Specifications:
Box lug and spade terminal suitable for line, load or
accessory connection
Box Lug Connection:
- 18-6 AWG (1 to 16mm2) single or dual rated, solid or
stranded – 75°C or higher - Cu only
- 4 AWG (25mm2) single – 75°C or higher - Cu only
Spade Terminal Connection:
- Max. 30A with insulated flanged spade terminal wire size
#12 - #10 AWG for stud size #8
Torque:
- 18-10 AWG 20 Lb-In (1-6mm2/3.4N•m)
- 8-4 AWG 35 Lb-In (10-25mm2/5.8N•m)
Lockout/tagout: 4mm shank lock or standard pin-out devices
35mm DIN-Rail mount
Dimensionally compliant to DIN 43880
Local indication minimum operating voltage:
– 90Vac for AC version
– 12Vdc for DC version
Agency Information:
UL Class CC fuse version
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
• CE Compliant
UL Midget fuse version
• UL 508 Listed
• cULus Certified 22.2 No. 14-05
• CE Compliant
10X38 IEC Class aM and gG/gL fuse version
• IEC 60947-3 AC23A
• IEC 60947-3 DC23A
• CE Compliant
Shipping Weight:
• 2.84 lbs (1.29kg) per carton
Carton Quantity:
• 12 Poles
Environmental Data
• Storage and operating temperature: -20°C to 75°C**
• Flammability rating: UL 94V0
** For fuse performance under or above 25°C, consult fuse
performance derating charts in the Cooper Bussmann
publication titled Selecting Protective Devices (SPD) reorder #3002.
The revolutionary Cooper Bussmann CCP is 1/3 the
footprint of a molded case circuit breaker. The level of
protection provided by the CCP is up to three times the
Short-Circuit Current Rating (SCCR) at full voltage than a
molded case circuit breaker while providing a disconnecting
means.
Product Features and Benefits
Extremely compact design at 17.5mm wide per pole
High Short-Circuit Current Ratings up to 200kA (UL) and
120kA (IEC)
Disconnect rated to provide means for load isolation
Full voltage rated up to 600Vac or 80Vdc
Class CC version is UL 98 Listed and horsepower rated,
and suitable for branch circuit disconnect and branch circuit
protection
IEC 10x38 version complies with IEC 60947-3 and
suitable for branch circuit disconnect and branch circuit
protection
Suitable for global installations, the units comply with UL,
cULus, and IEC standards accepting UL Class CC, Midget
or IEC aM and gG/gL fuses
Open Fuse Indication
- Local fuse indication lights* are standard.
- Optional wired remote open fuse indication can be
utilized to signal a PLC and open a contactor to
de-energize all phases, if required.
IP20 finger-safe with 10AWG (6mm2) or larger wire
Built-in switch interlock capability prohibits removing the
fuse under load
Padlockable handle for lockout/tagout procedures
Available in 1-, 2- and 3-pole versions
Spade terminals, rated up to 30A, installed on the line side
of the disconnect, make it easy to add NEC®240.21
compliant taps for loads up to 80% of the spade terminal
amp rating for devices that need to remain energized when
the disconnect is in the OFF position
*Circuit must be closed with 90Vac/115Vdc minimum for indication light to
illuminate
Compact Circuit Protector (CCP)
UL Class CC, Midget and IEC 10x38 fuses
1212 BU-SB101428 Form No.CCP Page 2 of 12 Data Sheet 1157
Disconnect Switch
Lockout
Provision
Open Fuse
Indication
Light
Fuse
Holder Compartment
Knob
Spade
Connection
Circuit
Marking Area
Box
Lug
Connection
Technical Ratings
