CSM_H3Y_DS_E_6_1
1
Solid-state Timer
H3Y
Miniature Timer Compatible with the MY
Relay
Semi-multi power supply voltage.
Large transparent time setting knob facilitates time setting.
A flat-blade and Phillips screwdriver can also be used for
time setting.
Pin configuration compatible with MY Power Relay.
LED indication for power and output statuses.
Conforms to EMC standards.
Conforms to EN61812-1 and approved b y UL and CSA.
LR
For the most recent informati on on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
Note: 1. Specify both the model number, supply voltage, and rated time when ordering.
2. Sockets and Hold-down Clips are not included with the H3Y. They must be ordered separately.
3. Use the H3Y-4 or H3Y-4-0 Series when switching micro loads.
Accessories (Order Separately)
Adapter, Mounting Plate, Clip
Note: For details, refer to Safety Precautions.
Socket
Note: 1. Cannot be used with the H3Y-@-0 (PCB terminals).
2.
The PYF
@@
A-E has a finger-protection structure. Round crimp
terminals cannot be used. Use forked crimp terminals.
3. For details, refer to Socket and DIN Track Products.
Operation/
resetting system Time-limit contact Time ranges Supply voltage Mounting
Surface/DIN-track
mounting
(with socket)
Surface mounting
(with PCB terminals)
Time-limit operation/
self-resetting DPDT (for power
switching) 0.04 s to 3 h 24, 100 to 120, 200 to 230 VAC
(50/60 Hz);
12, 24, 48, 125, 100 to
110 VDC
H3Y-2 H3Y-2-0
4PDT H3Y-4 (See note 3.) H3Y-4-0 (See note 3.)
Ex. H3Y-2 100 to 120 VAC 0.5 s
Rated time
Supply voltage
Name/specification Model
Flush mounting adapter Y92F-78
Mounting
Plate for
Socket
For 1 Socket PYP-1
For 18
Sockets PYP-18
Clip For PYF@A Y92H-3
For PY@ and
PYF@MY92H-4
Timer Square Sockets
Contact Model Pin
Connection
Terminal Model
DPDT H3Y-2
H3YN-2@8-pin
Front
Connecting
DIN track
mounting PYF08A
DIN track
mounting
(Finger-
safe tyape)
PYF08A-E
Screw
mounting PYF08F
Back
Connecting Solder
terminal PY08
4PDT H3Y-4
H3YN-4@14-pin
Front
Connecting
DIN track
mounting PYF14A
DIN track
mounting
(Finger-
safe tyape)
PYF14A-E
Back
Connecting Solder
terminal PY14
H3Y
2
Specifications
Time Ranges
Ratings
Note: 1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Times for details.
2. With DC ratings, single-phase full-wave rectified power sources may be used.
3. Only the H3Y-2 and H3Y-2-0 Series include 2-VDC models.
4. Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously under an ambient
operating temperature of 50°C.
5. Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC:10 VAC max.
200 to 230 VAC:20 VAC max.
100 to 110 VDC:10 VDC max.
6. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
7. A diode to prevent reverse voltages is provided only on models with a DC power supply.
Rated time Time setting range Rated time Time setting range
0.5 s 0.04 to 0.5 s 3 min 0.1 to 3 min
1 s 0.1 to 1 s 5 min 0.2 to 5 min
5 s 0.2 to 5 s 10 min 0.5 to 10 min
10 s 0.5 to 10 s 30 min 1 to 30 min
30 s 1.0 to 30 s 60 min 2 to 60 min
60 s 2.0 to 60 s 3 h 0.1 to 3 h
120 s 5.0 to 120 s --- ---
Item H3Y-2(-0)/H3Y-4(-0)
Rated supply voltage (See note 6, 7.) 24, 100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz) (See note 1.), 12, 24, 48, 125, 100 to 110 VDC
(See notes 2 and 3.)
Operating voltage range All rated voltages except 12 VDC: 85% to 110% of rated supply voltage
12 VDC: 90% to 110% of rated supply voltage (See note 4.)
Reset voltage 10% min. of rated supply voltage (See note 5.)
