1
General-purpose Relay
MY
An Improved Miniature Power Relay with
Many Models for Sequence Control and
Power Applications
A wide range of relay variations including ones with operation
indicators, built-in diodes, etc.
Arc barrier standard on 3- and 4-pole Relays.
Dielectric strength: 2,000 VAC.
LR
Ordering Information
List of Models
Type Contact form
Plug-in socket/solder terminals
PCB terminals
Upper-mounting/
solder terminals
W
ith indicator
Standard DPDT MY2 MY2N MY2-02 MY2F
DPDT (bifurcated)
MY2Z MY2ZN MY2Z-02 MY2ZF
3PDT MY3 MY3N MY3-02 MY3F
4PDT MY4 MY4N MY4-02 MY4F
4PDT (bifurcated)
MY4Z MY4ZN MY4Z-02 MY4ZF
W
ith built-in diode
DPDT MY2-D MY2N-D2 ––– –––
(DC only)
DPDT (bifurcated)
MY2Z-D MY2ZN-D2 ––– –––
3PDT MY3-D MY3N-D2 ––– –––
4PDT MY4-D MY4N-D2 ––– –––
4PDT (bifurcated)
MY4Z-D MY4ZN-D2 ––– –––
With built-in CR DPDT MY2-CR MY2N-CR –––
Not available.
(AC only)
DPDT (bifurcated)
MY2Z-CR ––– –––
3PDT MY3-CR ––– –––
4PDT MY4-CR MY4N-CR –––
4PDT (bifurcated)
MY4Z-CR ––– –––
W
ith test button
DPDT MY2I4 MY2I4N ––– –––
4PDT MY4I4 MY4I4N ––– –––
Rated coil voltage
Note: 1.
When ordering, add the rated coil voltage to the model number
. Rated coil voltages are given in the coil ratings table.
Example: MY2, 6 V
AC
2.
The standard contacts for MY2Z-series Relays and for the MY4Z are gold-plated.
MY MY
2
Accessories (Order Separately)
Sockets
Poles Front-mounting
socket
Back-mounting socket
(DIN-rail/screw mounting)
Solder terminals
W
ire-wrap terminals
PCB
W/ clip
W/o clip
W/ clip
W/o clip
terminals
2
PYF08A
PYF08A-E (finger protection)
PYF08A-N (finger protection)
PY08 PY08-Y1 PY08QN PY08QN-Y1 PY08–02
3PYF1
1A
PY11 PY11-Y1 PY11QN PY11QN-Y1 PY11-02
4
PYF14A
PYF14A-N (finger protection)
PYF14A-E (finger protection)
PY14
PY14-3*
PY14-Y1 PY14QN PY14QN-Y1 PY14-02
Note: *1.
Equipped with operation check terminal.
2.
The PYF08A(-E), PYF1
1A, and PYF14A(-E) have been approved as individual sockets by UL S08 and CSA C22.2.
Mounting Plates for Sockets
Socket
model For 1 socket
For 18 sockets For 36 sockets
PY08, PY1
1, PY14, PY08QN(2),
PY11QN(2), PY14QN(2)
PYP-1 PYP-18 PYP-36
Note:
PYP-18 and PYP-36 can be cut into any desired length in accordance with the number of sockets.
Socket Hold-down Clip Pairing
Relay
type
Poles Front-connecting
sockets
Back-connecting sockets
(rail-/screw-mounted) Solder/wire-wrap
terminals
PCB
terminals
Socket Clip Socket Clip Socket Clip
Standard, bifurcated contacts, operation
indicator,
built-in diode.
2
PYF08A-N,
PYF08A-E,
PYF08A
PYC-A1 PY08(QN) PYC-P PY08(QN) PYC-P
3 PYF11A PY11(QN) PY11(QN)
4 PYF14A-N,
PYF14A-E,
PYF14A
PY14(QN) PY14(QN)
T
est button
2
PYF08A-N,
PYF08A-E,
PYF08A
PYC-A1 PY08(QN) PYC-P2 PY08(QN) PYC-P2
3 PYF11A PY11(QN) PY11(QN)
4 PYF14A-N,
PYF14A-E,
PYF14A
PY14(QN) PY14(QN)
CR circuit
2
PYF08A-N,
PYF08A-E,
PYF08A
Y92H-3 PY08(QN) PYC-1 PY08(QN) PYC-1
3 PYF11A PY11(QN) PY11(QN)
4 PYF14A-N,
PYF14A-E,
PYF14A
PY14(QN) PY14(QN)
MY MY
3
Specifications
Coil Ratings
Rated
voltage
Rated current
Coil
resistance
Inductance
(reference value)
Must
operate
Must
release
Max.
voltage
Power
consum.