Catalog Amp Voltage Fuse Agency
Number Poles Rating Rating Type Max. Fuse Ampacity SCCR Approvals Hp ratings
CCP-1-30CC 1 30 600Vac Class CC 30A 200kA UL 98 Listed 0.5Hp@120V
cULus 22.2 No. 4-04
CCP-2-30CC 2 30 600Vac Class CC 30A 200kA UL 98 Listed 2.0Hp@240V
cULus 22.2 No. 4-04
UL98 Listed 3Hp@240V
CCP-3-30CC 3 30 600Vac Class CC 30A 200kA cULus  22.2 No. 4-04 5Hp@480V
7.5Hp@600V
240Vac* UL UL Midget 30A UL 508 Listed
CCP-1-30M 1 30 10kA* cULus 22.2 No. 14-05
400Vac* IEC
10x38 IEC 32A aM, 25A gG 120kA* IEC 60947-3 AC23A
240Vac* UL UL Midget 30A UL 508 Listed
CCP-2-30M 2 30 10kA* cULus 22.2 No. 14-05
400Vac* IEC
10x38 IEC 32A aM, 25A gG 120kA* IEC 60947-3 AC23A
240Vac* UL UL Midget 30A UL 508 Listed
CCP-3-30M 3 30 10kA* cULus 22.2 No. 14-05
400Vac* IEC
10x38 IEC 32A aM, 25A gG 120kA* IEC 60947-3 AC23A
CCP-1-DCC 1 30 80Vdc* Class CC 30A 20kA* UL 98 Listed
(DC rated) CSA 22.2 No. 4-04
UL Midget 30A UL 508 Listed
CCP-1-DCM 1 30 80Vdc* 10kA* cULus 22.2 No. 14-05
10x38 IEC 32A aM, 25A gG IEC 60947-3 DC23A
*Rating may be lower depending on installed fuse. Refer to fuse data sheet.
AC Voltage DC Voltage
Class CC Midget Class CC Midget
LP-CC KTK LP-CC KLM
KTK-R FNM
FNQ-R FNQ
BAF
Recommended UL Fuse Types Recommended IEC Fuse Types
10x38 IEC
Part Number IEC
Family Class
C10G gG/gL
C10M aM
1212 BU-SB101428 Form No.CCP Page 3 of 12 Data Sheet 1157
Motor Sizing Chart
Compact Circuit Protector (CCP)
UL Class CC, Midget and IEC 10x38 fuses
Note: NEMA motors only (no IEC or Design B Energy Efficient). Minimum size if no more than 1
start/hour. Code max if low to moderate reverse/jog/plug applications. Heavy start permitted only if
Code Max does not allow motor start-up. For high reverse/jog/plug applications or larger
horsepower motors, Class J fuses are recommended. See CCP with CUBEFuse.
Compact Circuit Protector (CCP)
CUBEFuse
1212 BU-SB101428 Form No.CCP Page 4 of 12 Data Sheet 1157
Specifications:
• Box Lug and Spade Terminal suitable for line, load or
accessory connection
Box Lug Connection:
30-60A:
-18-6 AWG (1 to 16mm2) single or dual rated, solid or
stranded – 75°C or higher - Cu only
- 4 AWG (25mm2) single – 75°C or higher - Cu only
100A:
- 18-1AWG (1-45mm2) single or dual rated, solid or
stranded 75ºC or higher - Cu only
- 6AWG (16mm2) single – 75ºC or higher - Cu only
• Spade Terminal Connection:
Max. 30A with insulated flanged spade terminal wire size
#12 - #10 AWG for stud size #8
• Torque:
30-60A:
- 18-10 AWG 20 Lb-In (1-6mm2/3.4N•m)
- 8-4 AWG 35 Lb-In (10-25mm2/5.8N•m)
100A:
- 18-10AWG 25 Lb-In (1-6mm2/2.82N•m
- 8-1AWG 40 LB-In (10-45mm2/4.52N•m)
- 6AWG 45Lb-In (16mm2/5.08N•m)
• Lockout/tagout: 4mm shank lock
• 35mm DIN-Rrail mount
• Local indication minimum operating voltage:
- 90Vac/115Vdc
Agency Information:
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
• CE Compliant
Shipping Weight:
• 2.03 lbs (0.92kg) per carton
Carton Quantity:
• 6 Poles
Environmental Data:
• Storage and operating temperature: -20°C to 75°C***
• Flammability rating: UL 94V0
The revolutionary Cooper Bussmann CCP is 1/3 the
footprint of a circuit breaker. The level of protection
provided by the CCP is up to three times the Short-Circuit
Current Rating (SCCR) at full voltage than a molded case
circuit breaker while providing disconnecting means.