Power consumption 100 to 120 VAC: Relay ON: Approx. 1.8 VA (1.6 W) at 120 VAC, 60 Hz
Relay OFF: Approx. 1 VA (0.6 W) at 120 VAC, 60 Hz
200 to 230 VAC: Relay ON: Approx. 2.2 VA (1.8 W) at 230 VAC, 60 Hz
Relay OFF: Approx. 1.5 VA (1.1 W) at 230 VAC, 60 Hz
24 VAC: Relay ON: Approx. 1.8 VA (1.4 W) at 24 VAC, 60 Hz
Relay OFF: Approx. 0.3 VA (0.2 W) at 24 VAC, 60 Hz
12 VDC: Relay ON: Approx. 1.1 W at 12 VDC
Relay OFF: Approx. 0.1 W at 12 VDC
24 VDC: Relay ON: Approx. 1.1 W at 24 VDC
Relay OFF: Approx. 0.1 W at 24 VDC
48 VDC: Relay ON: Approx. 1.2 W at 48 VDC
Relay OFF: Approx. 0.3 W at 48 VDC
100 to 110 VDC: Relay ON: Approx. 1.6 W at 110 VDC
Relay OFF: Approx. 0.4 W at 110 VDC
125 VDC: Relay ON: Approx. 1.6 W at 125 VDC
Relay OFF: Approx. 0.4 W at 125 VDC
Control outputs H3Y-2(-0):
5 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials : Ag
H3Y-4(-0):
3 A at 250 VAC, resistive load (cosφ = 1)
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Contact materials : Au-clad + Ag-alloy
H3Y
3
Characteristics
Note: 1. Add ±10 mS to the above value for the 0.5-S range model.
2. Terminal screw sections are excluded.
Accuracy of operating time ±1% FS max. (0.5 s range: ±1%±10 ms max.)
Setting error (see note 1) ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Reset voltage 10% max. of rated supply voltage
Influence of voltage (see note 1) ±2% FS max.
Influence of temperature (see note 1) ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts) (see note 2)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output) (see note 2)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) (see note 2)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Shock resistance Destruction: 1,000 m/s2 (approx. 100G)
Malfunction: 100 m/s2 (approx. 10G)
Ambient temperature Operating: –10°C to 50°C (with no icing)
Storage: –25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y-2: 500,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)
H3Y-4: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h)
Impulse withstand voltage Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Enclosure rating IP40
Weight Approx. 50 g
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Approved standards UL508, CSA C22.2 No. 14, Lloyds
Conforms to EN61812-1 and IEC60664-1. (2.5 kV/2 for H3Y-2/-2-0, 2.5 kV/1 for H3Y-4/-4-0)
Output category according to EN60947-5-1.
H3Y
4
Engineering Data
Operation
Timing Chart
H3Y-2, H3Y-2-0
Switching operations (×10
3
)
Load current (A)
H3Y-2, H3Y-2-0
H3Y-4, H3Y-4-0
Load current (A)
Load current (A)
H3Y-4, H3Y-4-0
Load current (A)
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 5 VDC (P reference value).
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both
cases, a life of 100,000 operations can be expected.The minimum
applicable load is 1 mA at 1 VDC (P reference value).
Switching operations (×10
3
)
Switching operations (×10
3
)
Switching operations (×10
3
)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 1
24 VDC, cosφ = 1 250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
H3Y-2, H3Y-2-0 H3Y-4, H3Y-4-0
NCNC
H3Y
5
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Timers
H3Y-2 H3Y-4
(63.0) 6.4
6.3
(63.0) 6.4
6.3
28 max.
21.5
max. 21.5
max.
28 max.
Mounting Holes
H3Y-2-0 H3Y-4-0
Mounting Holes
(60.7)
28 max.
(60.7)
28 max.
6.3
21.5
max.
6.3
21.5
max.
Eight,
1.3-dia. holes
Pin 1
Fourteen,
1.3-dia. holes
Pin 1
H3Y
6
Accessories (Order Separately)
Use the PYF@A, PY@, PY@-02, or PY@QN(2) to mount the H3Y. When ordering any one of these sockets, replace “@” with “08” or “14.
Terminal Arrangement
(Top View)
Track Mounting/Front Connecting Sockets
PYF08A
6
72 max.
23 max.
30 max.
16.5
35.4
3.4
4
6PYF@A
90.5 86.6
Two, 4.5 dia.
