Extended Product Type:
Product ID:
EAN:
Catalog Description:
Long Description:
Minimum Order Quantity:
Customs Tariff Number:
Data Sheet, Technical Information:
Product Net Width:
Product Net Depth:
Product Net Height:
Product Net Weight:
Number of Main Contacts NO:
Number of Main Contacts NC:
Number of Auxiliary Contacts NO:
Number of Auxiliary Contacts NC:
Rated Operational Voltage:
Rated Frequency (f):
Conventional Free-air Thermal
Current (Ith):
Rated Operational Current AC-1 (Ie):
Rated Operational Current AC-3 (Ie):
Rated Operational Power AC-3 (Pe):
Rated Operational Current AC-15
(Ie):
General Information
AF65-30-11-11
1SBL387001R1111
3471523132719
AF65-30-11-11 24-60V50/60HZ 20-60VDC Contactor
AF65 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They
are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.
AF... contactors include an electronic coil interface accepting a wide control voltage Uc min.
... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V
DC. AF contactors can manage large control voltage variations. One coil can be used for
different control voltages used worldwide without any coil change. AF contactors have built-in
surge protection and do not require additional surge suppressors. The AF... series 2-stack
3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3
main poles with side-mounted 1 N.O. + 1 N.C. auxiliary contact block, front-mounted add-on
auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of
IEC 60947-5-1 including the "Mechanically Linked" symbol on the contactor side.
N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC
operated - Accessories: a wide range of accessories is available. Note: 2-stack contactors
available in some countries: please consult your ABB representative. AF..-30-..-11 not
suitable for a direct control by PLC-output.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
1 piece
85364900
Popular Downloads
1SBC100173C0201
Dimensions
67 mm
111 mm
125.5 mm
1.010 kg
Technical
3
0
1
1
Auxiliary Circuit 690 V
Main Circuit 690 V
Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
(690 V) 40 °C 105 A
(690 V) 60 °C 90 A
(690 V) 70 °C 80 A
(220 / 230 / 240 V) 60 °C 65 A
(380 / 400 V) 60 °C 65 A
(415 V) 60 °C 65 A
(440 V) 60 °C 65 A
(500 V) 60 °C 55 A
(690 V) 60 °C 39 A
(220 / 230 / 240 V) 18.5 kW
(380 / 400 V) 30 kW
(400 V) 30 kW
(415 V) 37 kW
(440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
(220 / 240 V) 4 A
(24 / 127 V) 6 A
(400 / 440 V) 3 A
(500 V) 2 A
AF65-30-11-11
Rated Short-time Withstand Current
(Icw):
Maximum Breaking Capacity:
Maximum Electrical Switching
Frequency:
Rated Operational Current DC-13
(Ie):
Rated Insulation Voltage (Ui):
Rated Impulse Withstand Voltage
(Uimp):
Maximum Mechanical Switching
Frequency:
Rated Control Circuit Voltage (Uc):
Operate Time:
Connecting Capacity Main Circuit:
Connecting Capacity Auxiliary
Circuit:
Connecting Capacity Control Circuit:
Wire Stripping Length:
Degree of Protection:
Terminal Type:
Ambient Air Temperature:
Climatic Withstand:
Maximum Operating Altitude
Permissible:
Resistance to Vibrations acc. to IEC
60068-2-6:
Resistance to Shock acc. to IEC
60068-2-27:
Horsepower Rating UL/CSA:
(690 V) 2 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
AC-1 600 cycles per hour
AC-15 1200 cycles per hour
AC-2 / AC-4 150 cycles per hour
AC-3 1200 cycles per hour
DC-13 900 cycles per hour
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(48 V) 2.8 A / 134 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
(72 V) 1 A / 72 W
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
6 kV
3600 cycles per hour
50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Flexible with Insulated Ferrule 1/2x 4...35 mm²
Flexible with Ferrule 1/2x 4...35 mm²
Rigid 1/2x 6...35 mm²
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1...2.5 mm²
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Main Circuit 16 mm
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Screw Terminals
Environmental
Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Category B according to IEC 60947-1 Annex Q
3000 m
5 ... 300 Hz 3 g closed position / 3 g open position
Closed, Shock Direction: A 25 g
Closed, Shock Direction: B1 25 g
Closed, Shock Direction: B2 15 g
Closed, Shock Direction: C1 25 g
Closed, Shock Direction: C2 25 g
Open, Shock Direction: B1 5 g
Technical UL/CSA
(120 V AC) Single Phase 5 Hp
(240 V AC) Single Phase 15 Hp
(200 ... 208 V AC) Three Phase 20 Hp
Tightening Torque UL/CSA:
ABS Certificate:
BV Certificate:
CB Certificate:
CCC Certificate:
Declaration of Conformity - CE:
DNV GL Certificate:
EAC Certificate:
Environmental Information:
Instructions and Manuals:
KC Certificate:
LR Certificate:
RINA Certificate:
RMRS Certificate:
RoHS Information:
UL Certificate:
UL Listing Card:
Package Level 1 Units:
Package Level 1 Width:
Package Level 1 Length:
Package Level 1 Height:
Package Level 1 Gross Weight:
Package Level 1 EAN:
Package Level 2 Units:
Package Level 2 Width:
Package Level 2 Length:
Package Level 2 Height:
Package Level 3 Units:
Object Classification Code:
ETIM 4:
ETIM 5:
ETIM 6:
UNSPSC:
(220 ... 240 V AC) Three Phase 25 Hp
(440 ... 480 V AC) Three Phase 50 Hp
(550 ... 600 V AC) Three Phase 60 Hp
Auxiliary Circuit 11 in·lb
Control Circuit 11 in·lb
Main Circuit 35 in·lb
Certificates and Declarations (Document Number)
ABS_15-GE1349500-PDA_90682247
BV_2634H36994A
CB_SE_77418
CCC_2012010304589737
CCC_2015010304824714
1SBD250000U1000
DNV-GL_E13871
EAC_RU C-FR ME77 B01010
1SBD250168E1000
1SBC101036M6801
KC_HW02016-15003A
LRS_1300087E1
RINA_ELE084013XG
RMRS_1400682124
1SBD251021E1000
UL_20130926-E312527_14_1
UL_E312527
Container Information
1 piece
150 mm
150 mm
97 mm
1.11 kg
3471523132719
10 piece
250 mm
300 mm
300 mm
240 piece
Classifications
Q
EC000066 - Magnet contactor, AC-switching
EC000066 - Magnet contactor, AC-switching
EC000066 - Power contactor, AC switching
39121529