Product Features and Benefits
Uses Class CF finger-safe time-delay or fast-acting
CUBEFuse with Class J electrical performance*.
Extremely compact design at 25.4mm (1 inch) wide per pole
High Short-Circuit Current Ratings at 200kA
Disconnect rated to provide means for load isolation
Full voltage rated at 600Vac for 30A, 60A and 100A versions
Consult factory for DC ratings
UL 98 Listed and suitable for branch circuit disconnect and
branch circuit protection
1-, 2- and 3-pole versions are horsepower rated
Complies with UL and CSA
Open Fuse Indication:
- Local fuse indication lights** are standard
- Optional wired remote open fuse indication can be utilized
to signal a PLC and open a contactor to de-energize all
phases, if required
Additional open fuse indication can be provided by the
time-delay CUBEFuse
IP20 finger-safe construction with 10 AWG (6mm2) wire or
larger
Built-in switch interlock capability prohibits removing the fuse
under load
Padlockable handle for lockout/tagout procedures
Spade terminals, rated up to 30A, installed on the line side
of the disconnect, make it easy to add NEC®240.21
compliant taps for loads up to 80% of the spade terminal
amp rating for devices that need to remain energized when
the disconnect is in the OFF position
*See data sheet 9000 for CUBEFuse specifications
**Circuit must be closed with minimum 90Vac/115Vdc for indication light to
illuminate
***For fuse performance under or above 25°C, consult fuse performance derating
charts in the Cooper Bussmann publication “Selecting Protective Devices”
(SPD) reorder #3002.
Compact Circuit Protector (CCP)
CUBEFuse
1212 BU-SB101428 Form No.CCP Page 5 of 12 Data Sheet 1157
CCP Part Poles Voltage Time-Delay Time-Delay Fast-Acting Max. Fuse** SCCR Hp Ratings***
Numbers Rating Non-Indicating Indicating* Non-Indicating Ampacity
CCP-1-30CF 1 1.5Hp@120V
CCP-2-30CF 2 3Hp@240V
600Vac TCF1RN TCF30RN TCF6 – TCF30 FCF1RN – FCF30RN 30A 200kA 5Hp@240V
CCP-3-30CF 3 15Hp@480V
10Hp@600V
CCP-1-60CF 1 3.0Hp@120V
CCP-2-60CF 2 7.5Hp@240V
600Vac TCF35RN TCF60RN TCF35 – TCF60 FCF35RN – FCF60RN 60A 200kA 7.5Hp@240V
CCP-3-60CF 3 20Hp@480V
15Hp@600V
CCP-1-100CF 1 5.0Hp@120V
CCP-2-100CF 2 10Hp@240V
600Vac TCF70RN – TCF100RN TCF70 TCF100 FCF70RN – FCF100RN 100A 200kA 20Hp@240V
CCP-3-100CF 3 50Hp@480V
40Hp@600V
CUBEFuse™
(Class J performance)
Technical Ratings
*1A and 3A indicating CUBEFuse not available. Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.
**Any fuse with an amp rating less than or equal to the max fuse rating may be used.Example: TCF15 maybe used with CCPB-1-20CF.