M4 or M3
59±0.3
15±0.2
Mounting Holes
Terminal Arrangement
(Top View)
PYF14A
Mounting Holes
6
72 max.
29.5 max.
30 max.
16.5
35.4
3.4
4
6
Two, 4.5 dia.
M4 or M3
59±0.3
22±0.2
PYF08A-N Terminal Arrangement Mounting Holes
(for Surface Mounting)
4
42 1
85
12 9
14 14 13
44
12
14
41 11
A2 A2 A1
19.8
3.2 dia.
3.6 dia.
4
42
8
44
1
12
5
14
41
12
A2
14
11
9
A1
13
A2
14
22 max.
66.5 max.
PYF-08A-N
30 max.
4 3 2 1
87 6 5
12 11 10 9
14 14 13
42 32 22 12
44 34 24 14
41 31 21 11
A2 A2 A1
20.8
Two, 3.5 dia.
30 max.
4
42
3
32
2
22
1
12
8
44
7
34
6
24
5
14
41
12
31
11
21
10
11
9
A1
13
A2
14
A2
14
66.5 max.
PYF-14A-N
29.5 max.
PYF14A-N Terminal Arrangement Mounting Holes
(for Surface Mounting)
Two, 4.2 × 5
mounting holes Eight, M3 × 8
sems
Two, 4.2 × 5
mounting holes Fourteen, M3 × 8
sems
H3Y
Series
H3Y
7
PYF08A-E
31 max.
72 max.
23 max.
(Top View)
PYF14A-E
31 max.
29.5 max.
(Top View)
Two, 4.5 dia.
M4 or M3
Two, 4.5 dia.
M4 or M3
Two, 4.2 × 5
mounting holes Eight, M3 × 8
sems
Two, 4.2 × 5
mounting holes Eight, M3 × 8
sems
72 max.
Panel Cutout
Back Connecting Sockets
PY08, PY14
Terminal Arrangement
(Bottom View)
PY08QN, PY14QN
PY08QN(2), PY14QN(2)
PY08-02, PY14-02
29.5
max.
25.5
max.
24 max.
0.3
2.7 7.7
20 max.
2.6
29.5
max.
25.5
max.
22 max.
0.3
2.7 4.3
16.5 max.
2
(See
note)
2.7
29.5 max.
41.5 max.
(see note)
25 max. * 24 max.
22 max.
** 1 × 1
H3Y
Series
PY@, PY@-02,
PY@QN(2)
59.3
21.4+0.2
0
25.8+0.2
0
PY08-02 PY14-02
Terminal Arrangement
(Bottom View)
Terminal Arrangement
(Bottom View)
PY08QN
PY08QN(2) PY14QN
PY14QN(2)
PY08PY14
Eight, 3 × 1.2 dia. holes
only for PY08 (Fourteen,
3 × 1.2 dia. holes)
Note: With PY@QN(2), dimension * should read
20 max. and dimension ** 36.5 max.
H3Y
8
Socket Mounting Plates (t = 1.6)
Note: PYP-18 may be cut to any desired length.
Applicable socket For mounting 1 socket For mounting 18 sockets
PY08, PY14, PY08QN(2), PY14QN(2) PYP-1 PYP-18
PYP-1
Two, 3.4-dia. holes
PYP-18
53
4.5
4.5 1.2
9R
33.7
2.5
20 (84°)
30.5
24.5
5 max.
Y92H-3
Y92H-4
Relay Hold-down Clips
Y92H-3 for
PYF@A Socket
(Set of Two Clips)
Y92H-4 for
PY@ Socket
Mounting Track
PFP-100N/PFP-50N (see note 1) End Plate
PFP-M
1000 (500) (See note 2)
Note: 1. Meets DIN EN50022
2. This dimension applies to PFP-50N.
Spacer
PFP-S
H3Y
9
Installation
Connection
H
3
Y
-2,
H
3
Y
-2-0
H
3
Y
-4,
H
3
Y
-4-0
Connect the DC power supply to
terminals 13 and 14 according
to the polarity marks.
Connect the DC power supply to
terminals 13 and 14 according to
the polarity marks.
(Bottom View) (Bottom View)
H3Y
10
Safety Precautions
Refer to Safety Precautions for All Timers.
