13 | Keysight | N8700 Series System DC Power Supplies - Data Sheet
Supplemental Characteristics (continued)
1. The constant current programming readback and monitoring accuracy does not include the warm-up and load regulation thermal drift.
Analog programming and monitoring
Vout voltage programming 0-100%, 0-5 V or 0-10 V, user selectable. Accuracy and linearity: ±0.5% of rated Vout.
Iout voltage programming 10-100%, 0-5 V or 0-10 V, user selectable. Accuracy and linearity: ±1% of rated Iout.
Vout resistor programming 0-100%, 0-5/10 Kohm full scale, user selectable. Accuracy and linearity: ±1% of rated Vout.
Iout resistor programming 10-100%, 0-5/10 Kohm full scale, user selectable. Accuracy and linearity: ±1.5% of rated Iout.
On/Off control (rear panel) Controlled by voltage: 0-0.6 V/2-15 V, or dry contact, user selectable logic.
Output current monitor 10-5 V or 0-10 V, user selectable, Accuracy: ±1%.
Output voltage monitor 0-5 V or 0-10 V, user selectable, Accuracy: ±1%.
Power supply OK signal TTL high (4-5 V) = OK; 0 V = Fail; 500 ohm series resistance.
CV/CC Indicator 3.3 kW: CV = TTL high (4-5 V) (source current: 10 mA); CC = TTL low (0-0.6 V) (sink current = 10 mA)
5 kW: Open collector; CV mode: OFF, CC mode: ON, Max voltage = 30 V; Max sink current = 10 mA
Enable/disable Dry contact. Open: off, Short: on. Max. voltage at terminal = 6 V
Series and parallel capability
Parallel operation Up to 4 identical units (same model number) can be connected in master/slave mode with
single-wire current balancing
Series operation Up to 2 identical units (same model number) can be connected using external protection diodes
(see Output Terminal Isolation on page 13)
Savable states
In volatile memory
16 (in memory locations 0-15)
Interface capabilities
GPIB SCPI - 1993, IEEE 488.2 compliant interface
LXI Compliance Class C (only applies to units with the LXI label on the front panel)
USB 2.0 Requires Keysight I/O Library version M.01.01 and up, or 14.0 and up
10/100 LAN
Requires Keysight I/O Library version L.01.01 and up, or 14.0 and up
Environmental conditions
Environment Indoor use, installation category II (AC input), pollution degree 2
Operating temperature 0°C to 40°C @ 100% load
Storage temperature –20°C to 70°C
Operating humidity 30% to 90% relative humidity (no condensation)
Storage humidity 10% to 95% relative humidity (no condensation)
Altitude Up to 3000 meters.
Above 2000 m, derate the output current by 2%/100 m and derate the maximum ambient temperature
by 1°C/100 m.
Built-in Web server Requires Internet Explorer 5+ or Netscape 6.2+