Fuji Electric FA Components & Systems Co., Ltd./D & C Catalog
Information subject to change without notice
09
09/61
Instrument Transformers
CT with primary winding/CC3P
■
Description
CC3P CTs support primary winding for easy
wiring.
The mounting base can be rotated anywhere
in a 90° range to facilitate installation.
A double-mold structure gives CC3P CTs
excellent moisture resistance and good
insulation properties.
Select from a lineup of three types with rated
burdnes of 5VA, 15VA, and 40VA.
AF00-102
Notes: * Replace the mark by the secondary current code.
5: 5A 1: 1A
■
Types and ratings
Mounting base
CC3P
Secondary
current
(A)
5 or 1
5 or 1
5 or 1
5 or 1
5 or 1
Rated primary
current
(A)
1
2
3
5
7.5
10
15
20
25
30
40
50
1
2
3
5
7.5
10
15
20
25
30
40
50
1
2
3
5
7.5
10
15
20
30
40
50
Type
CC3P1-001
CC3P1-002
CC3P1-003
CC3P1-005
CC3P1-7P5
CC3P1-010
CC3P1-015
CC3P1-020
CC3P1-025
CC3P1-030
CC3P1-040
CC3P1-050
CC3P2-001
CC3P2-002
CC3P2-003
CC3P2-005
CC3P2-7P5
CC3P2-010
CC3P2-015
CC3P2-020
CC3P2-025
CC3P2-030
CC3P2-040
CC3P2-050
CC3P3-001
CC3P3-002
CC3P3-003
CC3P3-005
CC3P3-7P5
CC3P3-010
CC3P3-015
CC3P3-020
CC3P3-030
CC3P3-040
CC3P3-050
Accuracy
class
1.0
1.0
1.0
1.0
1.0
Thermal limit
current
40 times rated
primary current
40 times rated
primary current
40 times rated
primary current,
1 second
Max. voltage
(kV rms.)
1.15kV
1.15kV
1.15kV
1.15kV
1.15kV
4.0kV
4.0kV
4.0kV
4.0kV
4.0kV
Burden
(VA)
5
15
40
Dielectric
strength
(kV 1 min.)
Mass
(kg)
0.7
1.1
1.1
1.1
1.2
CC3P current transformers with primary winding
Primary current: 5 to 50A
Secondary current: 5A or 1A