(A )
50 Hz 60 Hz
es sta ce
Arm.
OFF
Arm. ON
% of rated voltage
co su
(Approx.)
AC
6 V
214.1 mA
183 mA
12.2
:
0.04 H 0.08 H
80% 30% 110%
1.0 to
12V
A
12 V
106.5 mA
91 mA
46
:
0.17 H 0.33 H
max. min.
1.2 V
A
(60 Hz)
24 V
53.8 mA
46 mA
180
:
0.69 H 1.30 H
(60 H
z
)
50 V
25.7 mA
22 mA
788
:
3.22 H 5.66 H
100/1
10 V
1
1.7/12.9 mA
10/1
1 mA
3,750
:
14.54 H
24.6 H
0.9 to
11V
A
1
10/120 V 9.9/10.8 mA 8.4/9.2 mA
4,430
:
19.20 H
32.1 H
1.1 V
A
(60 Hz)
200/220 V
6.2/6.8 mA 5.3/5.8 mA
12,950
:
54.75 H 94.07 H
(60 H
z
)
220/240 V
4.8/5.3 mA 4.2/4.6 mA
18,790
:
83.50 H
136.40 H
DC
6 V
150 mA
40
:
0.17 H 0.33 H
10%
0.9 W
12 V
75 mA
160
:
0.73 H 1.37 H
min.
24 V
36.9 mA
650
:
3.20 H 5.72 H
48 V
18.5 mA
2,600
:
10.60 H 21.00 H
100/1
10 V
9.1/10 mA
1
1,000
:
45.60 H 86.20 H
Note: 1. The
rated current and coil resistance are measured at a coil temperature of 23
q
C with tolerances
of +15%/–20% for rated currents
and r
15% for DC coil resistance.
2.
Performance characteristic data are measured at a coil temperatures of 23
qC.
3.
AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power
consumption drop was measured for the above data. When
driving transistors, check leakage current and connect a bleeder
resistor
if required.
Contact Ratings
Item
Double- or three-pole
Four-pole
Resistive load
(cosf
= 1)
Inductive load
(cosf
=0.4,
L/R=7 ms)
Inductive load
(cosf
=0.4,
L/R=7 ms)
Rated load
5 A, 220 V
AC
5 A, 24 VDC
2 A, 220 V
AC
2 A, 24 VDC
3 A, 220 V
AC
3 A, 24 VDC
0.8 A, 220 V
1.5 A, 24 VDC
Carry
current
5 A 3 A
Max.
switching
voltage
250 VAC
125 VDC
250 V
AC
125 VDC
Max.
switching
current
5 A 5 A 3 A 3 A
Max.
switching
capacity
1,100 VA
120 W
440 VA
48 W
660 VA
72 W
176 VA
36 W
Min.
permissible
load*
Standard type: 100 mA, 5 VDC
Bifurcated type: 100
P
A, 1 VDC
Standard type: 1
mA, 1 VDC
Bifurcated type: 100
PA, 1 VDC
*Note:
P level:
O60
= 0.1 x 10
-6
/operation, reference value
Resistive load
(cosf
= 1)
MY MY
4
Characteristics
Item All
relays
Contact resistance
50 m
:
max.
Operate time
20 ms max.
Release time
20 ms max.
Max. operating frequency
Mechanical:
18,000 operations/hr
Electrical:
1,800 operations/hr (under rated load)
Insulation resistance
1,000 M
:
min. (at 500 VDC)
Dielectric strength
2,000 V
AC, 50/60 Hz for 1 min (1,000 V
AC
between contacts of same polarity)
V
ibration resistance
Destruction:
10 to 55 Hz, 1.0-mm double amplitude
Malfunction:
10 to 55 Hz, 1.0-mm double amplitude
Shock resistance
Destruction:
1,000 m/s
2
(approx. 100G)
Malfunction:
200 m/s
2
(approx. 20G)
Life expectancy
See following table.
Ambient operating temperature*
Single- and double-pole standard, bifurcated-contact, test-button, relays:
–55q
C to 70
q
C (with no icing)
All other relays: –55
q
C to 60
q
C (with no icing)
Ambient operating humidity
35% to 85%
Weight
Approx. 85 g
Note:
The values given above are initial values.
