Short number: 3400
Deactivating
Send SMS with text to
short number
Text: STOP
Short number:
7676245
Text: STOP
Short number:
6245
Text: CLOSE
Short number: 8000
Text: CLOSE
Short number: 3400
TS Gateway
42 Operating Instructions, 09/2014, C79000-G8976-C380-01
Documentation references
B
Where to find Siemens documentation
You will find the article numbers for the Siemens products of relevance here in the
following catalogs:
SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI
SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog
ST 70
You can request the catalogs and additional information from your Siemens
representative.
You will find SIMATIC NET manuals on the Internet pages of Siemens Automation
Customer Support:
(http://support.automation.siemens.com/WW/view/en)
Enter the entry ID of the relevant manual as the search item. The ID is listed below some
of the reference entries in brackets.
As an alternative, you will find the SIMATIC NET documentation on the pages of Product
Support:
10805878 (http://support.automation.siemens.com/WW/view/en/10805878)
Go to the required product group and make the following settings:
"Entry list" tab, Entry type "Manuals / Operating Instructions"
You will find the documentation for the SIMATIC NET products relevant here on the data
medium that ships with some products:
Product CD / product DVD or
SIMATIC NET Manual Collection
B.1
/1/
SIMATIC NET
TS Gateway (Version V3)
Operating Instructions
Siemens AG
entry ID: 102255310 (http://support.automation.siemens.com/WW/view/en/102255310)
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 43
Documentation references
B.2 /2/
B.2
/2/
SIMATIC NET
CP 1242-7
Operating Instructions
Siemens AG
entry ID: 61029644 (http://support.automation.siemens.com/WW/view/en/61029644)
B.3
/3/
SIMATIC NET
TeleControl Server Basic (Version V3)
Operating Instructions
Siemens AG
entry ID: 46635999 (http://support.automation.siemens.com/WW/view/en/46635999)
TS Gateway
44 Operating Instructions, 09/2014, C79000-G8976-C380-01
Index
A
Administrator password, 27, 32
Loss, 27
ASCII characters
Users + passwords, 28
Authorized phone number, 36, 38
C
Changing port numbers, 33
Character set
Users + passwords, 28
CMT (Configuration and Monitoring Tool), 12
D
Database password, 16
E
Edit, 24
Export certificate, 26
F
Firewall settings, 15
G
Glossary, 4
I
Invalid parameters, 23
P
Password
Administrator, 27
Invalid entry, 27
Loss, 27
Port 587, 37
Ports
Numbers, 37
Opening, 37
S
Service & Support, 5
SIMATIC NET glossary, 4
SMS gateway provider, 37
SSL authentication, 37
T
TCM (Telecontrol Manager), 12
Telecontrol Manager, 12
TeleService server, 19
Training, 5
U
User name: Invalid entry,
V
Validation, 23
W
Wake-up SMS, 37
Wrong entry, user name, 27
TS Gateway
Operating Instructions, 09/2014, C79000-G8976-C380-01 45
Index