Descriptions
Catalog Number
SCP 100S24X-CP1 SCP 102D24X-C02
SCP 100S24X-DVN1 SCP 102D24X-D02
Input
Nominal Voltage Any voltage from 100 to 240 Vac Input
-AC Range 85 - 264 Vac Universal Input
-DC Range 100 - 353 Vdc
Nominal Current 1 1.6A / 0.7A 2.4 - 1.4A / 2.4 - 0.7A
-Inrush current max. Typ. <30A
Power Factor Correction 2 0.95
Frequency 50/60/400 Hz
Output
Power Back Immunity 35 V
Overvoltage Protection 25-25.5 Vdc, autorecovery
Nominal Voltage 24 Vdc
Tolerance < +/-2% overall
- Line Regulation < 0.5%
- Load Regulation < 0.5%
- Time & Temp. Drift < 1%
Input Voltage Setting 24.5 V +/-1%
Ripple 3< 50 mVpp
Total Nominal Current 3.8A 7.6A Total (3.8A max. per pair)
Holdup Time > 50 ms (Full load, 100 Vac Input @ Tamb=+25oC) to 95% output voltage
General
Emissions 4EN61000-6-3, EN61000-6-4, EN55011 Group 1, Class B, EN55022 Class B, EN61000-3-2, EN61000-3-3
Immunity 4EN61000-6-1, EN61000-6-2, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4,
IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, SEMI F47 Sag Immunity
Temperature
Storage: -40° to +85°C, Operation: -40° to +60°C full power with linear
derating to half power from +60° to +70°C.
No forced air required. Operation up to 100% load permissible
with sideways or front side up mounting orientation.
Storage: -40° to +85°C, Operation: -25° to +60°C full power with linear
derating to half power from +60° to +70°C.
No forced air required. Operation up to 100% load permissible
with sideways or front side up mounting orientation.
Humidity Up to 100% RH with condensation
Altitude 0 to 3,000 m (0 to 10,000 ft.)
Vibration 1 g non-operating swept sine over 10–500 Hz (IEC 60068-2-6). Non-operating random vibration test: 1.87 g over 10–500 Hz (IEC 60068-2-64). Oper-
ating random vibration test: 0.15 g over 5–100 Hz (IEC 60068-2-64)
Shock Non-operating: 30 g peak, 18 ms half-sine pulse (IEC 68-2-27). Operating: 4 g peak, 22 ms half-sine pulse (IEC 68-2-27)
Warranty 5 Year Limited Warranty
MTBF >800,000 hours according to Telcoredia/Bellcore SR-332 Issue 1,
(Vin 120 V ac, Tamb = 40°C)
>800,000 hr. according to Telcoredia/Bellcore SR-332 Issue 3,
(Vin 120 V ac, ambient temp. = 40°C)
General Protection/Safety
Protected against continuous short-circuit, continuous overload,
and continuous open circuit. Protection NEC Class 2 (IEC536),
degree of protection IP66/IP67 versatile (IEC60529).
Safety extra low voltage circuits: SELV (acc. EN60950-1).
Protected against continuous short-circuit, continuous overload, continu-
ous open circuit. Protection Class 1.
Safety extra low voltage circuits: SELV (acc. EN60950).
Status Indicators - Visual DC OK LED
Installation
Fusing
- Input Internally fused, fuses not replaceable
- Output Electronically current limited to meet NEC Class 2 per UL1310
Mounting Chassis mounted using integral mounting tabs. Recommended Screw Size: M4 x 0.7. Tightening Torque: 1N-m
Connections
An accessible disconnect device shall be installed external to the equipment.
Input: 3-PIN IP67 molded plug (quick disconnect).
Output: 4-PIN IP67 molded receptacle (quick disconnect).
Use UL 758 wire rated min. 24 V, VW-1/FT-1, max. 3.05 m.
Case IP66/67 versatile ingress protection; also meets UL50 Type 4X enclosure
Min. Required Free Space 0.39 in. (10 mm) all sides but base 1 in. (25 mm) all sides but base
H x W x D inches (mm) 4.73 x 7.00 x 1.80 (120.1 x 177.8 x 45.7) 4.73 x 7.00 x 3.27 (120.1 x 177.8 x 83.0)
Weight - lbs (kg) 2.2 (1.0) 3.3 (1.5)
1. Input current ratings are specified with low input, line conditions, worst case efficiency values and power factor.
2. Power Factor Correction at 50/60 Hz only.
3. Ripple/noise is stated as typical AC values when measured with a 20 MHZ bandwidth scope and 50 Ohm termination.
4. Emissions and immunity are met by individual power supply modules.