Life Expectancy Characteristics
Relays Mechanical
life
(at 18,000 operations/hr)
Electrical life
(at 1,800 operations/hr under rated load)
Normal,
With test button (except relays
with operation
indicator), With CR
AC
50,000,000 operations min.
DC:
100,000,000 operations min.
1-,2-,3-pole:
500,000 operations min.
4-pole:
200,000 operations min.
With operation indicator or built-in diode
AC
50,000,000 operations min.
DC:
100,000,000 operations min.
1-,2-,3-pole:
500,000 operations min.
4-pole:
200,000 operations min.
With bifurcated contacts
2-pole:
50,000,000 operations min.
4-pole:
2-pole:
200,000 operations min.
4-pole:
100,000 operations min.
Note:
See following tables for real load life expectancies.
Life Expectancies Under Real Loads
MY2
Rated
voltage
Load type
Conditions
Operating frequency
Electrical life
100 V
AC
AC motor
50 W
, 100 V
AC single-phase with
2.8-A inrush current, 0.4-A carry
current
ON for 2 s, OFF for 30 s
100,000 operations
50 W
, 100 V
AC single-phase with
1.6-A inrush current, 1-A carry current
ON for 1 s, OFF for 30 s
300,000 operations
AC solenoid
24 W with 1-A carry current ON for 1.5 s, OFF for 1.5 s
4,000,000 operations
MY4
Rated voltage
Load type
Conditions
Operating frequency
Electrical life
100 V
AC
AC solenoid
50 V
A with 2-A inrush current, 0.7A
carry current
ON for 1 s, OFF for 3 s
25,000 operations
DC magnetic
switch
25 W with L/R = 40 ms , 0.2-A carry
current
AC magnetic
switch
35 V
A with 1.5-A inrush current,
0.35-A carry current
500,000 operations
24 VDC
DC solenoid 40 W with L/R = 10 ms, 1.6-A carry
current
ON for 0.5 s, OFF for 1.5 s
5,000,000 operations
30 W with L/R = 10 ms with 0.34-A
carry current
ON for 0.5 s, OFF for 1.5 s
6,000,000 operations
MY MY
5
Approved by Standards
Some MY Relays are available in models meeting various safety
standards.
When ordering, you must specify
the desired standards.
Refer
to
Ordering Information
for specific models. Note that the rat
-
ing recognized by the various standards sometimes vary from the
ratings
of the individual relays.
UL 508 Recognitions (File No. 41515)
No.
of poles
Coil ratings Contact ratings
2
6 to 240 V
AC
6 to 125 VDC
5 A, 120 V
AC resistive load
5 A, 28 VDC resistive load
5 A, 240 V
AC inductive load
3
5 A, 28 VDC resistive load
5 A, 240 V
AC inductive load
4
6 to 240 V
AC
6 to 125 VDC
3 A 28 VDC resistive load
3 A 120 V
AC inductive load
1.5 A, 240 V
AC inductive load
5 A, 240 V
AC inductive load
(between contacts of same
polarity)
5 A, 28 VDC resistive load
(between contacts of same
polarity)
0.2 A, 120 VDC
CSA 22.2 No. 0 and No.14 (File No. LR31928)
Model No.
of
poles
Coil
ratings
Contact ratings
MY
2, 3 6 to 240
VAC
6 to 120
VDC
5 A, 28 VDC resistive
load
5 A, 240 V
AC inductive
load
43 A, 28VDC resistive
load
3 A, 240 V
AC inductive
load
5 A, 240 V
AC inductive
load (between contacts
of same polarity)
5 A, 28 VDC resistive
load (between contacts
of same polarity)
0.2 A, 120 VDC
LR (No. 563KOB-204524)
Model No.