Warning Indications
Meaning of Product Safety Symbols
Risk of fire and explosion due to arcing and rela y heat
generation that accompanies s witching. Do not use in an
environment where flammabl e or explosiv e gas is present.
The service life of the output relay varies widely
depending on switching capacity and switching
conditions. Use only within the rated load and
electrical life count, based on actual conditions of use.
Risk of contact sticking and burning if used past the
service life. Always use a load current that does not
ex ceed the rating, and if a heater is used, use a thermal switch in the
load circuit.
Do not remove the outer casing.
In rare circumstances there is a risk of slight electrical
shock, fire, or device damage. Do not disassemble,
modify, repair, or otherwise touch the inside.
Tighten the screws for the lead wires to the Socket to
the following torque.
PYF Socket: 0.78 to 1.18 N·m
This is the recommended range when crimp terminals
are used.
If the screws are not tightened sufficiently on Front-
connecting Sockets, the lead wires may come off, connection failure
may cause abnormal heating, or fires may occur.
If they are tightened excessively, the screw threads may be
damaged.
Confirm that the setting dial, indicators and plastic parts are
operating normally. Depending on the operating environment, the
setting dial, indicators and plastic parts may deteriorate faster than
expected, causing the indicators to fail. Periodically perform
inspections and replacements.
We recommend that y ou use a surge absorber if surge v oltages may occur.
When you dispose of the Timer, do so according to all local
ordinances for processing industrial waste.
When selecting a control output, use the H3Y-2 for switching ON and
OFF the power and the H3Y-4 for switching ON and OFF the minute
load.
The operating voltage will increase when using the H3Y in any place
where the ambient temperature is more than 50°C. Supply 90% to
110% of the rated voltages (at 12 VDC: 95% to 110%) when
operating at 45°C or higher.
Do not leave the H3Y in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts (aluminum
electrolytic capacitor) may become damaged. Therefore, the use of
the H3Y with a relay as shown in the following circuit diagram is
recommended to extend the service life of the H3Y.
Do not connect the H3Y as shown in the following circuit diagram on
the right hand side, otherwise the H3Y’s internal contacts different
from each other in polarity may become short-circuited.
Use the following safety circuit when building a self-holding or self-
resetting circuit with the H3Y and an auxiliary relay, such as an MY
Relay, in combination.
Do not use the H3Y in places where there is excessive dust,
corrosive gas, or direct sunlight.
Do not mount more than one H3Y closely together, otherwise the
internal parts may become damaged. Make sure that there is a
space of 5 mm or more between an y H3Y Models next to each other
to allow heat radiation.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3Y. When more than 100 V is
applied to 12- or 24-VDC models, the internal element (varistor) may
break.
Always use the same type of wire.
Installation
There are no restrictions on the installation orientation. Install the
Timer securely.
CAUTION Indicates a potentially hazardous situation
which, if not avoided, may result in minor
or moderate injury or in property damage.
Precautions for
Safe Use Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, malfunction or undesirable effect
on product performance.
Used for general prohibitions for which there is no
specific symbol.
Use to indicate prohibitions when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Used for general mandatory action precautions for
which there is no specified symbol.
CAUTION
Precautions for Safe Use
Precautions for Correct Use
L
2
L
1
L
2
L
1
Correct Incorrect
: H3Y
Auxiliary relay:
MY Relay
H3Y
11
Precautions for EN61812-1
Conformance
The H3Y as a built-in timer conforms to EN61812-1 provided that the
following conditions are satisfied.
Handling
Before dismounting the H3Y from the socket, make sure that no
voltage is imposed on any terminal of the H3Y.
Wiring
The power supply for the H3Y must be protected with equipment
such as a breaker approved by VDE.
Basic insulation is ensured between the H3Y’s operating circuit and
control output.
Insulation requirement: Overvoltage category II,
pollution degree 1 (H3Y-4/-4-0),
pollution degree 2 (H3Y-2/-2-0)
(with a clearance of 1.5 mm and a
creepage distance of 2.5 mm at 240 VAC)
Output terminals next to each other on the H3Y-4 or H3Y-4-0 must
have the same polarity.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omrons sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyers application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omrons test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omrons Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2014.6
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.