***Do not use UPS/Critical Application fast-acting CF with motors.
Circuit
Marking
Area
Lockout
Provision
Disconnect Switch
Spade
Connection
Box Lug
Connection
Fuse Holder
Compact Circuit Protector (CCP)
CUBEFuse
1212 BU-SB101428 Form No.CCP Page 6 of 12 Data Sheet 1157
CUBEFuse Motor Sizing Table
Low-Peak CUBEFuse
Time-Delay (Amp Rating)
Motor Motor* Optimal Code Heavy
Voltage Size (Hp) FLA (Amps) Protection Max Start
0.167 4.4 10 10 10
0.25 5.8 10 15 15
0.333 7.2 15 15 15
0.5 9.8 15 20 20
115Vac, 0.75 13.8 25 25 30
1-Phase 1 16 25 30 35
1.5 20 30 35 45
2 24 40 45 50
3 34 50 60 N/A
5** 56 90 100 N/A
0.167 2.2 666
0.25 2.9 666
0.333 3.6 6 10 10
0.5 4.9 10 10 10
230Vac, 0.75 6.9 15 15 15
1-Phase 1815 15 17.5
1.5 10 15 20 20
2 12 20 25 25
3 17 25 30 35
5 28 45 50 60
7.5 40 60 N/A N/A
10** 50 80 90 N/A
0.5 2.5 666
0.75 3.7 6 10 10
1 4.8 10 10 10
200Vac, 1.5 6.9 15 15 15
3-Phase 2 7.8 15 15 17.5
3 11 17.5 20 20
5 17.5 30 35 35
7.5 25.3 40 45 50
20** 62.1 100 N/A N/A
0.5 2.4 666
0.75 3.5 6 10 10
1 4.6 10 10 10
208Vac, 1.5 6.6 10 15 15
3-Phase 2 7.5 15 15 15
3 10.6 17.5 20 20
5 16.7 25 30 35
7.5 24.2 40 45 50
20** 59.4 90 N/A N/A
Low-Peak CUBEFuse
Time-Delay (Amp Rating)
Motor Motor1Optimal Code Heavy
Voltage Size (Hp) FLA (Amps) Protection Max Start
0.5 2.2 666
0.75 3.2 666
1 4.2 10 10 10
230Vac, 1.5 6 10 15 15
3-Phase 2 6.8 15 15 15
3 9.6 15 20 20
5 15.2 25 30 30
7.5 22 35 40 45
20** 54 90 100 N/A
0.5 1.1 333
0.75 1.6 333
1 2.1 666
1.5 3666
2 3.4 666
460Vac, 3 4.8 10 10 10
3-Phase 5 7.6 15 15 15
7.5 11 17.5 20 20
10 14 25 25 30
15 21 35 40 45
20 27 40 50 60
50** 65 100 N/A N/A
0.5 0.9 333
0.75 1.3 333
1 1.7 333
1.5 2.4 666
575Vac, 2 2.7 666
3-Phase 3 3.9 6 10 10
5 6.1 10 15 15
7.5 9 15 20 20
10 11 17.5 20 20
40** 41 70 80 80
Note: Use Code Max column for low to moderate reverse/jog/plug
applications. Heavy Start permitted only if Code Max does not allow motor
start-up.
*Based on motor FLA from NEC®tables 430.248 and 430.250.
**Max. Hp rating for the CCPB 100 Amp device at specified voltage.
1212 BU-SB101428 Form No.CCP Page 7 of 12 Data Sheet 1157
Compact Circuit Protector (CCP) Accessories
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
Accessories for use with Class CC, Midget, IEC 10x38 and CUBEFuse CCP
CCP Version Bradly Pin-Out P/N Ideal P/N Generic Brand
Class CC, Midget, IEC 10x38 90844 44-779 N/A
CUBEFuse N/A N/A 4mm Shank Lock
Recommended Lockout Devices
Minimum Circuit Agency
Catalog Number Description Configuration Signal Output Voltage Approvals
Auxiliary Contacts NO+NC UL 98 Recognized and
CCP-AUX* for Switch Status 1 per CCP 5A/240Vac cURus 22.2 No. 4-04,
up to 60A IEC 60947-5-1 AC15
CCP-PLC-IND* Wired Remote Fuse Indication 1 per CCP 24Vdc 100Vac UL 98 Recognized and
for PLC Applications cURus 22.2 No. 4-04
up to 60A
CCPHM-RXX** Rotary Handle Mechanism 3-Pole CCP ––UL 98 Recognized
CCPHM-FXX** Flex Shaft Handle Mechanism 3-Pole CCP ––UL 98 Recognized
*Cannot be used with rotary or flange handle mechanism. (CLPHM-_XX)