of
poles
Coil
ratings
Contact ratings
MY -LR 2
6 to 240
VAC
6 to 120
VDC
2 A, 30 VDC inductive
load
2 A, 200 V
AC inductive
load
4
1.5 A, 30 VDC
inductive load
0.8 A, 200 V
AC
inductive load
1.5 A, 1
15 V
AC
inductive load
Engineering Data
Maximum Switching Capacity
MY2, MY3
Switching
voltage (V)
Switching current (A)
AC resistive load
DC resistive
load
DC inductive
load (L/R = 7 ms)
AC inductive load
(cosf
= 0.4)
MY MY
6
MY4, MY4Z
Switching
voltage (V)
Switching current (A)
AC resistive
load
DC resis-
tive load
DC Inductive
load
L/R = 7 ms
AC inductive load
(cosf
= 0.4)
Life Expectancy
Switching current (A)
MY2, MY3 (Inductive Loads)
Switching current (A)
MY2, MY3 (Resistive
Loads)
110 VAC resistive load
220 VAC
resistive load
24 VDC resistive
load
24 VDC inductive load
(L/R = 7 ms)
110 VAC inductive
load (cosf
= 0.4)
220 VAC in-
ductive load
(cosf
= 0.4)
Life expectancy (x10 operations)
3
1,000
500
100
5,000
Life expectancy (x10 operations)
3
1,000
500
100
5,000
Switching current (A)
MY4 (Inductive Loads)
Switching current (A)
MY4 (Resistive Loads)
110 VAC resistive
load
30 VDC resistive
load
220 VAC resis-
tive load 110 VAC Inductive
load
220 VAC Inductive
load 30 VDC Inductive
load
Life expectancy (x10 operations)
3
1,000
500
100
5,000
Life expectancy (x10 operations)
3
1,000
500
100
5,000
Switching current (A)
MY4Z (Inductive Loads)
Switching current (A)
MY4Z (Resistive Loads)
220 VAC resis-
tive load
24 VDC resistive load
110 VAC (cosf
= 0.4)
24 VDC
L/R = 7 ms
220 VAC (cosf
= 0.4)
Life expectancy (x10 operations)
3
1,000
500
100
5,000
Life expectancy (x10 operations)
3
1,000
500
100
5,000
MY MY
7
Dimensions
Note: All
units are in millimeters unless otherwise indicated.
Relays with Solder Terminals
2.6
MY2, MY2N, MY2N-D2
Eight, 1.2 dia. x 2.2 ellipse holes
0.5
0.5
6.4
21.5
max.
6.3
28 max.
MY2N
Standard DC
type
AC type
Note: 1. AC type is equipped with a coil disconnection
self–diagnostic
function.
2.
Pay due attention as DC type has polarity
.
36
max.
MY2N-D2
MY3, MY3N, MY3N-D2,
2.6
Eleven, 1.2 dia. x 2.2
ellipse holes
0.5
36
max.
6.4
28 max.
6.3
21.5
max.
MY3N
Standard DC
type
AC type
Note: 1. AC
type is equipped with a coil disconnection self–
diagnostic
function.
2.
Do not reverse the polarity of DC relays.
MY3N-D2
MY MY
8
MY4
2.6
Fourteen, 1.2 dia. x 2.2
ellipse holes.
0.5
0.5
36
max.
6.4
21.5
max.
28 max.
6.3
Terminal arrangement/internal connections
(bottom view)
MY4N
Standard DC
type
AC type
Note: 1. AC
type is equipped with a coil disconnection self-
diagnostic function.
2.
Do not reverse the polarity of DC relays.
MY4N-D2
MY I4
2.6
Fourteen, 1.2 dia. x 2.2
ellipse holes
3.3
20.3
36
max.
0.5
6.4 21.5 max..
6.3
28 max.
3 max.
Push button
Note: 1. Mount
the relay with a socket.
2. T
est button
I4:
AC with red push button
DC with blue push button
Note:
The terminal arrangement and internal connections of the above relays are as same as these of MY
relays.
MY MY
9
MY (N)-CR, MY (Z)-CR
2.6
Fourteen, 1.2 dia. x 2.2 ellipse holes
0.5
0.5
53
max.
6.4
28 max.
6.3
21.5
max.
MY (N)-C
R
CR
MY (Z)-C
R
CR
Relays with PCB Terminals
MY -02
MY4-02 (4PDT)
3.5
3.3 (2.6)
0.5
0.5
4
6.3
DPDT 3PDT 4PDT
13.2 13.2 13.2
4.3
6.3
4.4
4.1
12.65
6.35
3.75
1
36 max.
28 max.
Note: 1. The figures in the parentheses are for MY4-02.
2. The above dimensions also apply to the DPDT and
3PDT Relays.
3. The internal connections of the above Relays are as
same as these of MY@ Relays.
PC Board Mounting Holes
Eight,
1.3r0.1
holes
Eleven,
1.3r0.1
holes
Fourteen,
1.3r0.1
holes
Note: The tolerance is r0.1.