**Refer to Product Profile #3178.
CCP-AUX CCP-PLC-IND
(Includes spade terminals)
CCPHM-RXX CCPHM-FXX
Auxiliary Contact
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
1212 BU-SB101428 Form No.CCP Page 8 of 12 Data Sheet 1157
CCP-AUX installed on a CCP-3-xx
Description
NO+NC contact output to indicate the status of the switching
mechanism on the CCP
Specifications:
Rated Ampacity: 5A
Rated Voltage: 240Vac
NC/NO contacts are closed/open when the CCP switch
is in the “ON” position (closed)
Flammability Rating: UL 94V0
For use with up to and including 100A CCP
Agency Information:
UL 98 File E155130, Guide WHTY2
cULus to CSA Standard 22.2 No. 4-04
IEC 60947-5-1
Wiring:
20-16 AWG (1 to 2.5mm2) wire
Torque 5 Lb-In (0.68N•m)
For use with only 75°C Cu wire
Packaging:
The CCP-AUX is packaged individually
A single unit is capable of mounting to a
1-, 2-, or 3-pole CCP
Installation Technique:
Mounts on the right side of the CCP, and mechanically
interlocks with the CCP switch handle with hardware
provided. Cannot be used with rotary or flange handle
mechanism.
IP20 Rating: Yes
Environmental Data:
Storage and Operating Temperature: -20°C to 75°C
Catalog Numbers:
1-60A: CCP-AUX
70-100A: CCP-AUX-100
De-energize all circuits before installing or removing any CCP-AUX devices and follow all prescribed safety procedures.
1212 BU-SB101428 Form No.CCP Page 9 of 12 Data Sheet 1157
Remote Fuse Monitoring Accessory
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
Description
A resetable three-phase remote fuse monitor that
integrates with a Programmable Logic Controller (PLC) or
other monitoring and control equipment
Specifications:
Power Input: 24Vdc, 8A
Output Signals: Digital 0Vdc (Low), 24Vdc (High)
- 0Vdc Low – Fuse is good
- 24Vdc High – Fuse has opened
When the fuse opens, the output signal is sent high and will
remain high until the unit is reset
Rated Impulse Voltage: 8kV
Local Indication: Two distinct LEDs indicate unit power
(green) and open fuse (red). Open fuse LED is resetable
upon the replacement of the fuse and the actuation of the
reset switch
Flammability Rating: UL 94V0
For use with up to and including 100A CCP
Wiring:
For power, signal and ground connections use 22-24AWG
(0.25mm2) 300V rated wire
Emissions and Immunity Testing:
Electrostatic Discharge IEC 61000-4-2
Electrical Fast Transient/Burst IEC 6100-4-4
Surge Immunity IEC61000-4-5
Packaging:
The CCP-PLC-IND is packaged individually
A single unit monitors up to three phases. Package includes
0.110” (2.8mm) quick connects for power, signal and ground
connections
Minimum Circuit Voltage:
Minimum circuit voltage required across the CCP is 100Vac
for the remote indication device to operate
Installation Technique:
Mounts on the left side of the CCP and mechanically
interlocks with the CCP switch handle with hardware
provided. Cannot be used with rotary or flange handle
mechanism.