21.5
max.
MY MY
10
Upper-mounting Relays
MY F MY4F
2.6
Fourteen, 1.2 dia. x 2.2
ellipse holes
0.5
6.4
0.5
36
max
.
24.35
29 max. 38 44 max.
3.5
22.5 max.
Note: 1. The above dimensions also apply to the DPDT,
and 3PDT relays.
2. The
internal connections of
the above relays are as
same
as these of MY
relays.
Mounting holes
Two 3.5 dia holes or M3 holes
38
Mounting Height with Socket
Note: 1. The
PTF-A can be rail–mounted or screw-mounted.
2. For
the MY
-CR (CR circuit built-in type) model, figure
in
the parentheses apply
.
3.
PYC-P hold down clip should be used with PYF08M.
70 (87) 66 (83)
MY
39 (56) MY
PY@
DIN Track/Surface-mounting Socket Back-mounting Socke
t
PYF A(-E)
MY MY
9
Sockets
PYF08A-E PY08 PY08-Y1 PY08QN
PY08-02
PYF08APYF08A-N
PY14 PY14QN(2)PY14-Y1PYF14A-N
PYF14A-E
PY14QN(2)-Y1 PY14-02
PY11-02
PY11 PY11QN(2) PY11QN(2)-Y1
PYF11A
MY MY
12
Mounting Plates for Sockets
27.4
r0.15
21.6
72 wide ellipse
hole
27.4
r0.15
21.6
492
17 x 27.4 = 465.8 r
0.6
72 wide el-
lipse hole
4.5
3.4
13.1
42r0.1 49
t = 1.6
492
17 x 27.4 = 465.8 r
0.6
4.5
3.4
R1.7
13.1
21.4 +0.2
0
39.7r0.2
39.7r0.2
21.6
13.1
17 x 27.4 = 465.8 r
0.6
t = 1.6
86.4
Two, 3.4 dia. holes
42
r0.1 49
21.4 +0.2
0
28
t = 1.6
PYP-1
Square
hole
63-PYP81-PYP
Hold-down Clips
Hold-down
clips are used to hold relays to sockets and prevent them from coming loose due to vibration or shock.
Connection to socket
Connection to
mounting plate
For relays with test
buttons
For relays with CR circuits
PYC-A1 PYC-P PYC-S PYC–P2 Y92H-3 PYC-1
+0.3
–0
36
+0.3
–0
77.5 +0
–0.4
PY14-3 (for 4PDT)
with operation check terminal
Operation check terminal
81
56
28
38.5
2
9(7.7)
0.3 34.5+0.4
Operation checklamp can be built-in.
Three, 1.2 dia holes Two dia. holes Short-circuit lead wire
Mounting holes
78
Safety Standards for Sockets
Item Standards File No.
PYF08A (-E), PYF1
1A UL508 E87929
PYF14A (-E) CSA22.2 LR31928
MY MY
13
Precautions
Connections
Do not reverse polarity when connecting DC-operated relays with
built-in
diodes or indicators DC-operated relays.
Mounting
tWhenever possible, mount relays so that it is not subject to
vibration or shock in the same direction as that of contact
movement.
tThe test button should be be pointed upwards when mounting
(refer
to the right figure).
T
est button
In the interest of product improvement, specifications are subject to change without notice.
Cat. No. J01P-E-01
Singapore
0410
Authorized Distributori
Asia Pacific Head Office:
OMRON ASIA PACIFIC PTE. LTD.
438A Alexandra Road
#05-05/08
(Lobby 2) Alexandra Technopark
Singapore 119967
Tel: (65) 6835 3011 Fax: (65) 6835 2711
E-mail: ask@ap.omron.com
Website: www.omron-ap.comeb .omr n
Singapore Office:
OMRON ELECTRONICS PTE. LTD.
438A Alexandra Road, #05-05/08
(Lobby 2) Alexandra Technopark
Singapore 119967
Tel: (65) 6547 6789
Fax: (65) 6547 6769
E-mail: mktg_sg@ap.omron.com
Malaysia Office:
OMRON ELECTRONICS SDN. BHD.
1101 Level 11 Uptown 1
1 Jalan SS21/58 Damansara Uptown
47400 Petaling Jaya, Selangor
Malaysia
Tel: (60-3) 7688 2888
Fax: (60-3) 7688 2833
E-mail: my_enquiry@ap.omron.com
Thailand Office:
OMRON ELECTRONICS CO. LTD.
Rasa Tower 20th Floor
555 Phaholyothin Road
Chatuchak, Bangkok
10900, Thailand
Tel: (66-2) 937 0500
Fax: (66-2) 937 0501
CRM Call Centre: (66-2) 942 6700
E-mail: th_enquiry@ap.omron.com
Australia Offices:
Sydney Office:
OMRON ELECTRONICS PTY. LTD.
Omron House
71 Epping Road, North Ryde
Sydney, New South Wales 2113
Australia
Tel: (61-2) 9878 6377
Fax: (61-2) 9878 6981
Toll Free: 1800 678838
E-mail: au_enquiry@ap.omron.com
Melbourne Office:
OMRON ELECTRONICS PTY. LTD.
Axxess Corporate Park
Unit 98, 45 Gilby Road
Mt Waverley Victoria 3149
Australia
Tel: (61-3) 8588 2600
Fax: (61-3) 8588 2690
E-mail: au_enquiry@ap.omron.com
Brisbane Office:
OMRON ELECTRONICS PTY. LTD.
Unit 14, 1378 Lytton Road
Hemmant 4174, Queensland
Australia
Tel: (61-7) 3859 3900
Fax: (61-7) 3348 8701
E-mail: au_enquiry@ap.omron.com
Adelaide Office:
OMRON ELECTRONICS PTY. LTD.
Suite 12, 18 Humpheries Terrace
Kilkenny, SA 5009
Australia
Tel: (61-8) 8440 6412
Fax: (61-8) 8345 1204
E-mail: au_enquiry@ap.omron.com
New Zealand Office:
OMRON ELECTRONICS LTD.
65 Boston Road, Mt Eden
Private Bag 92620
Symonds Street, Auckland
New Zealand
Tel: (64-9) 358 4400
Fax: (64-9) 358 4411
E-mail: nz_enquiry@ap.omron.com
Indonesia Office:
PT. OMRON ELECTRONICS
Graha Pratama Building, 3A Floor
Jl. M.T. Haryono Kav 15
Jakarta Selatan 12810
Indonesia
Tel: (62-21) 8370 9555
Fax: (62-21) 8370 9550
E-mail: id_enquiry@ap.omron.com
Philippines Office:
OMRON ASIA PACIFIC PTE. LTD.
MANILA REPRESENTATIVE OFFICE
2nd Floor, Kings Court II Building
2129 Do Chino Roces Avenue
Corner Dela Rosa Street
1231 Makati City, Metro Manila
Philippines
Tel: (63-2) 811 2831
Fax: (63-2) 811 2583
E-mail: ph_enquiry@ap.omron.com
Vietnam Offices:
OMRON ASIA PACIFIC PTE. LTD.
HANOI REPRESENTATIVE OFFICE
6th Floor, 92 Hoang Ngan Street
Trung Hoa, Cau Giay
Hanoi, SR Vietnam
Tel: (84-4) 3556 3444
Fax: (84-4) 3556 3443
E-mail: hn_enquiry@ap.omron.com
HO CHI MINH REPRESENTATIVE OFFICE
99 Nguyen Thi Minh Khai Street
District 1, Ho Chi Minh City
SR Vietnam
Tel: (84-8) 3839 6666
Fax: (84-8) 3830 1279
E-mail: hcm_enquiry@ap.omron.com
India Offices:
Bangalore Office:
OMRON AUTOMATION PVT. LTD.
No. 43, G.N. Complex
St.Johns Road
Bangalore - 560 042
India
Tel: (91-80) 4072 6400/401
Fax: (91-80) 4146 6403
E-mail: in_enquiry@ap.omron.com
Noida Office:
OMRON AUTOMATION PVT. LTD.
212 & 213, 2nd Floor
International Home Deco Park (IHDP)
Plot No.7, Sector 127, Taj Express Way
Noida 201301
India
Tel: (91-120) 4745 800
Fax:(91-120) 4745 801
E-mail: newdelhi_enquiry@ap.omron.com
Mumbai Office:
OMRON AUTOMATION PVT. LTD.
102 & 103, Meadows, Sahar Plaza,
Andheri-Kurla Road, Andheri East
Mumbai - 400 059
India
Tel: (91-22) 4275 5600
Fax: (91-22) 4275 5602
E-mail: mumbai_enquiry@ap.omron.com