IP20 Rating: Yes
Environmental Data:
Storage and Operating Temperature: -20°C to 75°C
Agency Information:
UL 98 File E155130, Guide WHTY2
cULus to CSA Standard 22.2 No. 4-04
PLC Programming:
The CCP-PLC-IND signal line is designed to provide a
digital input to a PLC I/O card. In this case, a
Programmable Logic Control program must be written to
properly interpret the input signal to the PLC. The PLC
program should check for consecutive high signals before
taking action on a critical process.
Catalog Numbers:
1-60A: CCP-PLC-IND
70-100A: CCP-PLC-100
PWR
GND
SIG
24V
CCP-PLC-IND installed on a CCP-3-xx
De-energize all circuits before installing or removing any CCP-PLC-IND devices and follow all prescribed safety procedures.
Connections for CCP-PLC-IND from a CCP-3 to a remote monitoring device
Connection from CCP-PLC-IND to CCP
Connect leads from CCP-PLC-IND to the terminals as
shown. There is a dedicated terminal on the CCP to
accept the spade connectors from the CCP-PLC-IND.
NOTE: When monitoring a 1-pole or 2-pole CCP, trim
unused leads.
Circuit Monitoring
Leads from CCP-PLC-IND
to CCP (100Vac – 600Vac)
Circuit Monitoring Leads
from PLC or Remote
Monitoring Device.
1212 BU-SB101428 Form No.CCP Page 10 of 12 Data Sheet 1157
Remote Fuse Monitoring Accessory CCP-PLC-IND
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
Compact Circuit Protector (CCP)
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
1212 BU-SB101428 Form No.CCP Page 11 of 12 Data Sheet 1157
3.1 (79.8)
3.7 (92.7)
1.9 (49.2)
1.8 (45)
0.7 (17.5)
1.4 (35)
2.1 (52.5)
CCP with CUBEFuse - 30 – 60A
CCP with CUBEFuse - 100A
74.09
[2.917]
67.74
[2.667]
147.05
[5.790]
56.62
[2.229]
80.29
[3.161]
91.19
[3.590]
25.15 ±0.38
[0.990 ±0.015]
Dimensions - in (mm)
CCP for Class CC, Midget and IEC 10x38
Compact Circuit Protector (CCP)
UL Class CC, Midget and IEC 10x38 fuses, and CUBEFuse
1112 BU-SB101428 Form No.CCP Page 12 of 12 Data Sheet 1157
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by
definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design
applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any prod-
ucts. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been select-
ed, it should be tested by the user in all possible applications.
CCP-AUX - 30 – 60A
CCP-PLC-IND - 30 – 60A
3.7 (92.7)
1.9 (49.2)
2.6 (66.6)
1.8 (45)
0.3 (8.7)
82.64 ±0.38
[3.254 ±0.015]
41 NC
33 NO 34 NO
42 NC
strip
4.83
[0.190]
92.71
[3.650]
56.61
[2.229]
13.88 ±0.38
[0.546 ±0.015]
15.88 ±0.25
[0.625 ±0.010]
8.75 ±0.25
[0.344 ±0.010]
3.7 (92.7)
2.6 (66.6)
1.9 (49.2)
45
1.8
0.3 (8.7)
2T1
4T2
6T3
1L1
3L2
5L3
+24vDC
ON
RESET
GND
SIG
STATUS
+24vDC
CCP-PLC-IND - 100A










 
74.09
[2.917]
56.62
[2.229]
81.79
[3.220]
92.96
[3.660]
81.33
[3.202]
82.66
[3.254]
16.14 ±0.38
[0.635 ±0.015]
14.14 ±0.38
[0.635 ±0.015]
© 2012 Cooper Bussmann
www.cooperbussmann.com
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Cooper Bussmann:
CCP-1-60CF CCP-2-60CF CCP-2-100CF CCP-3-60CF CCP-1-30CF CCP-2-30CF CCP-3-30CF CCP-1-100CF